SAVING LAMP, TV, JUICER & MIXER etc. It is not suitable for high-power motor or inductive 

load, such as the fridge of 1KW, the motor of 800W, AIR COOLER

having risk of rebooting

and so on. In this mode, the INVERTER operating voltage in AC mode is within 190~260Vac 

with the same output voltage. The line sensitivity is higher. 

 

B. Select 

“Wide”

  setting  to  save  energy.  In  this  mode  the  operating  range  of  voltage  for  the 

INVERTER is 100-280Vac. Therefore the output voltage will be the same as the MAINS input 

voltage. The INVERTER unit in this mode has a lower sensitivity with a longer transfer time for 

switching from AC mode to battery mode in the event of power failure. You can safely connect 

and use home appliances which are not sensitive to transfer time limitations such as florescent 

tubes, bulbs, TV etc. 

 

6. 

AC outlet 

The INVERTER provides one outlet for connected equipment to insure temporary uninterrupted 

operation during a power failure and against surges and spikes. 

 

7. 

AC Inlet

   

Connect to utility power through the input power cord. 

 

  Functional Test

 

 

AC Mode 

The INVERTER delivers power to the load derived from the utility and maintains proper battery charge. 

 

On-Battery Mode 

The INVERTER operates on battery when the utility voltage has fallen outside the limits. Local users are 

alerted to this mode of operation by visual and audible indicators. The INVERTER provides power to the 

load from the battery and the output voltage of the INVERTER are regulated within a narrow range 

 

1. 

Switch On 

Press the power switch then the status LED will

 

light up. 

 

2. 

Switch Off 

Press again the power switch, the status LED will go off. 

 

3. 

Cold Start / Start on Battery:   

          This INVERTER can be turned on even when AC is not present. 

 

Press the power switch then the status LED will

 

light up. 

 

ROUTINE MAINTENANCE AND STORAGE

 

 

ROUTINE MAINTENANCE

 

1. 

Use dry soft clothes to clean the panel and plastic parts. Do not use any detergent that contains 

alcoholic ingredient.   

 

2. 

Unplug the INVERTER from power inlet if the INVERTER will not operate for long period of time. 

 

STORAGE

 

1. 

First turn off your INVERTER and disconnect its power cord from the wall outlet. Disconnect all 

cables connected the INVERTER to avoid battery drain.   

 

2. 

The INVERTER should be stored in a cool dry location. 

 

3. 

Make sure the battery is fully charged before the INVERTER is stored. 

 

4.

 

For extended storage in moderate climates, the battery should be charged for 12 hours every 3 

months by plugging the power cord into the wall receptacle and turning on the main switch. Repeat 

it every 2 months in high temperature locations.

 

 

DEFINITIONS FOR INDICATORS 

 

 

Condition 

Fault 

 

Battery Mode 

 

AC Mode   

 

Alarm 

 

Normal Mode 

(Battery is fully charged) 

Off 

Off 

On 

Off 

Normal Mode 

(Battery is charging) 

Off 

Off 

Normally On but blink 

every 5 seconds 

Off 

Battery Mode   

(above low battery voltage) 

Off

 

On 

Off 

Off 

Battery Mode 

(under low battery voltage) 

Off 

On 

Off 

Beeps every 2 

seconds 

Off charge mode 

(Auto bypass) 

Off 

Off 

Normally Off but blink 

every 5 seconds 

Off 

Fault   

On 

Off 

Off 

Beeps 

continuously 

Overload 

Beeps every 

0.5 seconds 

Off 

Off 

Beeps every 0.5 

seconds 

 
 
 
 
 
 
 
 

 

TROUBLE SHOOTING

 

 

Problem 

Possible Causes 

Remedy 

No LED display 

1.  Battery Weak 

1. Re-charge battery 

2.  Battery defective 

2. Battery replacement. 

3.  Power switch is not 

pressed 

3. Press and hold power 

switch. 

Mains normal but not works in 

AC mode 

1.  AC Input    missing 

1. Check AC input 

connection. 

2. Input protector is effective 

2. Reset the input protector. 

Alarm buzzer beeps 

continuously 

Overload 

Verify that the load matches 

the capability specified in 

the specs. 

Backup time is shortened 

Overload 

Remove some non-critical 

load. 

Battery voltage is too low. 

Charge battery for 8 hours 

or more. 

If any abnormal situations occur that are not listed above, please contact service personnel.

 

 
 

TECHNICAL SPECIFICATIONS 

 

Model 

 

CPS1000EI 

CPS2000EI

 

Capacity    (VA) 

1000VA 

2000VA 

Capacity    (Watts) 

600W 

1200W 

Input 

Input Voltage Range 

Wide mode: 100VAC-280VAC 

Narrow mode: 190VAC-260VAC 

Frequency Range 

50/60Hz 

Output 

On Battery Output 

Voltage 

Simulated Sine Wave at /-10% 

On Battery Output 

Frequency   

50/60Hz   

Overload Protection 

On Utility: Circuit Breaker, On Battery: Internal Current Limiting 

Physical

 

Total # of INVERTER 

Receptacles 

(1) Shuko 

Maximum Dimensions 

265mm(L)*250cm(W)*90cm(H) 

Weight   

1.9 kg / 4.2 Lbs 

2.0 kg / 4.4 Lbs 

Battery

 

Lead Acid Battery 

12VDC 

24VDC 

Charging Voltage 

13.7VDC 

27.4VDC 

Charging Current 

10A 

Warning Diagnostics 

Indicators 

AC Mode, Battery mode, Fault 

Audible Alarms 

Low Battery, Overload, Fault 

Environmental

 

Operating Temperature 

+32

°

F to 104

°

F ( 0

°

C to 40

°

C ) 

Operating Relative 

Humidity 

0 to 90% NON-CONDENSING 

Management

 

Auto-Charger 

Yes 

Auto-Restart 

Yes 

 

Visit 

www.cpsww.com

 for more product information and the nearest CyberPower local contact for your 

region. 

 

 

Entire contents copyright ©2011 CyberPower Systems, Inc All rights reserved. Reproduction 

in whole or in part without permission is prohibited. 

 

 

 

All manuals and user guides at all-guides.com

Reviews: