CyberPower OL6000RT3UTF Specifications Download Page 3

SMART APP SERIES

OL6000RT3UTF SPECIFICATIONS

GENERAL

UPS Topology

Double-Conversion Online

Energy Saving

ECO Mode Efficiency >95%

INPUT

Voltage

200 – 240Vac

Input Frequency Range

40Hz – 70Hz (auto-sensing)

Input Power Factor

0.99

Cold Start

Yes

Backfeed Protection

Yes

Plug Style

NEMA L6-30P

Cord Length (FT)

6

OUTPUT

VA

6,000 (6 kVA)

Watts

5,400 (5.4 kW)

On Battery Waveform

Sine Wave

On Battery Voltage

120Vac; 200, 208, 220, 230, 
240Vac (Configurable) ±2%

On Battery Frequency

50/60Hz (Auto-Sensing or 
Configurable) ±0.25Hz

Rated Power Factor

0.9

Harmonic Distortion

THD < 3% at Linear Load,  
< 5% at Non-linear Load

Crest Factor

3:1

ECO Mode Voltage Regulation

±10%, ±15% (Configurable)

Outlets - Total

15

Outlet Type

NEMA L6-20R (2)  
NEMA L6-30R (1)
NEMA 5-20R (12)

Bypass

Internal Bypass  
(Automatic and Manual)

Transfer Time

0 ms

SURGE PROTECTION & FILTERING

Surge Suppression

Network Grade  
Surge Protection

Phone / Network Protection 
RJ11/RJ45

1-In / 1-Out

EMI/RFI Filtration

Yes

BATTERY

Runtime at Half Load (min.)

15.8

Runtime at Full Load (min.)

5.3

Battery Type

Sealed lead acid

Battery Size

12V/7.2AH

Battery Quantity

20

User Replaceable

Yes

Hot Swappable

Yes

Typical Recharge Time

4 Hours (*2.5 w/Fast Charge 
Technology)

Smart Battery Management 
(SBM) Mode

Yes

Expandable Battery  
Module Option

BP240V30ART3U

MANAGEMENT & COMMUNICATIONS

LCD Control Panel

The LCD control panel 
enables users to check 38 
different settings or status 
options via the UPS Status 
menu, UPS Setup menu and 
run Testing menus. Refer to 
the "Function Setup Guide" 
on the "Resources" tab for 
complete options.

Removable LCD Control Panel

Yes - Requires a separate 
DB26 Cable  
(Two Ports - Front/Back)

HID Compliant USB Port

Yes

Serial Port

Yes

EPO Port

Yes

Dry Contacts

Yes

Management Cable

USB Cable, Serial Cable

LED Indicators

Power On (White),  
Line Mode (Green), Battery 
Mode (Yellow), Bypass Mode 
(Yellow), Fault (Red), Replace 
Battery (Red)

Audible Alarms

Battery Mode, Battery Low, 
Overload, UPS Fault,  
Replace Battery

MANAGEMENT & COMMUNICATIONS (CONT.)

Software

PowerPanel

®

 Business Edition

SNMP / HTTP Remote 
Monitoring

Yes - Optional RMCARD302 
or RMCARD303

PHYSICAL

Form Factor

Rack / Tower Convertible

Power Module, Battery Module and Step-down Tranformer

Dimensions (WxHxD) (in.)

17 x 14 x 26

Dimensions (WxHxD) (mm.)

433 x 355.6 x 660

Weight (lbs.)

348.3

Weight (Kg.)

158.3

Installed Rack Height

8U

Enclosure ConStruction

Steel

Mounting Hardware Included:

Yes

ENVIRONMENTAL

Operating Temperature

32 °F to 104°F  
0°C to 40 °C

Operating Humidity

0% – 90% non condensing

Operating Elevation

0 – 10000 feet  
0 – 3000 meters

Storage Temperature

5 – 113 °F (-15 – 45 °C) 

Storage Relative Humidity 

0% – 95% non condensing

Storage Elevation 

0 – 50000 feet  
0 – 15000 meters

Audible noise at 1.5M from 
surface of unit 

55 dBA

Online Thermal Dissipation

2048 BTU/hr

CERTIFICATIONS

Certifications

UL1778,  
CSA C22.2 NO.107.3-05, 
FCC DOC Class A

ROHS

ROHS Compliant

WARRANTY

Product Warranty

3 Years Limited

Connected Equipment 
Guarantee

Lifetime

CEG Amount

$300,000 

© 2013 CyberPower Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners. CyberPower reserves the right to modify product information or specifications without previous notice. The information presented is accurate at the time of publication. 

10-2013

CyberPower Systems, Inc. designs and manufactures state-of-the-art power protection and distribution equipment for corporate, business, home, government and educational markets. CyberPower leads the industry by surpassing customer expectations in the 
development, design, construction, durability and functionality of uninterruptible power supply (UPS) products for computers, peripherals and connected devices. CyberPower Systems operates in the Asian Pacific, North American and European markets. 
For additional information, including sales office locations and authorized reseller partners, visit 

CPSww.com

.

*Fast Charge Technology requires the External Battery Module (EBM) to be connected to a 208Vac utility power source.