ENGLISH
114
14*
General enabling of the inverter by an external signal
(NO) without error message
F3
15*
General enabling of the inverter by an external signal
(NC) without error message
F3
* Function available for firmware V 26.1.0 and later versions
Table 24: Input configuration
6.6.13.1
Disabling functions associated with input
If an input is configured at 0, each function associated with this input will be disabled, regardless of the signal on the terminals of the
input itself.
6.6.13.2
Setting the external float function
The external float can be connected to any input, for all electrical connections, refer to paragraph 2.2.4.2. The float function is
implemented by setting the parameter INx associated with the input where the float is connected, with one of the values of Table 23.
Activation of the external float function generates a system block. The function is envisaged to connect the input to a signal from a
float that indicates a water supply failure.
When this function is enabled, the symbol F1 is shown on the STATUS line of the main page.
The input must be activated for at least one second for the system to block and indicate the error F1.
When in the F1 error condition, the input must be deactivated for at least 30 seconds before the system unblocks. The function
behaviour is summarised in Table 23.
When several float functions are configured at the same time on different inputs, the system indicates F1 when at least one function is
activated and clears the alarm when none are activated.
Response of external float function according to setting of INx and input
Parameter
value
INx
Input
configuration
Input status
Operation
Display
1
Active with high signal
on input (NO)
Absent
Normal
None
Present
System block due to lack of
water from external float
F1
2
Active with low signal
on input (NO)
Absent
System block due to lack of
water from external float
F1
Present
Normal
None
Table 25: External float function
6.6.13.3
Setting the auxiliary pressure input function
The auxiliary set points are disabled if the flow sensor is not used (FI=0) and when FZ is used in minimum frequency mode
(FZ ≠ 0).
The signal that enables an auxiliary set point can be supplied on any one of the 4 inputs, (for electrical connections, refer to paragraph
2.2.4.2). The auxiliary set point function is obtained by setting parameter INx, associated with the input on which the connection is
made, in accordance with Table 24.
The auxiliary pressure function modifies the system setpoint from pressure SP (see section 6.3) to pressure Pi . For electrical
connections, see paragraph 2.2.4.2) where i represents the input used. In this way, as well as SP there are four additional pressures
available: P1, P2, P3, and P4.
When this function is enabled, the symbol Pi is shown on the STATUS line of the main page.
The input must be active for at least 1 second for the system to operate with the auxiliary setpoint.
When operating with the auxiliary setpoint, the input must not be active for at least 1 second to return to operation with setpoint SP.
The function behaviour is summarised in Table 24.
Summary of Contents for AD 1.0 AC
Page 13: ...ITALIANO 11 Figura 2 Fissaggio e distanza minima per la circolazione d aria...
Page 74: ...ENGLISH 72 Figure 2 Fixture and minimum clearance for air circulation...
Page 135: ...FRAN AIS 133 Figure 2 Fixation et distance minimum pour la circulation de l air...
Page 196: ...DEUTSCH 194 Abbildung 2 Befestigung und Mindestabstand f r die Luftzirkulation...
Page 257: ...ESPA OL 255 Figura 2 Fijaci n y distancia m nima para la circulaci n del aire...
Page 269: ...ESPA OL 267 Figura 13 Ejemplo de conexi n de las entradas...
Page 312: ...310 IEC 60634 1...
Page 313: ...311 1 6 1 1...
Page 317: ...315 1 2 1 1 1 1 2 5 2 1 2 1 2 2...
Page 318: ...316 2...
Page 319: ...317 2 2 3 3 15 2 2 1 1a 2a...
Page 320: ...318 4a 5b 1b 127 240 240 480 3 6 3b...
Page 324: ...322 2 2 2 GP GI 6 6 4 6 6 5 8 A B C D...
Page 332: ...330 3 14 64 X 128 4 MODE SET 12 9 MODE 1 SET 11 3 EEprom SET 6 SET MODE 3 1 11...
Page 333: ...331 3 2 1 2 3 2 1 MODE SET MODE 10 2 2 5 5 5 2 2 12...
Page 335: ...333 3 2 2 13 SET 15 15 14 16...
Page 337: ...335 17 15 15 3 4 PW 6 6 16 GO SB...
Page 338: ...336 4 4 1 Link 8 4 2 4 2 1 Link Link 16 18 Link...
Page 367: ...365 OC 10 6 OF 10 6 33 8 8 1 PMW 4 2 8 2 8 3 8 3 SET EE EEprom FLASH...
Page 379: ...NEDERLANDS 377 Afbeelding 2 Bevestiging en minimumafstand voor luchtrecirculatie...
Page 440: ...SVENSKA 438 Fig 2 Fasts ttning och min utrymme f r luftcirkulation...
Page 501: ...T RK E 499 ekil 2 Hava sirk lasyonu tesisat ve minimum a kl k...
Page 556: ...554 IEC 364 1 inverter...
Page 557: ...555 1 Inverter inverter inverter 6 inverter 1 1...
Page 561: ...559 1 2 1 1 inverter inverter 1 1 2 5 inverter 2 1 inverter 2 1 2 2 C...
Page 562: ...560 2...
Page 563: ...561 2 2 3 3 inverter 15 inverter 2 2 1 inverter inverter 1a 2a...
Page 564: ...562 4a 5b 1b V 127 240 240 480 mm 3 6 3b azione...
Page 568: ...566 2 2 2 inverter inverter GP GI 6 6 4 6 6 5 inverter 8 A B C D...
Page 576: ...574 3 14 oled 64 X 128 4 MODE SET 12 inverter 9 MODE 1 SET 11 3 EEprom SET 6 SET MODE 3 1 11...
Page 577: ...575 3 2 1 2 3 2 1 MODE SET Setpoint MODE 10 ONOMA TOY MENOY 2 Setpoint 2 5 5 5 2 2 12...
Page 581: ...579 17 15 15 3 4 Password inverter password password inverter password PW 6 6 16 GO SB FAULT...
Page 623: ...ROM N 621 Figura 2 Fixarea i distan a minim pentru circula ia aerului...
Page 684: ...POLSKI 682 Rys 2 Mocowanie oraz minimalna odleg o na potrzeby cyrkulacji powietrza...
Page 745: ...MAGYAR 743 2 bra R gz t s s minim lis t vols g a szell z leveg kering se rdek ben...
Page 800: ...798 IEC 364 1...
Page 801: ...799 1 3 1 1...
Page 805: ...803 1 2 1 1 1 1 2 5 2 1 2 1 2 C...
Page 806: ...804 2...
Page 807: ...805 2 2 3 3 15 2 2 1 1 2a...
Page 808: ...806 4a 5b 1b V 127 240 240 480 3 6 3b...
Page 812: ...810 2 2 2 GP GI 6 6 4 6 6 5 8 A B C D...
Page 817: ...815 V 36 36 12V A 3 3 3 3 2 13 9 11 8 13...
Page 819: ...817 3 14 64 X 128 4 MODE SET and 12 9 MODE 1 SET 11 3 EEprom SET 6 SET MODE 3 1 11...
Page 820: ...818 3 2 1 2 3 2 1 10 2 2 5 5 5 2 2 12...
Page 824: ...822 15 3 4 GO SB FAULT...
Page 825: ...823 4 4 1 8 4 2 4 2 1 16 18...
Page 862: ...ESKY 860 Obr zek 2 P ipevn n a minim ln vzd lenost kv li cirkulaci vzduchu...
Page 917: ...915 IEC 60634 1...
Page 918: ...916 1 6 1 1...
Page 922: ...920 1 2 1 1 1 1 2 5 2 1 2 1 2 2...
Page 923: ...921 2...
Page 924: ...922 2 2 3 3 15 2 2 1 1a 2a...
Page 925: ...923 4a 5b 1b 127 240 240 480 3 6 3b...
Page 929: ...927 2 2 2 GP GI 6 6 4 6 6 5 8 A B C D...
Page 931: ...929 10 4 20 6 4 20 PR 6 5 7 4 20 2 18 J5 GND 1 J5 GND o IN 11 J5 4 20 7 OUT 8 10 11 IN...
Page 935: ...933 13 J5 I1 11 17 16 18 16 17 I2 11 15 16 18 15 16 I3 11 14 13 18 13 14 I4 11 12 13 8 12 13 9...
Page 937: ...935 3 14 64 X 128 4 MODE SET 12 9 MODE 1 SET 10 3 EEprom SET 6 SET MODE 3 1 11...
Page 938: ...936 3 2 1 2 3 2 1 MODE SET MODE 10 2 2 5 5 5 2 2 11...
Page 940: ...938 3 2 2 13 SET 15 15 14 16...
Page 942: ...940 17 14 15 3 4 PW 6 6 16 GO SB FAULT...
Page 943: ...941 4 4 1 Link 8 4 2 4 2 1 Link Link 16 18 Link...
Page 946: ...944 4 3 1 2 1 4 3 1 3 SET MODE LA RC MS FS SO AE O1 1 O2 2 4 4 2 2 4 2 5 4 5 ET 6 6 9 FL...
Page 969: ...967 10 0 Mode Set PW 0 PW 2 7 3 6 6 16 1 PW PW PW PW 0 PW 0 0 PW PW PW PW PW 0 PW...