background image

6

Cypress Suprex® RS-485 Series - Setup and Pre-installation

Final Field Installation Checklist:

• The Central unit and access control panel should have a common ground.
• The Remote unit and card reader should have a common ground.
• The RS-485 connection between the Central and Remote unit is straight through, and not reversed. 

Unpacking:

Remove Central and Remote units from from

 

the packaging material and check interior for any shipping damage. Inventory 

any included parts (depending on model) such as terminal connectors.

Bench Testing:

Before installing the units in the field they should be assembled and tested at a convenient bench top location.  This will 
make it easier to verify / change settings and check operation when both units are visible at the same time.  
It is also a chance to become familiar with the system if this is the first time using the Suprex system. It is much more 
difficult to set up and test the units when they are several thousand feet apart.
Both units will need to be connected with two conductors (see image below) and each will need to be powered by a suitable 
power supply. For testing purposes, the units can share the same power supply.

Basic Bench Test:

During initial setup, refer to the Run / Configuration mode settings (pgs 7-9).

1. Connect a suitable power supply to both units. Each unit should be provided with 8 - 16 Volts dc and approx 300mA.  

Units should be separated by a minimum of 24 inches.

2. Apply power.  After about a 1-2  second delay both units Diagnostic LED should be flashing green. The supervision relay 

(Relay 3) activates when the units are communicating. Note: Supervision relay is disabled by default (see pgs. 7-9).

3. Touch a jumper wire from the Ground connection to the Relay 1 input on the Central unit.  Relay 1 on the Remote unit 

should activate with an audible click.

4. Units are shipped from the factory set for the Wiegand data format. If a different format is required, set the DIP switch to 

the required reader and panel format (see pgs. 7-9) 

5. If a reader & panel are accessible, connect the reader to the Remote unit & the Central unit to the panel to verify card 

reads are accepted by the access control system. If troubleshooting is necessary, it is easier with units in close proximity.  

6. Once these steps are completed, the units are ready for installation at their permanent locations.

Summary of Contents for 816684001659

Page 1: ...x RS 485 SPX 7500 Wired Reader Extender Product Manual Cypress Integration Solutions 35 Years of Access Control Ingenuity CypressIntegration com 2019 Cypress Computer Systems 1778 Imlay City Road Lape...

Page 2: ...O Interface Wiegand maximum 248 bits pass through Strobed Clock Data F 2F Unsupervised LED 0 30V Range and Cable Requirements Typical range of 4000 ft 22 AWG Shielded Twisted Pair Additional Features...

Page 3: ...n Mode Settings 8 DIP Switch Map 9 Quick Reference for Typical Connections 10 Troubleshooting 11 Accessory I O I O Overview 12 Central Relay Inputs 13 Relay 1 2 I O 14 Remote Relay Inputs 15 Relay 3 4...

Page 4: ...Series Physical Dimensions and Mounting Hole Locations All dimensions are listed in inches EXP Enclosure 0 120 X 4 4 125 2 890 3 155 2 121 2 364 EXP 2000 SPX 7500 Enclosure 0 120 X 4 3 065 2 770 4 06...

Page 5: ...y 4 N O Relay 4 COM Relay 4 N C Relay 3 N O Relay 3 COM Relay 3 N C Ground Aux Output Relay 2 Input Relay 1 Input 8 16VDC Input Ground EXP EXP 5VDC Output Relay 4 Input Relay 3 Input LED Output D1 Dat...

Page 6: ...e powered by a suitable power supply For testing purposes the units can share the same power supply Basic Bench Test During initial setup refer to the Run Configuration mode settings pgs 7 9 1 Connect...

Page 7: ...ng properly Check that all connected EXPs are powered and properly connected For details on setting Configuration Mode see pgs 7 9 OPERATING MODES Wired Suprex products have 3 operating modes Run Mode...

Page 8: ...select Run Mode settings When switching to Run Mode always reselect Run Mode settings Central Remote Select Turn DIP switch 3 on for Central Mode turn off for Remote Mode Remote Digital Analog Relay...

Page 9: ...tion Mode setting the unit will need to be powered off turn DIP 1 on and other Configuration DIP Switches as needed power the unit on and the Status LED will be solid green The solid green LED means t...

Page 10: ...Ground exp exp 5V Out P R 4 P R 3 LED In D1 Data Out D0 Clock Out Relay 4 N O Relay 4 Com Relay 4 N C Relay 3 N O Relay 3 Com Relay 3 N C Ground Aux Output Relay 2 Input Relay 1 Input Door Strike Out...

Page 11: ...he access control panel data port are functional by directly connecting the reader to the data port and passing card data Check Suprex circuit boards for any signs of visual damage such as burnt trace...

Page 12: ...vated and will hold this state for as long as the Relay Input is set to 0Volts The Relay Inputs can be tested by making a jumper connection to ground and monitoring the change in continuity of the Rel...

Page 13: ...emote unit will be activated When the relay is activated the Relay Output pins will change continuity from N C and COM to N O and COM not shown in diagram Cypress Suprex RS 485 Series Accessory I O Ce...

Page 14: ...xp 5V Out Relay 4 Input Relay 3 Input LED Out D1 Data In D0 Clock In Relay 2 N O Relay 2 Com Relay 2 N C Relay 1 N O Relay 1 Com Relay 1 N C Ground Aux Input Not Used Not Used Remote 8 to 16 VDC Groun...

Page 15: ...ay output pins will change continuity from N C and COM to N O and COM not shown in diagram Relay 3 can used to send signals to the access panel while Supervision mode is active but it is important to...

Page 16: ...Ground exp exp 5V Out P R 4 P R 3 LED In D1 Data Out D0 Clock Out Relay 4 N O Relay 4 Com Relay 4 N C Relay 3 N O Relay 3 Com Relay 3 N C Ground Aux Output Relay 2 Input Relay 1 Input Central 8 to 16...

Page 17: ...ot Used pin is the new Relay 4 input pin Use the diagram below as a reference For most applications the analog relay inputs are sufficient But for instances where a significant delay is noticed in the...

Page 18: ...O Signal Diagram below shows how this signal is passed through he SPX 7500 Ground LED Out Data1 Data 0 N O COM Access Control Panel Card Reader Power Ground LED IN Data 1 Data 0 LED I O Signal Diagram...

Page 19: ...In pin The AUX I O Signal Diagram below shows how this signal is passed through the SPX 7500 AUX I O Signal Diagram Ground Input Data1 Data 0 N O COM Access Control Panel Card Reader Power Ground Out...

Page 20: ...ormally closed contact at the Remote unit and the other example is monitoring a normally open contact at the Remote unit In the examples given a normally closed contact will require a programming resi...

Page 21: ...x Central and Remote units must be configured with the total number of EXP pairs being used This is configured in the Run Mode settings and is controlled by DIP switches 6 7 and 8 Change settings on b...

Page 22: ...N C Ground Aux Output Relay 2 Input Relay 1 Input 8 to 16 VDC Ground exp exp 5V Out P R 2 P R 1 LED In D1 Data Out D0 Clock Out Relay 4 N O Relay 4 Com Relay 4 N C Relay 3 N O Relay 3 Com Relay 3 N C...

Page 23: ...k In Relay 2 N O Relay 2 Com Relay 2 N C Relay 1 N O Relay 1 Com Relay 1 N C Ground Aux Input Not Used Not Used 8 to 16 VDC Ground exp exp 5V Out Relay 4 Input Relay 3 Input LED Out D1 Data In D0 Cloc...

Reviews: