28
Code Defect function Check method
F 1 (FRZ.) F-sensor
R 1 (REF.) R1-sensor
R 2 (Q.R) R2-sensor
D 1 (E.R) D-sensor
RT (E.R) RT-sensor
D 0 (1 Fridge) Door switch
C 1 (2 Fridge) Cooling cycle
(check after first
defrost mode)
F 3 (3 Fridge) Heater
3) Self-diagnosis table
➧
If both R1 and R2-sensor are out of order, then RT-sensor control R-fan.
- Room temperature
≤
14˚C : R-fan is off
- Room temperature
≥
26˚C : R-fan is on for 15 minutes, R-fan is off for 5 minutes
- 14˚C < Room temperature < 26˚C : R-fan is on for 2 minutes, R-fan is off for 18 minutes
- Compressor & F-fan is on for 24 minutes.
- Compressor & F-fan is off for 16 minutes.
- Regarded by R2-sensor.
- Detecting weak cooling is impossible.
- Heater is on only for 35 minutes.
- Natural defrost for 80 minutes.