Intended use
- Rack and pinion drive for electric opening and
closing of windows and flaps in the facade and
roof area
- Operating voltage 24 V DC
- Useable for smoke ventilation, D+H Euro-SHEV
in according with DIN EN 12101-2 as well as daily
ventilation
- Suitable for indoor mounting only
2/12
Performance features
- Microprocessor-controlled synchronous
electronics BSY+ for safe and precise
synchronous running of up to 8 drives
- Individually programmable (via software SCS)
- SHEV-high speed function (fast-running
feature in OPEN-direction)
- Especially quiet motor running in ventilation mode
English
Mounting informations
- Swivel radius of the drive must go free over entire
range of stroke. Otherwise, the toothed rack and
the suspension can be damaged
- Drives with a stroke of
≥
800 mm (31.2'') must not be
mounted „hung up at the bottom“ (e.g. bracket UK)
- The drive set will be full configured by factory.
The drives must be reconfigured in case of
alterations (e.g. removing of drives from existing
set or integrating a new drive) with SCS
- Use only drives with the same force
- Ensure evenly load distribution on all the drives
- Eyebolt has to be adjusted so, that the drive is
disconnected with closed flap through it’s inside
stop position damping. Brackets can be damaged
by to rigid adjustment!
Scope of supply
Drive unit with 2,5 m (97.5'') silicone cable.
Dependent on the type of window, different bracket
sets are available separately.
3/12
English
99.824.48 2.3/03/22
99.824.48 2.3/03/22
RDM -BSY+ (-HS)
RDM -BSY+ (-HS)
Main closing edge
Beside closing edge
Beside closing edge
Entrapment protection
(see N.12 of Safety Notes; p 2/12)
In "CLOSE" direction the drive has an active
clamping protection for the main closing edge. With
an overload in the closing range 3 and 2 the drive
runs "OPEN" for 10 seconds, then drive "CLOSE"
again. If after three attempts a closing is not possible,
the drive remains in this position.
In addition, the drive has a passive clamping
protection. The closing speed in closure Range 2
and 1 is reduced to 5 mm/s (0,2"/s). The drive were
not evaluated for entrapment protection.
Higher forces can occur
on besides closing edges.
Danger of violent pressure
in handaccessible area.
The drives were not evaluated for
entrapment protection.
Type
ZA 35-BSY+(-HS)
ZA 85-BSY+(-HS)
ZA 105-BSY+(-HS)
ZA 155-BSY+(-HS)
Nominal voltage
24 V DC, ±15 %
24 V DC, ±15 %
24 V DC, ±15 %
24 V DC, ±15 %
Nominal current
0,5 A (1,2 A)
1,0 A (2,0 A)
1,2 A (2,2 A)
1,4 A (2,5 A)
Nominal force
300 N / 67.44 lbf
800 N / 179.8 lbf
1000 N / 224.8 lbf 1500 N / 337.2 lbf
Nominal locking force 1100 N / 247.3 lbf
Lifetime
>10 000 double strokes
Duty cycle
30 % (with cycle time 10 min.)
Housing
Anodized aluminium / polycarbonate
Ingress protection
IP 65 (“-W“ = IP 54)
Temperature range
-5 ... +75 °C (23 ... 167 °F)
Fire stability
30 min / 300 °C (572 °F)
Nominal stroke length* See type plate
Additional functions *
Closing edge protection activated (3 stroke repeatings)
* Programmable with software Service and Configuration Suite BSY+ (SCS)
Running speed
and forces
Normal operation
=
SHEV- fast running =
Technical data
All approx. 20 % switch-off reserve
(temporary)
I
III
77 mm
3''
23 mm
0.9''
7,1 mm/s
0.28''/s
5 mm/s
0.2'’/s
5 mm/s
0.2'’/s
~7,1 mm/s / ~8 mm/s (~17 mm/s)
II
Closing Range
~0.28''/s / ~0,31''/s (~0.67''/s)
OPEN
Forces
CR III
CR II
CR I
300 N
67.44 lbf
300 N
67.44 lbf
300 N
67.44 lbf
300 N
67.44 lbf
ZA 35
800 N
179.8 lbf
800 N
179.8 lbf
800 N
179.8 lbf
800 N
179.8 lbf
ZA 85
1000 N
224.8 lbf
1000 N
224.8 lbf
1000 N
224.8 lbf
800 N
179.8 lbf
ZA 105
1500 N
337.2 lbf
1000 N
224.8 lbf
1000 N
224.8 lbf
800 N
179.8 lbf
ZA 155
! IMPORTANT ! Safety Notes
1. Mounting of the drive should be carried out by a D+H distributor, whose qualification and experience is
ensured by regular in-house training.
2. All wiring must be installed by a qualified electrican according to National Electrical Codes, NFPA 70.
3. For indoor use only. Use always rain detector with danger of rain (e.g. at domelights or roof windows).
4. Observe enclosed red safety slip!
5. Danger of violent pressure in handaccessible area.
6. The window operators have been evaluated for Residential or Light Duty Commercial Use only.
7. A suitable field wiring means should be provided in the end use application.
8. The mounting and routing of external wiring should be determined in the end product.
9. The mounting of each unit shall be evaluated in the end use.
10. The suitability of the leads for field wiring should be determined in the end-use application.
11. The drive must be mounted a min of 8 feet above the floor or any access level.
12. The drives were not evaluated for entrapment protection since they are to be installed at least 8 feet above
the floor. Where entrapment is a consideration, the need for additional tests and evaluation should be
determined during the end product investigation.
13. The drive shall be connected to a Class 2 power supply.
For North America:
14. The Uniform Building Code Standard Vols. 1, 2 & 3 have to be observed.