Dacor REMP3 Installation Instructions Manual Download Page 7

5

Installation Preparation

1.  Prepare the mounting surface and reinforce it if neces-

sary according to the 

Blower Location and Mounting

 

specifications on the facing page.

2.  Make a cutout in the center of the mounting location 

according to 

Figure 1

 on the facing page.

Installation Requirements

Exhaust, no obstructions 

within 15” (38 cm)

Roof

Wall

Blower

Blower

Duct and wiring passing 

through cutout

Example of Roof 

Installation

Example of Wall 

Installation

Figure 3: Installation with Roof Curb (for flat roofs)

Roof curb

Blower 

exhaust

Prevailing 

wind

33 1/2”

(85.1 cm)

2”

(5.1 cm)

26"

(66.0 cm)

30 1/2”

(77.6 cm)

6”

(15.2 cm)

2”

(5.1 cm)

REMP16 Roof Curb

25 1/2"

(64.8 cm)

2"

(5.1 cm)

19"

(48.3 cm)

23 ¼"

(59.1 cm)

6"

(15.2 cm)

2"

(5.1 cm)

REMP3 Roof Curb

Figure 4

Figure 2

3.  On roofs with a pitch of 2:12 or less, construct a roof 

curb according to the specifications below. Attach it to 

the mounting surface and seal it around the base.

NOTE:

 Range hood installations with a very short 

duct run are not recommended due to noise. When a 

range hood installation can accommodate a short duct 

run, Dacor instead recommends installation of a range 

hood with an integral blower instead of using a REMP 

series blower.

Summary of Contents for REMP3

Page 1: ...Rev J Suitable for use in a household cooking area Suitable for use with solid state controls To complete this blower a Dacor hood assembly or Dacor downdraft vent must be purchased separately See the...

Page 2: ...fully before you begin the installation process Leave these installation instructions with the customer Customer Keep these installation instructions for future reference and the local electrical insp...

Page 3: ...S OBSERVE THE FOLLOWING a Use this unit only in the manner intended by the manufacturer If you have questions contact the manufacturer b Before servicing or cleaning unit switch power off at service p...

Page 4: ...n functional system complete electrical connections properly Follow the wiring diagrams carefully in the hood or in line blower installation instructions to ensure a proper installation After installa...

Page 5: ...C L C L C L C L 26 66 0 cm 32 1 4 81 9 cm 3 5 8 9 2 cm 12 1 4 31 1 cm Mounting flange 33 1 2 85 1 cm 9 1 2 24 1 cm Discharge Intake collar Power supply conduit location C L C L C L C L 24 1 4 61 6 cm...

Page 6: ...lated snow if applicable On hori zontally mounted units shield the exhaust if more than 3 8 cm of snow may accumulate on the roof Avoid installing the blower in a location where the exhaust could be e...

Page 7: ...of Curb for flat roofs Roof curb Blower exhaust Prevailing wind 33 1 2 85 1 cm 2 5 1 cm 26 66 0 cm 30 1 2 77 6 cm 6 15 2 cm 2 5 1 cm REMP16 Roof Curb 25 1 2 64 8 cm 2 5 1 cm 19 48 3 cm 23 59 1 cm 6 15...

Page 8: ...4 and meet local codes and ordinances Consult the hood or downdraft vent installation instruc tions for additional part requirements Installation 1 Before installing the blower unpack the unit and ch...

Page 9: ...to place 8 Check the wires from the blower wiring harness to make sure that they are firmly attached to the terminal according to Figure 10 Reconnect any wires that are loose Make sure all terminal sc...

Page 10: ...MP16 1000 CFM 994 8 CFM Airflow CFM Cubic feet minute Static pressure inches of water 0 1 0 2 0 3 0 4 0 5 0 100 200 300 400 500 600 700 REMP3 Blower Performance Airflow CFM Cubic feet minute Static pr...

Page 11: ......

Page 12: ...Dacor 14425 Clark Avenue City of Industry CA 91745 Phone 800 793 0093 Fax 626 403 3130 www dacor com...

Reviews: