HSTP3T 60-500 KE User Manual
Chapter 2 Installation Instruction
2.6 Power Cables
2.6.1 Specifications
The UPS power cables are recommended in Table 2.2.
Table 2.2 Recommended cables for power cables
Contents
60kVA
80kVA
90kVA
100kVA 120kVA 150kVA
Main
Input
Main Input
Current(A)
96
128
144
159
191
239
CableSection
(mm²)
A
25
35
35
50
70
95
B
25
35
35
50
70
95
C
25
35
35
50
70
95
N
25
35
35
50
70
95
Main
Output
Main Output
Current(A)
91
121
136
152
182
227
CableSection
(mm²)
A
25
35
35
50
70
70
B
25
35
35
50
70
70
C
25
35
35
50
70
70
N
25
35
35
50
70
70
Bypass
Input
(Optional)
Bypass Input
Current(A)
91
121
136
152
182
227
CableSection
(mm²)
A
25
35
35
50
70
70
B
25
35
35
50
70
70
C
25
35
35
50
70
70
N
25
35
35
50
70
70
Battery
Input
Battery Input
current(A)
125
167
188
208
250
313
CableSection
(mm²)
+
35
50
70
70
95
120
-
35
50
70
70
95
120
N
35
50
70
70
95
120
PE
CableSection
(mm²)
PE
50
50
70
70
95
120
Contents
200kVA 250kVA 300kVA 400kVA 500kVA
Main
Input
Main Input
Current(A)
319
398
478
638
797
CableSection
(mm²)
A
120
185
185
2*150
2*185
B
120
185
185
2*150
2*185
C
120
185
185
2*150
2*185
N
120
185
185
2*150
2*185
Main
Output
Main Output
Current(A)
303
379
454
606
758
CableSection
(mm²)
A
120
185
185
2*150
2*185
B
120
185
185
2*150
2*185
C
120
185
185
2*150
2*185
N
120
185
185
2*150
2*185
Bypass
Input
(Optional)
Bypass Input
Current(A)
303
379
454
606
758
CableSection
(mm²)
A
120
185
185
2*150
2*185
B
120
185
185
2*150
2*185
C
120
185
185
2*150
2*185
N
120
185
185
2*150
2*185
Battery
Input
Battery Input
current(A)
417
521
626
833
1042
CableSection
(mm²)
+
185
240
240
2*185
2*240
-
185
240
240
2*185
2*240
N
185
240
240
2*185
2*240
PE
CableSection
(mm²)
PE
185
2*120
2*120
2*150
2*150