background image

 

ENGLISH 

 

17 

 

4

 

FUNCTION 

The electronics automatically control starting and stopping (ON/OFF) of the pump depending on the request for water. 

The electronics protect the pump from faults in the Non Return Valve (NRV) in the pump casing, which are generally caused by dirt or sand 

deposits. The deposits may prevent the NRV from closing, even in the absence of water. Adequate maintenance of the NRV is therefore 

recommended. 

The pump is automatically switched off every hour; if everything is normal, the user only notices a very slight drop in pressure lasting a few 

seconds. If the NRV is blocked, the pump will go into alarm and can be restarted after removing the causes of the obstruction, preferably by 

disconnecting and reconnecting it to the power supply. However, the alarm stops if the valve is released mechanically. 

The electronics protect the pump from dry running, that is without water (see anti-DRYRUN function). 

The electronics protect the pump from false starts in the event of water bubbling (see anti-burping function). 

For DTRON3, the electronics protect the pump from leaks in the system, which would cause continuous restarts (see ANTICYCLING function). 

 

4.1

 

Pump start and stop conditions 

 

When water is consumed in the water supply network, the pump starts when the starting conditions are met. This is done, for example, by 

turning on a tap and lowering the pressure in the system. The pump stops again when the water consumption stops, that is when the tap is 

turned off. 

 

Start conditions 

The pump starts when one of the following conditions is met: 

- The flow rate is higher than the minimum flow rate of 2 l/min (0.53 rpm). 

- The pressure is lower than the starting pressure (CUT-IN). The cut-in is factory set at 2.4 bar (34.8 psi).  

 

If the pump is equipped with a control panel, the cut-in is variable. 

  

Stop conditions 

The pump stops with a delay of 10 seconds when: 

-The flow rate is lower than the minimum flow rate with pressure above the CUT-IN. 

-The pump stops even when there is no water, safeguarding the motor (see ANTI DRYRUN function). 

- Various alarms. 

 

4.2

 

 Pump On – OFF 

The pump motor is powered by the electronic control board, located inside the pump body, with an alternating voltage equal to that of the 

electrical power mains. 

The pump power supply is supplied to the motor according to the evolution of the user's requirements and the hydraulic conditions of the 

system, as described below. 

 

CUT-IN / Flow – Normal operation 

Normally (in the absence of alarms and when the pump has been primed) the motor is switched on immediately if the pressure is lower than the 

cut-in (see paragraph 4.1) or if there is flow. The motor is switched off if the pressure is greater than the CUT-IN and the flow is absent 

(however, after 10 seconds of permanence in this condition).  

 

Connection to the power mains - first priming of the pump   

After connecting the pump to the mains, the pump motor is switched off and the non-return valve is at rest: if this is not the case, the pump stops 

and the motor will never start (see ANTIFLOOD paragraph). 

 

In the normal case, however, the pump behaves as follows: 

• If the hydraulic circuit upstream from the pump has a pressure higher than CUT-IN, the pump motor does not start, the priming is finished 

regularly. 

• If the circuit is not under pressure (P<CUT-IN), the pump motor is started. In this case: 

o

 

If the hydraulic circuit goes under pressure (P>CUT-IN) and there is no flow, for example because the delivery tap is closed, 

the motor is switched off 10 seconds after starting: the pump is primed. 

o

 

If there is no flow or pressure for 20 seconds (P<CUT-IN), the pump goes into DRYRUN alarm and is switched off: the pump 

is not primed. 

o

 

Finally, if there is flow, the pump is primed and runs normally. 

Anti DRYRUN 

If no pressure and flow is detected during normal operation (or during pump start-up) for 20 seconds, the pump will go into DRYRUN alarm and 

the motor will be switched off.  

 

The pump control electronics will try to restart the pump until the dry running condition, i.e. the absence of flow and pressure, is no longer 

detected. 

Summary of Contents for DTron 3

Page 1: ...Fig Fig Image Abb Afb Fig Obr Kuva Fig Fig ekil Rys bra Fig Fig 1 Fig 2 Fig 3 Fig 5...

Page 2: ...Fig 6 Fig 7 Fig 8 Fig 9...

Page 3: ...Fig 10 Fig 11 Fig 12...

Page 4: ...danger for personal safety Notes and general information WARNINGS Read this documentation carefully before installation Installation and operation must comply with the local safety regulations in forc...

Page 5: ...he products that it may consider necessary or useful without affecting their essential characteristics who lack experience or knowledge on condition that they are under supervision or after they have...

Page 6: ...nly use the pump in clean water The pump must not be used to pump salt water sewage inflammable corrosive or explosive liquids e g petroleum petrol thinners greases oils The temperature of the liquid...

Page 7: ...r with I n 30 mA and that the earth system is efficient Any extension cables comply with the regulations in force 2 1 Mechanical Installation Install the pump in a location that is not exposed to free...

Page 8: ...ve protects the pump from breakage Installation in a well Install the pump so that the pump suction is at least 1 m 3 28ft above the bottom of the well to prevent the intake of sand and impurities Use...

Page 9: ...ressure above the CUT IN The pump stops even when there is no water safeguarding the motor see ANTI DRYRUN function Various alarms 4 2 Pump On OFF The pump motor is powered by the electronic control b...

Page 10: ...scribed here is also effective if starting is set to Manual mode 5 2 Auto mode In this mode the pump power supply is supplied to the motor according to the evolution of the user s requirements and the...

Page 11: ...e the plug out of the socket If the power cable or any electrical part of the pump is damaged the repair or replacement must be carried out by the manufacturer or by their technical assistance service...

Page 12: ...e in MONITOR mode pressure on the delivery of the DTRON3 pump 6 motor power status 4 DISABLE status of the pump XX current faults alarms 5 8 10 11 connection status of the COM BOX with the DTRON s 8 T...

Page 13: ...ons Figure 12 2 and Reset Select Figure 12 3 simultaneously for at least 3 seconds or wait for 1 minute without touching any button on the interface When switched on the COM BOX is in Monitor mode by...

Page 14: ...resented in the barometric scale by flashing Instead the current value of the CUT IN is highlighted with the corresponding LED lit with a steady light Too low a CUT IN value could prevent the pump tur...

Reviews: