TROUBLE SHOOTING

 

 

Problem 

Possible Cause 

Solution 

Batteries are not fully charged. 

Recharge the battery by leaving the UPS 
plugged in. 

The UPS does not 
perform expected 
runtime. 

Battery is slightly worn out. 

Contact Cyber Power Systems at 

[email protected]

The on/off switch is designed to 
prevent damage by rapidly 
turning it off and on.   

Turn the UPS off. Wait 10 seconds and then 
turn the UPS on.   

The unit is not connected to an 
AC outlet. 

The unit must be connected to a 220-240V 
50/60Hz outlet.   

The battery is worn out. 

Contact Cyber Power Systems at 

[email protected]

The UPS will not 
turn on. 
 

Mechanical problem. 

Contact Cyber Power Systems at 

[email protected]

Fuse is blown due to overload 

Turn the UPS off and unplug at least one piece 
connected equipment. Unplug the power cord of 
the UPS then remove the fuse compartment 
beneath the power inlet of the UPS and replace 
the blown fuse with a spare one. Lock the 
compartment back to the UPS. Connect power 
cord then turn the UPS on. Make sure that your 
spare fuse meets the specification: 6.3A, 250V, 
5x10mm. 

Batteries are discharged 

Allow the unit to recharge for at least 4 hours. 

Outlets do not 
provide power to 
equipment 

Unit has been damaged by a 
surge or spike. 

Contact Cyber Power Systems at 

[email protected]

The serial cable is not 
connected. 

Connect the serial cable to the UPS unit and 
an open serial port on the back of the 
computer. You must use the cable that came 
with the unit. 

The serial cable is connected to 
the wrong port. 

Try another serial port of your computer. 

The unit is not providing battery 
power. 

Shutdown your computer and turn the UPS off. 
Wait 10 seconds and turn the UPS back on. 
This should reset the unit. 

PowerPanel

®

 Plus 

is inactive (all icons 
are gray). 

The serial cable is not the cable 
that was provided with the unit. 

You must use the cable included with the unit 
for the software. 

 

 

 

 

TECHNICAL SPECIFICATIONS 

Model

 

OP350E

 

OP500TE 

Capacity  (VA) 

350VA 

500VA 

Capacity  (Watts) 

200W 

300W 

Input  

 

 

 

Input Voltage Range 

220-240Vac 

Frequency Range 

50/60 Hz 

Output  

 

 

 

On Battery Output 

Voltage 

Simulated Sine Wave at /- 7% 

On Battery Output 

Frequency  

50 Hz 

Overload Protection 

On Utility: Fuse, On Battery: Internal Current Limiting 

Surge Protection and Filtering 

Lightning / Surge 

Protection 

Yes 

Network Protection 

RJ45 (One In/One Out) 

Physical  

 

 

 

Total # of UPS 

Receptacles 

Maximum Dimensions 

23.8cm*8.0cm*13.7cm 

Weight (Kg) 

4.6 

5.3 

Battery  

 

 

 

Sealed Maintenance 

Free Lead Acid 

Battery 

12V / 4AHx1 

12V/4.5AHx1 

User Replaceable 

Yes, Hot Swappable Battery Pack 

Typical Recharge 

Time 

8 Hours 

Warning Diagnostics 

Indicators 

Power On, Using Battery, Boost, Buck 

Audible Alarms 

On Battery, Low Battery, Overload 

Environmental      

 

Operating 

Temperature 

+32

°

F to 95

°

F ( 0

°

C to 35

°

C ) 

Operating Relative 

Humidity 

0 to 95% NON-CONDENSING 

Communication    

 

 

PowerPanel

®

 Plus

 

Software 

Windows 98/ME/2000/NT/XP, Server 2003 

Management      

Auto-Charger Yes 

Auto-Restart Yes 

USB Yes 

 
 

 

DEFINITIONS FOR ILLUMINATED LED INDICATORS 

 

 

 
 
 

Power 

On 

 
 
 

Using 

Battery

 
 
 
 
 

 
 
 
 
 

 
 

 

Fuse 

 
 
 
 

Alarm

 

Condition 

On Off Off Off 

Normal 

Off 

Normal 

On Off On 

Off 

Normal 

Off 

Max. boost 13% of input 
voltage for output regulation 
while input voltage is from 
12% to 22% under nominal. 

On Off Off 

On 

Normal 

Off 

Max. buck 12% of input 
voltage for output regulation 
while input voltage is from 
10% to 17% over nominal. 

Off On Off Off 

Normal 

Two 

Beeps 

Utility Failure- The UPS is 
providing battery power to the 
Battery-Power Supplied outlets. 

Off On Off Off 

Normal 

Rapid 

Beeps 

Utility Failure- The UPS is 
providing battery power.  The 
rapid beeps indicate the battery 
will run out of charge within a few 
minutes. 

Off On/Off 

On/Off 

On/Off 

Blown 

Two 

beeps or 

rapid 

beeps 

Overload- Occurs in the Full-time 
Surge Protection Outlets. Please 
turn the UPS off and unplug at 
least one piece of equipment from 
the UPS.  Replace the fuse with 
a spare one then turn the UPS 
on. 

Off On/Off 

On/Off 

On/Off 

Normal/ 

Blown 

Long 

Beep 

Overload- Occurs in the 
Battery-power Supplied Outlets. 
Turn the UPS off and unplug at 
least one piece of equipment from 
the UPS. Check the fuse and do 
the replacement if necessary. 
Turn the UPS on. 

 

For more information, visit 

eu.cyberpowersystems.com

 or contact 

 

CyberPower Systems B.V. Flight Forum 3545, 5657DW Eindhoven, The Netherlands 

TEL: +31 (0)40 2348170, FAX: +31 (0)40 2340314, E-MAIL: 

[email protected]

   

 

CyberPower Systems Inc. (USA) 4241 12th Avenue East Suite 400 Shakopee, MN 55379, U.S.A. 

Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL: 

[email protected]

   

 

Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved. Reproduction in 

whole or in part without permission is prohibited. PowerPanel

®

 and PowerPanel

®

 Plus are 

trademarks of CyberPower Systems (USA) Inc. 

 

CyberPower warrants to you, the original purchaser, that CyberPower UPS will be free from defects 

in design, assembly, materials and workmanship for two years ( battery is only one year) from the 

date of original purchase.    Any warranty services, please contact your local dealers or distributors. 