background image

ECO FUNCTION SETUP

ECO Function

When the ECO function is active the UPS can 

detect whether the PC that is connected to the 

USB port is turned on or off. If the PC is turned 

off, the UPS will turn off the ECO controlled 

outlets and cut power to the devices connect-

ed to them in order to save power.
Generally, these are peripherals that are not 

used when the PC is not turned on.

ECO Controlled Outlets

Three of the surge-only outlets are also ECO con-

trolled outlets. When the PC that is connected to 

the USB port is turned off, the UPS will turn off 

the ECO controlled outlets to save energy.

ECO Setup

1. The factory default setting is OFF. ECO mode 

can only be enabled/disabled and will only be 

active when the UPS is receiving utility power 

and not in battery mode.
2. For the EC650/850LCD, press the Mode 

switch for approximately 3 seconds to enter 

setup mode and select the ECO function. When 

the ECO function is selected, press the Mode 

switch for 3 seconds to turn the function ON or 

OFF. Once ON or OFF is selected, wait 8 sec-

onds for the setting to be confirmed and the 

LCD screen will return to status mode. For the 

EC450/550/750G, press the ECO button for 3 

seconds to turn ON or OFF the ECO function.
3. When the ECO function is OFF, utility power 

from the ECO outlets will always be on. When 

the ECO function is ON, utility power from the 

ECO outlets will turn off if the PC connected 

to the UPS via the USB port is turned off or if 

there is no PC is connected to the UPS via USB.

ECO Indicator

The LED will blink when the ECO function 

is turned ON but the PC is either off or not 

connected. The LED will be solid if the ECO 

function is turned on and the connected PC is 

on. The LED is off when the ECO function is 

disabled. See below table for more information.

DEFINITIONS FOR LED INDICATORS & AUDIBLE ALARMS 

 

ECO Indicator

ECO Function

ECO Outlet Status

Condition

Solid (green)

ON

With Utility Power

When PC is ON and USB port on the UPS is 

connected, Peripherals will receive power to 

operate.

Blinking

ON

Without Utility Power

When PC is OFF or the USB port on the UPS 

is not connected, power to the Peripherals will 

be turned off.

OFF

OFF

Always with Utility Power

When PC is ON/OFF, Peripherals is always ON.

POWER

ALARM

CONDITION

On

Off

Normal

On

Beep twice  

every 30 seconds

Utility Failure - The UPS is providing power to battery power-supplied 

outlets from its battery.

On

Rapid beeping  

every 1/2 second

Utility Failure - The UPS is providing battery power. Rapid beeping  

indicates the unit will run out of power shortly. 

On/Off

Constant tone

Battery Overload - Occurs when connected equipment exceeds the  

listed capacity of the UPS. Turn the UPS off, unplug at least one piece of 

equipment from battery outlets, wait 10 seconds, reset the circuit breaker 

and turn the unit on.

(EC650LCD and EC850LCD only) 

INPUT voltage meter:

 This meter measures the 

AC voltage that the UPS system is receiving 

from the utility wall outlet. The UPS is designed 

to continuously supply connected equipment 

with stable output voltage. In the event of a 

complete power loss, extended power reduc-

tion, or over-voltage, the UPS relies on its inter-

nal battery to supply consistent 110/120 output 

voltage. The INPUT voltage meter can be used 

as a diagnostic tool to identify poor-quality 

input power.

OUTPUT voltage meter:

 This meter measures, 

in real time, the AC voltage that the UPS sys-

tem is providing to the connected equipment 

during normal AC/Utility Power mode and 

battery backup mode.

ESTIMATED RUNTIME:

 This displays the run 

time estimate of the UPS with the current bat-

tery capacity and load.

NORMAL icon:

 This icon appears when the 

UPS is working under normal conditions.

BATTERY icon:

 During an extended power re-

duction or power outage, this icon appears and 

an alarm sounds (two short beeps followed by 

a pause) to indicate the UPS is operating from 

its internal battery. The alarm will continue to 

sound during a prolonged power reduction or 

power outage. The BATT.CAPACITY meter will 

show one 20% capacity segment remaining 

to indicate the UPS’s battery is nearly out of 

power. You should save files and turn off your 

equipment immediately.

OVER LOAD icon:

 This icon appears and an 

alarm sounds to indicate the battery-supplied 

outlets are overloaded. To clear the overload, 

unplug some of your equipment from the 

battery-supplied outlets until the icon turns off 

and the alarm stops.

BATTERY  CAPACITY meter:

 This meter dis-

plays the approximate charge level of the UPS’s 

internal battery in 20% increments. During a 

power outage or extended power reduction, 

the UPS switches to battery power (the BAT-

TERY icon appears) and the battery charge 

level decreases.

LOAD CAPACITY meter:

 This meter displays 

the approximate output load level of the UPS 

battery outlets in 20% increments.

DEFINITIONS FOR ILLUMINATED LCD INDICATORS 

The LCD display indicates a variety of UPS operational 

conditions. All descriptions apply when the UPS is 

plugged into an AC outlet and turned on or when the 

UPS is on battery.

Summary of Contents for EC450G

Page 1: ... of Electronic Computer Data Processing Equipment ANSI NFPA 75 CAUTION To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit over current protection in accordance with the National Electric Code ANSI NFPA 70 DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT CyberPower Systems does not sell products for life support or medical applications DO NOT use in...

Page 2: ...r proper accessibility 1 Battery and Surge Protected Outlets The unit has battery powered surge suppression outlets to ensure temporary uninterrupted operation of your equip ment during a power failure DO NOT plug a laser printer paper shredder copier space heater vacuum cleaner sump pump or other large electrical device into the Battery and Surge Protected Outlets The power demands of these devic...

Page 3: ...eeping every 1 2 second Utility Failure The UPS is providing battery power Rapid beeping indicates the unit will run out of power shortly On Off Constant tone Battery Overload Occurs when connected equipment exceeds the listed capacity of the UPS Turn the UPS off unplug at least one piece of equipment from battery outlets wait 10 seconds reset the circuit breaker and turn the unit on EC650LCD and ...

Page 4: ...the cable in The unit is not providing battery power Shutdown your computer and turn the UPS off Wait 10 seconds and turn the UPS back on This should reset the unit Additional troubleshooting and contact information can be found online at CyberPowerSystems com support TECHNICAL SPECIFICATIONS SYSTEM FUNCTION BLOCK DIAGRAM Model EC450G EC550G EC750G EC650LCD EC850LCD Capacity 450VA 260W 550VA 330W ...

Page 5: ...cur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment t...

Reviews: