![CyberPower Paragon OL1000RMXL2U User Manual Download Page 20](http://html.mh-extra.com/html/cyberpower/paragon-ol1000rmxl2u/paragon-ol1000rmxl2u_user-manual_2702795020.webp)
3.2 LED indicators
LEDs
21
to
24
provide three different indications:
1. Remaining backup time as a percentage (during normal
operation).
2. Percentage of load drawn by the protected equipment, when
button
20
is pressed.
3. Operating faults (alarmed by flashing LED and beep):
LED Alarm Condition
21
Site wiring fault
22
Battery fault or end of life warning
23
UPS fault
24
Overload
Description of LEDs
17
and
18
indicator status
for programmable outlets 1 and 2:
- OFF: The outlets are not supplied with power.
- Flashing: Status change in progress.
- ON: The outlets are supplied with power.
Outlets 1 and 2 can be remotely programmed and controlled.
They may be used for sequential start-up of the protected
applications, shedding of non-priority applications during operation on
battery power, and priority management at the end of battery backup
time to reserve the longest possible backup time for the most
sensitive applications. These outlets are programmed using
PowerPanel Business Edition Agent
software.
Operation 13