X4
1
2
3
X2
X3
X1
X4
X.x
5.15
35/48
LSC 44-M4
99.823.35 1.2/06/09
Plug and Play-Initiation-Airflow-Alignment
X4
PIN 1 and 2
PIN 2 and 3
Appliance
base
Detection
unit
Standard settings will not be changed in case of a
plug and play initiation.
The jumper X4 (pin 1,2 or pin 2,3) in the detection
unit of the MICRO-SENS must be plugged into a
different socket during initiation.After that, airflow
alignment will be automatically effected.
®
During initialization of the TITANUS
the green operational indicator will be flashing.
If the initialization is terminated, the operational indicator will change to steady burning light.
The airflow of the TITANUS
shall not be influenced during the initialization process.
MICRO-SENS
MICRO-SENS
®
®
Airflow initialization of the TITANUS
has been successfully terminated, if for
a period of 2 minutes following condition is
existing:
Airflow initialization will be immediately
interrupted, if one of following faults will occur
MICRO-
SENS
®
- no lift is going
- temperature is varying by less than 0.1K
- airflow is not too strongly varying
(temperature adjustment)
- ventilator voltage can be adjusted according to
the regulations, ventilator and ventilator power
pack are working normally.
- measurement of temperature is faulty
- airflow measurement is faulty
- ventilator control faulty
Alarm detection will be fully operative during the
learning process. During this period the operational
indicator will flash and no airflow influences shall
occur.
After termination of initialization, the operational
indicator will change to steady burning light and the
airflow detector has its set point determined for the
connected tube system.
Initiation with diagnosis tool
Presettings are changeable in case of initiation with
a diagnosis tool. Then an airflow alignment can be
carried out dependent or independent on air
pressure.
Initialization of the airflow will be started by means
of the diagnosis tool.
The diagnosis tool is optionally available at D+H
Mechatronic under the designation DIAG 3.
After the initiation is completed, a test record can be
generated using the diagnosis tool.
Testing of TITANUS
MICRO·SENS
®
After successful conclusion of the initialization, the
function can be tested by injecting smoke of a
cigarette or a joss stick into the tube suction hole.