ENGLISH

GB

33

Page 2.0

The regulating mode is set from Page 2.0. You can choose 
between the following modes:

1      = Proportional  differential pressure regulation.
2          = Proportional differential pressure regulation with set-
point set by external signal (0-10V or PWM).
3        = Proportional differential pressure regulation with set-
point depending on temperature.
4      = Regulation with constant differential pressure.
5          = Constant differential pressure regulation with set-point 
set by external signal (0-10V or PWM).
6        = Constant differential pressure regulation with set-point 
depending on temperature.
7      = Regulation with constant curve with rotation speed set 
from the display.
8        = Regulation with constant curve with rotation speed set 
by an external signal (0-10V or PWM).

Page 2.0 displays 3 icons which represent:
- central icon = setting currently selected
- right icon = next setting
- left icon = previous setting

Page 3.0

7KHUHJXODWLQJVHWSRLQWFDQEHPRGL¿HGIURP3DJH

Depending on the type of regulation chosen on the previous 
page, the set-point to be set will be a head or, in the case of a 
Constant Curve, a percentage of the rotation speed.

Page 4.0

On Page 4.0 it is possible to modify the parameter THs with 
which to make the curve depending on temperature (see Par. 
10.1.4).
This page will be displayed only for the regulating modes de-

SHQGLQJRQÀXLGWHPSHUDWXUH

.

Page 5.0

Page 5.0 allows you to set the “auto” or “economy” operating 
mode.
“Auto” mode disables the reading of the status of digital input 
IN2 and in fact the system always activates the set-point set 
by the user.
“Economy” mode enables the reading of the status of digital 
input IN2. When input IN2 is energised the system activates a 
percentage reduction of the set-point set by the user (Page 6.0 
of the EVOPLUS menu).
For the connection of the inputs see par. 8.2.1

Page 6.0

Page 6.0 is displayed if “economy” mode has been chosen 
on page 5.0 and allows setting of the percentage value of the 
set-point.
This reduction will be carried out if digital input IN2 is ener-
gised.

Page 7.0

Page 7.0 is displayed if an operating mode has been chosen 
with set-point regulated by an external signal.
This page allows you to choose the type of control signal: ana-
logue 0-10V (positive or negative increase) or PWM (positive 
or negative increase).

Page 8.0

If a twin system is used (see Par. 8.3) on page 8.0 you can set one 
of the 3 possible twin operation modes:

Alternate every 24h: 

The 2 circulators alternate in regula-

tion every 24 operating hours. If one of the 2 malfunctions, 
the other takes over regulation.

Simultaneous: 

The 2 circulators work at the same time 

DQGDWWKHVDPHVSHHG7KLVPRGHLVXVHIXOZKHQDÀRZ

rate is required that cannot be provided by a single pump.

Main/Reserve: 

Regulation is always performed by the 

same circulator (Main), the other (Reserve) takes over only 
if there is a malfunction of the Main one.

If the twin communication cable is disconnected the systems auto-

PDWLFDOO\¿JXUHDV6LQJOHZRUNLQJFRPSOHWHO\LQGHSHQGHQWRIHDFK

other.

Summary of Contents for 500 Series

Page 1: ...Circulating Pumps Series 500 SINCE 1981 www flofab com available in both the single and twin version Instructions Operating Manual...

Page 2: ...the equipment but invalidates every right to assistance under guarantee The appliance is not intended to be used by persons including children with reduced physical sensory or mental capacities or who...

Page 3: ...a percentage of no more than 30 4 APPLICATIONS EVOPLUS series circulators allow integrated adjustment of the differ ential pressure which enables the circulator performance to be adapted to the actua...

Page 4: ...Always switch off the mains power supply before working on the electrical or mechanical part of the system Wait for the war ning lights on the control panel to go out before opening the ap pliance The...

Page 5: ...es in the motor casing are not closed or partly blocked 7R JXDUDQWHH PD LPXP HI FLHQF RI WKH V VWHP DQG ORQJ OLIH RI WKH FLUFXODWRU LW LV UHFRPPHQGHG WR XVH PDJQHWLF VOXGJH UHPRYLQJ OWHUV WR separate...

Page 6: ...le leakage current selective protected against sudden tripping The automatic differential switch must be marked with the fol lowing two symbols The circulator does not require any external motor prote...

Page 7: ...puts and digital outputs so as to be able to realise interface solutions with more complex installations RU WKH LQVWDOOHU LW ZLOO EH VXI FLHQW WR ZLUH XS WKH GHVLUHG LQSXW DQG RXWSXW FRQWDFWV DQG WR F...

Page 8: ...stopped Closed Open Pump running with set point set by the user Closed Closed Pump running with reduced set point 8 2 2 MODBUS and LON Bus EVOPLUS circulators provide serial communication through an...

Page 9: ...arable voltage V 250 Max bearable current A 5 If resistive load 2 5 If inductive load Max accepted cable section mm 2 5 8 3 Connections for Twin Systems 3HU UHDOL DUH XQ VLVWHPD JHPHOODUH q VXI FLHQWH...

Page 10: ...LUS control panel see par 12 Page 2 0 10 1 1 Regulation with Proportional Differential Pressure In this regulating mode the differential pressure is redu ced or increased as the demand for water decre...

Page 11: ...e panel there are a graphic display 4 navigation keys and 3 LED warning lights see Figure 10 11 1 Graphic Display Using the graphic display it will be possible to navigate in an easy and intuitive men...

Page 12: ...tton then press and release the central button To modify the settings use the left and right buttons 7R FRQ UP WKH FKDQJH RI D VHWWLQJ KROG GRZQ WKH central button OK IRU VHFRQGV RQ UPDWLRQ ZLOO EH LQ...

Page 13: ...onomy operating mode Auto mode disables the reading of the status of digital input IN2 and in fact the system always activates the set point set by the user Economy mode enables the reading of the sta...

Page 14: ...a message in the language selected on Page 10 0 giving a brief description of the fault By pressing the right button you can scroll through all the pa ges of the log 2 questions appear at the end of...

Page 15: ...tly asked questions faq on the ecodesign directive 2009 125 ec establishing a framework for the setting of ecodesign requirements for energy related products and its implementing regulations http ec e...

Page 16: ...EVOPLUS B 40 240 50 M 0 23 EVOPLUS B 60 240 50 M 0 21 EVOPLUS B 80 240 50 M 0 21 EVOPLUS B 100 280 50 M 0 20 EVOPLUS B 120 280 50 M 0 19 EVOPLUS B 150 280 50 M 0 19 EVOPLUS B 180 280 50 M 0 19 EVOPLU...

Reviews: