User Manual 19 / 43 CPS Mini Central series
5.2
Selecting the Installation Location
This is guidance for installer to choose a suitable installation location, to avoid damage
to device and operators,
The wall selected to install the inverter must be strong and firm enough to support and
bear the weight of the inverter for a long period time. (Refer to Chapter 3.2)
The location selected must be suitable for inverters’ dimension. (Refer to 3.2
Dimensions and Fig.5.2 Required Clearances)
Do not install the inverter on structures constructed of flammable materials.
Never install the inverter in environment without air flow, nor dust environment.
The Ingress Protection rate is IP65 which means the inverter can be installed outdoors
and indoors.
Do not expose the inverter to direct sunlight to avoid the power and efficiency derating
caused by excessive heating.
The humidity of the installation location should be 5~95% without condensation.
The ambient temperature applied on the inverter should be -25
℃
~+60
℃
.
The installation location must be freely and safely to make service possible all the time.
The inverter can be installed with vertically, backward tilted and horizontally.
Never install with upset-down and forward tilted.( Refer to drawings below).
Fig5.1