WPT-DB Installation Manual
Document No. 910-00014-01, Rev. 04
Page 13 of 20
Figure 15. Friction Clip and Control Lever
4. When the desired control pressure is achieved, press the OVR button to exit and
save the value.
•
A confirmation screen will appear and flash the stored control pressure for 3
seconds. Repeat the calibration procedure if this value does not match the
desired control pressure.
NOTE: The WPT-DB will automatically exit Calibration Mode if OVR is not pressed
after 3 minutes. The control pressure will NOT be saved and the WPT-DB
will return to the home screen.
5. Replace the WPT-DB front cover.
Friction Clip
Control Lever