background image

Intended use

-   Rack and pinion drive for electric opening and

   closing of windows and flaps in the facade and
   roof area

-   Operating voltage 24 V DC
- Useable for smoke ventilation, D+H Euro-SHEV

 

in according with DIN EN 12101-2 as well as daily

 

ventilation

-   Suitable for indoor mounting only

2/12

Performance features

- Microprocessor-controlled synchronous

 

electronics BSY+ for safe and precise

   synchronous running of up to 8 drives

-   Individually programmable (via software SCS)
- SHEV-high speed function (fast-running 

 

 

 

feature in OPEN-direction)

- Especially quiet motor running in ventilation mode

English

Mounting informations

-   Swivel radius of the drive must go free over entire

   range of stroke.  Otherwise, the toothed rack and
   the suspension can be damaged

-   Drives with a stroke of 

800 mm (31.2'') must not be

   mounted „hung up at the bottom“ (e.g. bracket UK)

- The drive set will be full configured by factory.

   The drives must be reconfigured in case of
   alterations (e.g. removing of drives from existing
   set or integrating a new drive) with SCS

- Use only drives with the same force
- Ensure evenly load distribution on all the drives
-   Eyebolt has to be adjusted so, that the drive is

   disconnected with   closed flap through it’s inside
   stop position damping.    Brackets can be damaged
   by to rigid adjustment!

Scope of supply

Drive  unit  with  2,5  m  (97.5'')  silicone  cable. 
Dependent on the type of window, different bracket 
sets are available separately.

3/12

English

99.824.48 2.3/03/22

99.824.48 2.3/03/22

RDM -BSY+ (-HS)

RDM -BSY+ (-HS)

Main closing edge

Beside closing edge

Beside closing edge

Entrapment protection

(see N.12 of Safety Notes; p 2/12)

In  "CLOSE"  direction  the  drive  has  an  active 
clamping protection for the main closing edge. With 
an overload in the closing range 3 and 2 the drive 
runs  "OPEN"  for  10  seconds,  then  drive  "CLOSE" 
again. If after three attempts a closing is not possible, 
the drive remains in this position.
In  addition,  the  drive  has  a  passive  clamping 
protection.  The  closing  speed  in  closure  Range  2 
and 1 is reduced to 5 mm/s (0,2"/s). The drive were 
not evaluated for entrapment protection.

 

Higher forces can occur 

on besides closing edges. 
Danger of violent pressure 
in handaccessible area.

The drives were not evaluated for 
entrapment protection.

Type 

ZA 35-BSY+(-HS)   

  ZA 85-BSY+(-HS) 

ZA 105-BSY+(-HS) 

ZA 155-BSY+(-HS)

 

Nominal voltage 

24 V DC, ±15 %  

  24 V DC, ±15 % 

  24 V DC, ±15 % 

24 V DC, ±15 %

Nominal current  

0,5 A (1,2 A) 

 

  1,0 A (2,0 A)   

  1,2 A (2,2 A)  

1,4 A (2,5 A)

Nominal force 

300 N / 67.44 lbf  

  800 N / 179.8 lbf 

  1000 N / 224.8 lbf  1500 N / 337.2 lbf

 

Nominal locking force  1100 N / 247.3 lbf
Lifetime

 

>10 000 double strokes

Duty cycle

 

30 % (with cycle time 10 min.)

Housing

 

Anodized aluminium / polycarbonate

Ingress protection

 

IP 65 (“-W“ = IP 54)

Temperature range 

-5 ... +75 °C (23 ... 167 °F)

Fire stability 

30 min / 300 °C (572 °F)

Nominal stroke length*  See type plate
Additional functions *

 

Closing edge protection activated (3 stroke repeatings)

 

* Programmable with software Service and Configuration Suite BSY+ (SCS)

Running speed
and forces

Normal  operation

  =

SHEV- fast running =

Technical data

All approx. 20 % switch-off reserve
(temporary)

I

III

77 mm

3''

23 mm

0.9''

7,1 mm/s

0.28''/s

5 mm/s

0.2'’/s

5 mm/s

0.2'’/s

~7,1 mm/s /         ~8 mm/s (~17 mm/s)

II

Closing Range

~0.28''/s /             ~0,31''/s (~0.67''/s)

OPEN

Forces

CR III

CR II

CR I

300 N

67.44 lbf

300 N

67.44 lbf

300 N

67.44 lbf

300 N

67.44 lbf

ZA 35

800 N

179.8 lbf

800 N

179.8 lbf

800 N

179.8 lbf

800 N

179.8 lbf

ZA 85

1000 N

224.8 lbf

1000 N

224.8 lbf

1000 N

224.8 lbf

800 N

179.8 lbf

ZA 105

1500 N

337.2 lbf

1000 N

224.8 lbf

1000 N

224.8 lbf

800 N

179.8 lbf

ZA 155

! IMPORTANT ! Safety Notes

1.  Mounting of the drive should be carried out by a D+H distributor, whose qualification and experience is 

ensured by regular in-house training.

2.  All wiring must be installed by a qualified electrican according to National Electrical Codes, NFPA 70.
3.  For indoor use only. Use always rain detector with danger of rain (e.g. at domelights or roof windows).
4.  Observe enclosed red safety slip!
5.  Danger of violent pressure in handaccessible area.
6.  The window operators have been evaluated for Residential or Light Duty Commercial Use only.
7.  A suitable field wiring means should be provided in the end use application.
8.  The mounting and routing of external wiring should be determined in the end product.
9.  The mounting of each unit shall be evaluated in the end use.
10. The suitability of the leads for field wiring should be determined in the end-use application.
11. The drive must be mounted a min of 8 feet above the floor or any access level.
12. The drives were not evaluated for entrapment protection since they are to be installed at least 8 feet above 

the floor. Where entrapment is a consideration, the need for additional tests and evaluation should be 
determined during the end product investigation.

13. The drive shall be connected to a Class 2 power supply.

For North America:
14. The Uniform Building Code Standard Vols. 1, 2 & 3 have to be observed.

Summary of Contents for ZA35-BSY+(-HS)

Page 1: ...ion without tube option OT Modelo sin tubo opcional OT en Original instructions Page 2 es Manual original P gina 6 Please order bracket sets separately Rogamos que pidan los juegos de fijaci n por sep...

Page 2: ...h 2 5 m 97 5 silicone cable Dependent on the type of window different bracket sets are available separately 99 824 48 2 3 03 22 RDM BSY HS IMPORTANT Safety Notes 1 Mounting of the drive should be carr...

Page 3: ...2A 2 2A 1 4A 2 5A Nominal force 300 N 67 44 lbf 800 N 179 8 lbf 1000 N 224 8 lbf 1500 N 337 2 lbf Nominal locking force 1100 N 247 3 lbf Lifetime 10 000 double strokes Duty cycle 30 with cycle time 10...

Page 4: ...amid Domelight Pyramid Weighty wing Uncritical load distribution Critical load distribution Guiding device required by customer in case of complete lift off of pyramid domelight because of possible la...

Page 5: ...be carried out exclusively by D H Wipe away debris or contamination with a dry soft cloth Do not use cleaning agents or solvents Guarantee You will get 2 years guarantee for all D H products from date...

Page 6: ...as de seguridad 1 El montaje del actuador deber efectuarse por un distribuidor autorizado de D H que cuente con la cualificaci nyexperiencianecesaria adquiridamedianteunaformaci ncontinuadaennuestraem...

Page 7: ...3 1 s 0 6 7 s ABRIR Fuerzas RC III RC II RC I 300 N 67 44 lbf 300 N 67 44 lbf 300 N 67 44 lbf 300 N 67 44 lbf ZA 35 800 N 179 8 lbf 800 N 179 8 lbf 800 N 179 8 lbf 800 N 179 8 lbf ZA 85 1000 N 224 8 l...

Page 8: ...Y HS Carga m x Carrera 1000N 224 8 lbf 800N 179 8 lbf 600N 134 9 lbf 400N 89 9 lbf 200N 45 lbf 500 mm 19 5 600 mm 23 4 800 mm 31 2 1000 mm 39 0 1100 mm 42 9 1200 mm 46 8 1300 mm 50 7 1400 mm 54 6 1500...

Page 9: ...a para todos los productos D H desde la fecha de su puesta en marcha hasta un m ximo de 3 a os de la fecha de la entrega siempre que el montaje y la puesta en marcha hayan sido realizados por un distr...

Page 10: ...io normal SHEV fast running marcha r pida SVHC High Speed High Speed High Speed Not in case of No en el caso GVL K M E Protect against short circuit Proteger contra cortacircuitos In case of connectio...

Page 11: ...ng cable Segundo cable de conexi n WH Mot a BN Mot b OG HS YE Data A GN Data B GY BRV PK n c Option BRV Opci n BRV WH Mot a BN Mot b OG HS YE Data A GN Data B Standard Est ndar RDM BSY HS Dimensions D...

Page 12: ...49 239 Tel 40 605 65 49 Fax 40 605 65 254 E Mail info dh partner com www dh partner com 2013 D H Mechatronic AG Ammersbek Rights to technical modifications reserved Derecho reservado a modificaciones...

Reviews: