Dacor DMT2420B Service Manual Download Page 27

25

DMT2420B
DMT2420R
DMT2420S

ABSOLUTE HUMIDITY SENSOR CIRCUIT

(1) Structure of Absolute Humidity Sensor

The absolute humidity sensor includes two thermistors
as shown in the illustration. One thermistor is housed in
the closed vessel filled with dry air while another in the
open vessel. Each sensor is provided with the protective
cover made of metal mesh to be protected from the
external airflow.

(2) Operational Principle of Absolute Humidity Sensor

The figure below shows the basic structure of an absolute
humidity sensor. A bridge circuit is formed by two
thermistors and two resistors (R1 and R2).
The output of the bridge circuit is to be amplified by the
operational amplifier.
Each thermistor is supplied with a current to keep it
heated at about 150½C (302½F), the resultant heat is
dissipated in the air and if the two thermistors are placed
in different humidity conditions they show different
degrees of heat conductivity leading to a potential
difference between them causing an output voltage from
the bridge circuit, the intensity of which is increased as
the absolute humidity of the air increases. Since the
output is very minute, it is amplified by the operational
amplifier.

(3) Detector Circuit of Absolute Humidity Sensor Circuit

This detector circuit is used to detect the output voltage
of the absolute humidity circuit to allow the LSI to control
sensor cooking of the unit.  When the unit is set in the
sensor cooking mode, 16 seconds clearing cycle occurs
than the detector circuit starts to function and the LSI
observes the initial voltage available at its AIN5 terminal.

With this voltage given, the switches SW1 to SW5 in the
LSI are turned on in such a way as to change the
resistance values in parallel with R98 ~ R102. Changing
the resistance values results in that there is the same
potential at both F-3 terminal of the absolute humidity
sensor and AIN4 terminal of the LSI. The voltage of AIN5
terminal will indicate about -2.5V. This initial balancing is
set up about 16 seconds after the unit is put in the Sensor
Cooking mode.  As the sensor cooking proceeds, the
food is heated to generate moisture by which the
resistance balance of the bridge circuit is deviated to
increase the voltage available at AIN5 terminal of the
LSI.
Then the LSI observes that voltage at AIN5 terminal and
compares it with its initial value, and when the comparison
rate reaches the preset value (fixed for each menu to be
cooked), the LSI causes the unit to stop sensor cooking;
thereafter, the unit goes in the next operation
automatically.
When the LSI starts to detect the initial voltage at AIN5
terminal 16 seconds after the unit has been put in the
Sensor Cooking mode, if it is not possible to balance the
bridge circuit due to disconnection of the absolute humidity
sensor, ERROR will appear on the display and the
cooking is stopped.

1) Absolute humidity sensor circuit

ventilation opening for sensing

Sensing part
(Open vessel)

Sensing part
(Closed vessel)

Thermistors

C

S

R3

R1

R2

+

Operational
amplifier

Output
voltage

S : Thermistor
     open vessel

C : Thermistor
      closed vessel

2

Absolute humidity (g/m  )

Output voltage

Absolute humidity vs,
output voltage characteristic

SW1

SW2

SW3

SW4

SW5

P20

P21

P22

P23

P24

 LSI

(IC1)

AIN4

AIN5

620k

300k

150k

75k

37.4k

26

23

22

50

49

24

25

47k

47k

10k

1 2 3 4

8 7 6 5

0.01uF

0.015uF

0.01uF

VA : -15V

VA : -15V

R90

C90

C91

C93

C92

S

F-2

1.8k

IC2

F-1

F-3

C

3.57k

3.32k

VC : -5V

0.1 uF

C. Thermistor in 

    closed vessel

S. Thermistor in

    open vessel

R98

R99

R96

R91

360k

R93

R92

R94

R95

D91

D90

R100

R101

R102

R97

Summary of Contents for DMT2420B

Page 1: ...IONS TO BE OBSERVED BEFORE AND DURING SERVICING TO AVOID POSSIBLE EXPOSURE TO EXCESSIVE MICROWAVE ENERGY INSIDE FRONT COVER BEFORESERVICING INSIDE FRONT COVER WARNING TO SERVICE PERSONNEL 1 MICROWAVEM...

Page 2: ...operative unit perform a microwave emission check as per the Microwave Measure ment Procedure outlined in this service manual If microwave emissions level is in excess of the specified limit contact...

Page 3: ...tage capacitor 4 Disconnect the leads to the primary of the power transformer 5 Ensure that the leads remain isolated from other components and oven chassis by using insulation tape 6 After that proce...

Page 4: ...er of the oven cavity The water container shall be a low form of 600 ml 20 oz beaker with an inside diameter of approx 8 5 cm 3 1 2 in and made of an electrically nonconductive material such as glass...

Page 5: ...is no other visible damage with the oven Servicing and repair work must be carried out only by trained service personnel DANGER Certaininitialpartsareintentionallynotgroundedandpresent a risk of elec...

Page 6: ...Defrost pad Beverage pad Set Up pad Number selection pads Easy Minute pad Stop Clear pad Start pad New Wave Cookbook pads Oven Cavity Light Yes Safety Standard UL Listed FCC Authorized DHHS Rules CFR...

Page 7: ...1 One touch door open button Push to open door 2 Door latches The oven will not operate unless the door is securely closed 3 Removable turntable support 4 Removable turntable The turntable will rotat...

Page 8: ...power transformer oven lamp etc are turned off and the generationofmicrowaveenergyisstopped Theovenwill revert to the OFF condition 6 Whenthedoorisopenedduringacookcycle themonitor switch door sensing...

Page 9: ...and humidity and calculates cooking time and variable power CookingSequence 1 TouchoneoftheSENSORpadsandthentouchtheStart pad NOTE The oven should not be operated on SENSOR immediately after plugging...

Page 10: ...LAMP WHT SECONDARY INTERLOCK SWITCH TURN TABLE MOTOR WHT A1 120V AC 60Hz N GND GRN C T FUSE RED COM SENSOR CONTROL UNIT BLK H A2 CAVITY TEMP FUSE HUMIDITY N O N C COM ORG BRN ORG WHT WHT F3 F2 F1 B2...

Page 11: ...ontacts CAUTION BEFORE REPLACING A BLOWN C T FUSE TEST THE DOOR SENSING SWITCH PRI MARY INTERLOCK RELAY RY2 RELAY RY1 SECONDARYINTERLOCKSWITCHAND MONITOR SWITCH FOR PROPER OPERA TION REFER TO CHAPTER...

Page 12: ...BA019 KIT as an assembly IMPORTANT Whenever troubleshooting is performed with the power supply cord disconnected It may in some cases be necessary to connect the power supply cord after the outer case...

Page 13: ...plugged into wall receptacle Monitor fuse blows when power cord is plugged into wall receptacle Any letters or indicators do not appear in display when power cord is first plugged into wall outlet Dis...

Page 14: ...ultymagnetronandthereisnodefectinthefollowing componentsorwiring siliconrectifier highvoltagecapacitorandpowertransformer Thistestwillrequire a 16 ounce 453cc measuring cup and an accurate mercury the...

Page 15: ...cabinet 7 Reconnect the power supply cord after the outer case is installed 8 Run the oven and check all functions NOTE Be sure to use an ohmmeter that will supply a forward bias voltage of more than...

Page 16: ...ter should indicate an open circuit with the door open and a closed circuit with the door closed If improper operation is indicated replace the door sensing switch 5 Reconnect all leads removed from c...

Page 17: ...er pad two figures or more are displayed c When touching the pads sometimes a pad produces no signal If the Key unit is defective H TOUCH CONTROL PANEL ASSEMBLY TEST 1 Disconnect the power supply cord...

Page 18: ...isconnect the power supply cord and then remove outer case 2 Open the door and block it open 3 Discharge high voltage capacitor 4 Reconnect all leads removed from components during testing 5 Re instal...

Page 19: ...ling fan motor RY2 Approx 23 0V D C Power transformer 8 Disconnect the power supply cord and then remove outer case 9 Open the door and block it open 10 Discharge high voltage capacitor 11 Reconnect a...

Page 20: ...ions 2 Followthetroubleshootingguidegivenbelow ifindicatordoesnotlightupafterabovecheckandrepairs are finished 1 Disconnect the power supply cord and then remove outer case 2 Open the door and block i...

Page 21: ...ad cooking test WARNING The oven should be fully assembled before following procedure Makesuretheovenhasbeenpluggedinatleasttwominutesbeforecheckingsensorcookoperation The cabinet should be installed...

Page 22: ...padonce thePowerLevelpadtwice theStartpadonceandthenumber pad 1 once 9 2 The control panel is in the sensor cooking operation 9 3 After approximately 25 seconds push plunger of select switch for more...

Page 23: ...e function that was requested The touch control section consists of the following units 1 Key Unit 2 Control Unit TheControlUnitconsistsofPowerUnitand LSI Unit Theprincipalfunctionsoftheseunitsandthes...

Page 24: ...rminal not used 13 Vss IN Powersourcevoltage GND 0V The power source voltage to drive LSI is input to Vss terminal 14 TxD0 OUT Data signal is output to a memory IC IC4 15 P91 OUT Clock signal is outpu...

Page 25: ...voltage to drive LSI is input to Vss terminal 47 58 A8 A19 OUT Address signal is output to IC2 and IC5 59 Vss IN Power source voltage GND 0V The power source voltage to drive LSI is input to Vss termi...

Page 26: ...or open close information to LSI Door close H level signal 5V Door open L level signal GND 85 AN5 IN Used for initial balancing of the bridge circuit absolute humidity sensor This input is an analog i...

Page 27: ...in such a way as to change the resistance values in parallel with R98 R102 Changing the resistance values results in that there is the same potential at both F 3 terminal of the absolute humidity sen...

Page 28: ...en the touch control panel and the oven itself is so short that the two can t be separated For those models check and repair all the controls sensor related ones included of the touch control panel wh...

Page 29: ...ING FOR WIRING 1 Disconnect the power supply cord 2 Make sure that a definite click can be heard when the microwave oven door is unlatched Hold the door in a closed position with one hand then push th...

Page 30: ...ment lead short one of the power transformer from the high voltage capacitor 7 Remove one 1 screw holding capacitor holder with the high voltage rectifier to the base plate 8 Disconnect rectifier term...

Page 31: ...e the LSI unit carefully so that there is no excessive force applied to the ribbon connection LSI unit 1 Disconnect the power supply cord 2 Removeturntableandturntablesupportfromovencavity 3 Lay the o...

Page 32: ...s smoothly after installation Make sure that the axis of the shaft is not slanted 5 Install the fan motor to the the oven cavity back plate with the two 2 screws 6 Connect the wire leads to the fan mo...

Page 33: ...oor sensing switch secondary interlock switch and monitorswitchdonotoperateproperlyduetoamisadjustment the following adjustment should be made 4 Loosen the two 2 screws holding latch hook to the oven...

Page 34: ...door glass into the five 5 tabs of the door frame 1 3 Slidethedoorglassleftwardsandinserttheleftedgeof door glass into the two 2 tabs of the door frame 2 Re installthedoorglassstoppertothedoorframesot...

Page 35: ...NOTE The neutral WHT GRY wire must be connected to the terminal with N mark on the power supply cord RED WHT BRN RED WHT WHT ORG WHT RED RED PNK GRN GRN to Oven cavity WHT WHT WHT WHT BLUE MARK RED CA...

Page 36: ...N BUZZR MICRO N C N C AC MICRO OVEN LAMP FAN MOTOR TURNTABLE MOTOR OVEN LAMP FAN MOTOR TURNTABLE MOTOR DOOR SENSING SWITCH NOTE IF NOT SPECIFIED 0 1 F 50V DOOR SENSING SWITCH AC120V 60Hz CN A CN C 11P...

Page 37: ...F3 C11 C10 C9 C7 C8 C2 C1 C5 VR VA GND INT AH SENSOR BUZZER ENV BUZZER OVEN LAMP TURNTABLE MOTOR FAN MOTOR MICROR NC NC DOOR SENSING SWITCH CN C G 5 G 1 SETUP PASTA GRAINS DEFROST FROZEN FOOD EASY MIN...

Page 38: ...1 2 3 A B C D E F G H A B C D E F G H Figure S 4 Printed Wiring Board of Power Unit R3 CN C Q1 SH A GREEN E B R2 D20 XA VH QKITPB033MREO J1 VRS1 CN A R1 ZD1 C2 C1 VH CN B SH B SP30 RY1 RY2 D21 T1 P S...

Reviews: