background image

                                                                                   

ENGLISH 

 

35 

 

 

4.1

 

Electromagnetic Compatibility (EMC) 

MCE/C inverters respect standard EN 61800-3, in the C2 category, for electromagnetic compatibility. 

-

 

Electromagnetic emissions. Residential environment (in some cases restrictive measures may be requested). 

-

 

Conducted emissions. Residential environment (in some cases restrictive measures may be requested). 

5.

 

ELECTRICAL CONNECTIONS 

 

Always switch off the mains power supply before working on the electrical or mechanical part of the system. Before 

opening the equipment, wait at least 5 minutes after disconnecting it from the power supply. The capacitor of the 
direct current intermediate circuit remains charged with dangerously high voltage even after the mains power has 

been turned off.  

Only firmly cabled mains connections are admissible. The appliance must be earthed (IEC 536 class 1, 
NEC and other applicable standards). 

 

 

Ensure that the voltage and frequency on the data plate of the  MCE-22/C are the same as those of the 
power mains. 

 

5.1

 

Connection to the Power Supply Line 

The connection between the single-phase power supply line and the MCE-22/C must be made with a 3-core cable (phase + n 

earth). The characteristics of the power supply must satisfy the indications in 

Table 1. 

The 

input terminals

 are the ones marked with the words 

LINE LN

 and with an 

arrow entering

 the terminals, see 

Figure 1

 

 

Figure 1: Electrical connections 

The minimum section of the input and output cables  must be such as to guarantee correct tightening of the cable clamps, while the 
maximum section accepted by the terminals is 4mm

2

The section, type and laying of the cables for supplying power to the inverter and connecting to the electropump must be chosen 

according to the regulations in force. The table 2 supplies an indication on the section of the cable to be used to supply power to the 
inverter. The table refers to 3-core PVC cables (phase + n earth) and gives the recommended minimum section with relation 
to the current and the length of the cable.  

The electropump current is generally specified on the motor data plate. 
The maximum supply current of the MCE-22/C may generally be estimated as double the maximum current absorbed by the pump.  

Although the MCE-22/C has its own internal protections, it is still advisable to install a suitably sized thermal magnetic circuit breaker.  

 

ATTENTION

: The thermal magnetic circuit breaker and the power cables of the MCE-22/C and of the pump must be of a size suited 

to the system; if the indications given in the manual do not agree with the regulation in force, use the regulation as reference. 

 

5.2

 

Connection to the Electropump 

The connection between the MCE-22/C and the electropump is made with a 4-core cable (3  earth). 
At output an electropump must be connected to a three-phase power supply with the characteristics specified in 

Table 1

The output terminals are the ones marked with the words 

PUMP UVW

 and with an 

arrow leaving

 the terminals, see 

Figure 1

The rated voltage of the electropump must be the same as the MCE-22/C power supply voltage.  
The utility connected to the MCE-22/C must not absorb a current higher than the maximum that can be supplied, indicated in 

Table 1.

 

Check the data plates and the type of connection (star or delta) of the motor used to respect the above-mentioned conditions. 

Table 3

 supplies an indication on the section of the cable to be used to connect to the pump. The table refers to 4-core PVC cables (3 

 earth) and gives the recommended minimum section with relation to the current and the length of the cable. 

Summary of Contents for MCE-11/C

Page 1: ...TALLATIE EN ONDERHOUD INSTRUCCIONES DE INSTALACIÓN Y MANTENIMIENTO INSTALLATIONS OCH UNDERHÅLLSANVISNING РУКОВОДСТВО ПО МОНТАЖУ И ТЕХНИЧЕСКОМУ ОБСЛУЖИВАНИЮ KURMA VE BAKIM BİLGİLERİ ΟΔΗΓΙΕΣ ΓΙΑ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΚΑΙ ΤΗ ΣΥΝΤΗΡΗΣΗ INSTRUCTIUNI PENTRU INSTALARE SI INTRETINERE NAVODILA ZA VGRADNJO IN UPORABO ИНСТРУКЦИЯ ЗА МОНТАЖ И ПОДДРЪЖКА INSTALLÁCIÓS ÉS KARBANTARTÁSI UTASÍTÁS MCE 22 C MCE 15 C MCE 11 ...

Page 2: ...1 FRANÇAIS page 17 ENGLISH page 33 DEUTSCH seite 49 NEDERLANDS pag 65 ESPAÑOL pág 81 SVENSKA sid 97 РУССКИЙ стр 113 TÜRKÇE sf 129 ΕΛΛΗΝΙΚΑ σελ 145 ROMANA pag 161 SLOVENŠČINA Stran 177 БЪЛГАРСКИ Стр 193 MAGYAR Old 209 ...

Page 3: ...ing Lights 44 9 MENU 44 10 FACTORY SETTINGS 48 11 TYPES OF ALARM 48 12 MODBUS MCE C 48 13 BACNET 48 1 KEY The frontispiece shows the version of this document in the form Vn x This version indicates that the document is valid for all software versions of the device n y For example V3 0 is valid for all Sw 3 y In this document the following symbols will be used to avoid situations of danger Situatio...

Page 4: ...s may still have dangerous voltage when the motor is stopped 3 APPLICATIONS The inverter of the MCE C series is a device conceived for the management of circulation pumps allowing integrated regulation of the differential pressure head it is thus possible to adapt the performance of the circulation pump to the actual demands of the system This determines considerable energy saving a greater possib...

Page 5: ...p must be chosen according to the regulations in force The table 2 supplies an indication on the section of the cable to be used to supply power to the inverter The table refers to 3 core PVC cables phase neutral earth and gives the recommended minimum section with relation to the current and the length of the cable The electropump current is generally specified on the motor data plate The maximum...

Page 6: ... mm 10 m 20 m 30 m 40 m 50 m 60 m 70 m 80 m 90 m 100 m 120 m 140 m 160 m 180 m 200 m 4 A 1 5 1 5 1 5 1 5 2 5 2 5 2 5 2 5 4 4 4 6 6 6 10 8 A 1 5 1 5 2 5 2 5 4 4 6 6 6 10 10 10 10 16 16 12 A 1 5 2 5 4 4 6 6 10 10 10 10 16 16 16 16 16 16 A 2 5 2 5 4 6 10 10 10 10 16 16 16 16 16 16 16 20 A 2 5 4 6 10 10 10 16 16 16 16 16 16 16 16 16 24 A 4 4 6 10 10 16 16 16 16 16 16 16 16 16 16 28 A 6 6 10 10 16 16 1...

Page 7: ...he electrical characteristics of the inputs see Table 4 Electrical characteristics of the inputs DC inputs V AC inputs Vrms Minimum switch on voltage V 8 6 Maximum switch off voltage V 2 1 5 Maximum admissible voltage V 36 36 Current absorbed at 12V mA 3 3 3 3 Max accepted cable section mm 2 13 N B The inputs can be controlled with any polarity positive or negative with respect to their earth conn...

Page 8: ...set point reduction function in remote mode I3 Quick Start If input 3 is activated from the control panel the pump is started at the quick start frequency Fq see advanced menu I4 Not enabled Figure 5 Example of Connection of Quick Start Digital Input With reference to the example in Figure 4 and if the EXT and Economy functions have been activated from the control panel the system behaviour will b...

Page 9: ...oportion to the input voltage 0 10V itself see par 0 and par 9 The input A2V is not enabled Figure 6 Example of Connection of Analogue Input N B The 0 10V analogue input is mutually exclusive with the NTC type temperature sensor T connected to the same poles of the 18 pole terminal block 5 5 3 NTC wiring diagram for measuring the fluid temperature T and T1 For installation of the fluid temperature...

Page 10: ...puts listed below refer to the two 3 pole terminal boards J3 and J4 indicated with the screen printing OUT1 and OUT2 below which is also indicated the type of contact for the terminal NC Normally Closed C Common NO Normally Open Characteristics of the output contacts Type of contact NO NC COM Max bearable voltage V 250 Max bearable current A 5 If resistive load 2 5 If inductive load Max accepted c...

Page 11: ... follows 1 hold down the central menu key for 5 seconds 2 scroll through the parameters until you see ET 3 increase the value of the ET parameter in the advanced menu until the noise disappears For the possible operating modes of twin systems see par 9 6 START All the starting operations must be performed with the MCE 22 C cover closed Start the system only when all the electrical and hydraulic co...

Page 12: ...ee par 9 7 1 4 Regulation with Proportional Differential Pressure In this adjustment mode the differential pressure is reduced or increased as the water request falls or rises This mode may be set by means of the control panel on the cover of the MCE 22 C see par 9 7 1 5 T constant function This function causes the circulator to increase or decrease the flow rate to keep constant the temperature m...

Page 13: ...xample if T1 50 C dTs T T1 13 75 C when the temperature T1 is between 40 C and 70 C the circulator works to keep the absolute difference between T and T1 constant at a dTs inversely proportional to the temperature recorded by T1 For example when T1 50 C the circulator keeps the absolute difference between T and T1 constant at 13 75 C 5 If T1 70 C dTs T T1 10 Finally when the temperature T1 is high...

Page 14: ...the yellow light is lit Red light Warning of an alarm malfunction present in the system If the light is blinking it is a non blocking alarm and the pump can still be controlled If the light is fixed it is a blocking alarm and the pump cannot be controlled Green light Pump ON OFF signal If On the pump is running If Off the pump is stopped 9 MENU MCE C provides 2 menus user menu and advanced menu Th...

Page 15: ...fluid temperatures T and T1 1 10000 K Td Running time of the hydraulic circuit it acts in an inversely proportional way on the regulating speed in the T and DT regulations 0 1800 s Bs Parameter for setting up Booster mode 0 80 Ad Modbus address of the device 1 247 Br Serial communication baud rate 1 2 2 4 4 8 9 6 19 2 38 4 Kb s Pa Type of parity control None Odd Even Sb Number of stop bits 1 2 Rd ...

Page 16: ...t point is set from Page 3 0 Depending on the type of regulation chosen on the previous page the set point to be set will be a head Hs a frequency Fs a temperature Ts or a difference in temperature dTs Page 5 0 Page 5 0 is displayed in all pressure regulating modes and allows the setting of auto or economy operating mode Auto mode disables the reading of the status of digital input I2 and in fact ...

Page 17: ...urs Liquid temperature measured on the input A1V 18 pole terminal block Liquid temperature measured on the input A2V 18 pole terminal block T Temperature difference of the liquid T T1 in absolute value Page 9 0 On page 9 0 you can choose the language in which to display the messages Page 10 0 On page 10 0 you can display the alarms log by pressing the right button Alarms Log If the system finds an...

Page 18: ...e Error e22 e30 Voltage Error e31 Protocol Error e32 e35 Excess temperature e37 Low voltage e38 High voltage e39 e40 Excess current e42 Dry operation e43 e44 e45 e54 Pressure Sensor e46 Pump Disconnected Booster mode activated in an operation mode not allowed e55 Temperature sensor T error e56 Temperature sensor T1 error Table 7 List of Alarms 12 MODBUS MCE C The use of the Modbus protocol is allo...

Reviews: