Dacor Renaissance RNTT365GB Planning Manual Download Page 2

All specifications subject to change without notice.

Phone: (800) 793-0093

www.dacor.com

PLANNING

GUIDE

4.39

RNTT365GB

Renaissance 36” Wide

Drop-in,Touch-Control Gas Cooktop

Document # PG04-010

Revised 09/02/15   Page 2/5

Gas Supply Requirements

◊ 

Be certain that the cooktop being installed is correct for the 

gas service being provided (natural gas or LP gas). Units 

equipped for LP operation have “LP” in the model number 

listed on the model/serial number label. See the diagram 

below for label location.

◊ 

Check your local building codes for the proper method of 

installation. In the absence of local codes, this appliance 

should be installed in accordance with the National Fuel Gas 

Code ANSI Z223.1/NFPA 54.

◊ 

An external manual shut-off valve must be installed between 

the gas inlet and the cooktop in an easily accessible location 

for the purpose of controlling the  gas supply to the appliance.

◊ 

The cooktop comes from the factory with a regulator in 

the shipping carton. Use only the regulator provided. The 

regulator must be installed in the gas line that runs from the 

cooktop gas inlet to the gas shut off valve.

◊ 

The regulator inlet accommodates a 1/2” gas line. The inlet 

to the cooktop itself is equipped with a metric fitting. A brass 

metric to 1/2” NPT adapter is included for connecting the 

regulator to the appliance.

The cooktop gas connection is located on the bottom of the 

cooktop in the back left corner as you face the front of the unit. See 

page 3 for location.

RNTT365GB

RNTT365GBLP

Gas Type

Natural Gas

LP Gas

Manifold 

Pressure

4” water  

column

11” water 

column

Min. Gas Supply 

Pressure **

5” water  

column

12” water 

column

Max. Gas Supply 

Pressure

1/2 psi

1/2 psi

Total Connected 

Load

0.5 Amp.

(0.03 kW)

0.5 Amp.

(0.03 kW)

Circuit  

Requirement

120 Vac,

60 Hz, 15 Amp.

120 Vac,

60 Hz, 15 Amp.

Gas and Electrical Requirements*

The electrical and gas data on this page is for reference only. If 

the above data does not agree with the product specification label, 

use the data on the product specification label.
** The gas supply pressure for testing the regulator setting shall be 

at least 1-inch water column (249 Pa) above the specified manifold 

pressure.

Flexible gas 

line with fitting

Pressure  

regulator

Brass NPT 

adapter  

Fiber gasket

Gas inlet

Cooktop

(not included)

1/2”  NPT  

Gas Line Parts Installation

 

 WAR

WARNING

NING

•  Verify that the gas supply meets specifications before 

connection. See page 4.

•  Do not install or use the cooktop without the included gas 

regulator installed.

•  Make sure that the arrow on the regulator points in the 

direction of the gas flow, towards the cooktop.

•  Do not apply excessive pressure when tightening gas 

connections and fittings.

•  Do not use Teflon tape or plumber’s putty on flexible gas line 

connections.

•  Test the gas lines for leaks as instructed before use. Do not 

use a flame to check for leaks. 

•  The maximum gas supply pressure to the regulator must 

never exceed 1/2 pounds per square inch (psi) or 3.5 kPa.

•  The cooktop and shut-off valve must be disconnected from 

the gas supply piping system during any pressure testing 

exceeding 1/2 psi (3.5 kPa).

•  The cooktop must be isolated from the gas supply piping 

system by closing the shut-off valve to the cooktop during 

any gas supply piping system pressure testing equal to or 

less than 1/2 psi (3.5 kPa).

•  For LP gas installations, the LP gas tank must have its own 

high-pressure regulator in addition to the pressure regulator 

supplied with the cooktop.

These

parts

are

included

Reviews: