SAFETY AND EMC INSTRUCTIONS 

 

 
(SAVE THESE INSTRUCTIONS) 

 
This manual contains important safety instructions. Please read and follow all instructions 
carefully during installation and operation of the unit. Read this manual thoroughly before 
attempting to unpack, install, or operate your Emergency Power System (EPS). 

 

CAUTION!

    To prevent the risk of fire or electric shock, install in a temperature and 

humidity controlled indoor area free of conductive contaminants. (Please see specifications 
for acceptable temperature and humidity range). 
 

CAUTION!

    To reduce the risk of electric shock, do not remove the cover. 

 

CAUTION!

    EPS must be connected to an AC power outlet with circuit breaker 

protection. Do not plug into an outlet that is not grounded. If you need to de-energize this 
equipment, turn off and unplug the unit. 
 

CAUTION!

    To avoid electrical shock, turn off the unit and unplug it from the AC power 

source before servicing EPS, replacing the external battery or installing equipment. 
 

CAUTION!

   

To reduce the risk of fire, only connect the EPS to a circuit with 25 amperes 

maximum branch circuit over-current protection in accordance with the CE requirement. 
 

CAUTION! 

The building wiring socket outlet (shockproof socket outlet) must be easily 

accessible and close to the EPS. 

CAUTION! 

Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable 

of your equipment) to connect the EPS to the building wiring socket outlet (shockproof 
socket outlet). 

CAUTION! 

Please use only VDE-tested, CE-marked power cables to connect the loads 

to the EPS. 

CAUTION! 

When installing the equipment, ensure that the sum of the leakage current of 

the EPS and the connected equipment does not exceed 3.5mA. 

CAUTION! 

This is permanently connected equipment and only qualified maintenance 

personnel may carry out installations. 

CAUTION! 

Do not disconnect the mains cable on the EPS or the building wiring socket 

outlet (shockproof socket outlet) during operations since this would remove the protective 
ground of the EPS and of all connected loads. 

Summary of Contents for CPS3000PIE

Page 1: ...CPS3000PIE USER MANUAL K01 0000010 00 ...

Page 2: ...D EMC INSTRUCTIONS 1 INSTALLING YOUR EPS 3 BASIC OPERATION 4 REPLACING THE BATTERY 6 DEFINITIONS FOR ILLUMINATED LCD 7 EPS STATUS INQUIRY AND FUNCTIONS SETUP 8 FAULT WARNING DISPLAY AND ALARM 10 TROUBLESHOOTING 11 TECHNICAL SPECIFICATIONS 12 ...

Page 3: ... source before servicing EPS replacing the external battery or installing equipment CAUTION To reduce the risk of fire only connect the EPS to a circuit with 25 amperes maximum branch circuit over current protection in accordance with the CE requirement CAUTION The building wiring socket outlet shockproof socket outlet must be easily accessible and close to the EPS CAUTION Please use only VDE test...

Page 4: ...er demands of these devices will overload and possibly damage the unit DO NOT INSTALL THE EPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR HEAT DO NOT BLOCK OFF VENTILATION OPENINGS IN THE EPS S HOUSING DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO EPS OUTPUT SOCKETS SAFETY EN62040 1 1 EMI Conducted Emission IEC EN 62040 2 Category C2 Radiated Emission IEC EN 62040 2 Category C...

Page 5: ...edder copier space heater vacuum or other large electrical device into the EPS The power demand of these devices may overload and damage the unit DO NOT use with medical or life support equipment DO NOT use with or near aquariums as condensation may cause the unit to short 3 After connecting the hard wires plug the EPS into a 2 pole 3 wire grounded receptacle wall outlet Make sure the wall branch ...

Page 6: ... D must be 2AWG or greater 4 DC Circuit Breaker Located on the side of the EPS the circuit breaker serves to provide overload and fault protection 5 AC Output Circuit Breaker Located on the side of the EPS the circuit breaker serves to provide overload and fault protection The breaker only works on 1b 6 AC Input Circuit Breaker Located on the side of the EPS the circuit breaker serves to provide o...

Page 7: ... EPS status and set up functions using the toggle Installation Guide Note The installation must be done by professionals 1 Remove the cover from the back of the machine 2 Make sure both the POWER SW and the BATTERY SW are turned off Step1 UPS will not function if the switch is enabled Enabling this switch provides the bypass for charge only Step 1 3 Connect the AC OUTPUT connections AC plugs or te...

Page 8: ...reassemble the back cover The installation is now complete 11 When the external battery needs to be maintained or replaced remember to turn the machine off Once off remove the AC power source and switch off the BATTERY SW before maintenance or replacing the batteries When the work is complete please start from Step 3 to re install the machine REPLACING THE BATTERY CAUTION Read and follow the IMPOR...

Page 9: ... of a complete power loss severe brownout or over voltage the EPS will rely on its external battery to supply consistent 220 output voltage The Input Voltage Meter can be used as a diagnostic tool to identify poor quality input power 2 OUTPUT VOLTAGE Meter This meter measures the AC voltage that the EPS is providing to the computer It displays normal line mode AVR mode and battery backup mode 3 NO...

Page 10: ...vel in 20 increments of the EPS s external battery During a blackout or severe brownout the EPS will switch to battery power the ON BAT icon will be illuminated and the charge level will decrease 10 LOAD CAPACITY Meter This meter displays the approximate output load level in 20 increments of the EPS s battery outlets EPS Status Inquiry and Functions Setup 1 General Mode a Press the Display button ...

Page 11: ...ectricity voltage supplied in the area country where the EPS will be used 220V 230V and 240V may be selected The system default setting is 220V Function description AVR Dynamic Voltage Compensation works automatically based on the system voltage settings d Static Frequency Tolerance There are 6 settings The default setting is 10 Function description The settings may be adjusted to the quality of t...

Page 12: ...NG DISPLAY AND ALARM 1 Overheat Protection z EPS overheat The output of the machine is removed and the LCD display shows the temperature exceeds 70 157 FAULT Icon lights as well 2 Over voltage Protection The output of the machine is removed Over Load and FAULT Icon lights on the LCD display 3 Battery Missing A long beep is heard and Battery Icon flashes 4 The following table shows each correspondi...

Page 13: ... Voltage Output Off the battery voltage is too high during cold start 1 Check Input Output connection 2 Check the reason for battery over voltage TROUBLESHOOTING Problem Possible Cause Solution Full time surge protection outlets stop providing power to equipment Circuit breaker button is projecting from the side of the unit Circuit breaker has tripped due to an overload Turn the EPS off and unplug...

Page 14: ...ty Circuit Breaker On Battery Internal Current Limiter Transfer Time 10 ms Typical Output Receptacles Schuko 2 Terminal Block External Battery Voltage x Recommended Rating X Quantity 12V x 100Ah X 2 External Battery Voltage Rating 24V External Battery Type Sealed Maintenance Free Lead Acid Battery External Battery Protection DC Circuit Breaker Hot Swappable External Battery Yes Extended Runtime Ye...