ACTIVE DRIVER T/T 3.0  

Suits three phase power supply, and will couple to three phase pump units up to 3.0kW, 
and is programmable to a maximum pressure of 9 Bar (900kPa), not exceed a flow of 
300lpm. 
 

ACTIVE DRIVER T/T 5.5  

Suits three phase power supply, and will couple to three phase pump units up to 5.5kW, 
and is programmable to a maximum pressure of 9 Bar (900kPa), not exceed a flow of 
300lpm. 

 

>Selecting the Correct Pump. 

 
It is import ant to choose the correct pump when utilizing the ACTVE DRIVER as a constant 
pressure control device. It is important that the pump is selected to provide the maximum 
potential flow at the desired demand pressure. 
 
>>For Example, 
 
If a duty point of 100lpm at 350kPa is required, 
then this should be assumed as the maximum 
required duty of the pump.  
 
An ideal selection for this would be the DAB 
KVCX35/120, as it will provide the flow 
required at around 380kPa and the required 
pressure at a maximum flow of 115lpm. 
 
As the ACTIVE DRIVER is controlled by required 
pressure, inputting a set point of 350kPa will 
mean that the pump will normally run at lower 
frequency (speed), and less likely to cavitate. 
 

>Installing the ACTIVE 
DRIVER 

 
The ACTIVE DRIVER would normally be 
installed in an upright position, on the 
discharge side, above the main body of water 
in the pump. 
 
A check valve should be installed inlet to the controller or in the suction port of the pump. 
Failure to install a check valve will result in the unit cycling. 
 
The ACTIVE DRIVER is pressure sensitive and a suitable sized ENERGY SAVER should be 
installed on the discharge side of the controller. The pre-charge should be set to be slightly 
lower (15kPa min) that the restart point set in the controller, which is factory set at 0.5 Bar 
(50kPa) below the set point. 
 
The AD M/T 1.0, AD M/T 2.2, AD T/T3.0 and AD T/T 5.5 can be interconnected with up to three 
units (total) operating as one system, allowing for alternating starts and various inputs and 
outputs for integrated operation. 
 
 
If using the AD M/M 1.1, retain the PLUG and PLAY fly lead supplied with the pump as it will be 
helpful in priming the pump before attempting to set the ACTIVE DRIVER.  
 
This allows you to use the pump in a manual mode while priming is completed. 
 

 

Summary of Contents for ACTIVE DRIVER M/M 1.1

Page 1: ...configurations ACTIVE DRIVER M M 1 1 Suits single phase 230v power supply and will couple to single phase pump units up to 1 1kW and is programmable to a maximum pressure of 6 Bar 600kPa not exceed a...

Page 2: ...ting a set point of 350kPa will mean that the pump will normally run at lower frequency speed and less likely to cavitate Installing the ACTIVE DRIVER The ACTIVE DRIVER would normally be installed in...

Page 3: ...stem is required to run at This is inputted in Bar The rated current of the pump can be located on the compliance plate attached to the pump or is listed in the DAB Factory catalogue in the ELECTRICAL...

Page 4: ...the back of this guide Displays of the Main Values It is also possible to access operational information of the system by pressing the mode key these indications are Fr Displays the current frequency...

Page 5: ...e desired operating pressure of the system To access this setting press mode and set simultaneously for two seconds the display should indicate SP and then flash to 3 0 which is the pre set of 3 0 Bar...

Page 6: ...e system Go or Sb od OPERATING MODE this refers to the presence of a pressure cell To access this setting press mode set and simultaneously for five seconds press mode until the display indicates od a...

Page 7: ...or Sb Eb ENABLING THE BOOSTER turn the alternating function on in a multiple pumps system Not applicable to the AD M M 1 1 To access this setting press mode set and simultaneously for five seconds pre...

Page 8: ...8 Programming Resetting Factory Settings It is possible to restore the default settings by pressing set an for two seconds whilst restoring the power supply switching on...

Page 9: ...9 Programming Quick Set Up The following is a quick set up procedure for basic operation for all settable parameters refer to the complete input list on the last page...

Page 10: ...10...

Reviews: