SAVING LAMP, TV, JUICER & MIXER etc. It is not suitable for high-power motor or inductive
load, such as the fridge of 1KW, the motor of 800W, AIR COOLER
(
having risk of rebooting
)
and so on. In this mode, the INVERTER operating voltage in AC mode is within 190~260Vac
with the same output voltage. The line sensitivity is higher.
B. Select
“Wide”
setting to save energy. In this mode the operating range of voltage for the
INVERTER is 100-280Vac. Therefore the output voltage will be the same as the MAINS input
voltage. The INVERTER unit in this mode has a lower sensitivity with a longer transfer time for
switching from AC mode to battery mode in the event of power failure. You can safely connect
and use home appliances which are not sensitive to transfer time limitations such as florescent
tubes, bulbs, TV etc.
6.
AC outlet
The INVERTER provides one outlet for connected equipment to insure temporary uninterrupted
operation during a power failure and against surges and spikes.
7.
AC Inlet
Connect to utility power through the input power cord.
Functional Test
AC Mode
The INVERTER delivers power to the load derived from the utility and maintains proper battery charge.
On-Battery Mode
The INVERTER operates on battery when the utility voltage has fallen outside the limits. Local users are
alerted to this mode of operation by visual and audible indicators. The INVERTER provides power to the
load from the battery and the output voltage of the INVERTER are regulated within a narrow range
1.
Switch On
Press the power switch then the status LED will
light up.
2.
Switch Off
Press again the power switch, the status LED will go off.
3.
Cold Start / Start on Battery:
This INVERTER can be turned on even when AC is not present.
Press the power switch then the status LED will
light up.
ROUTINE MAINTENANCE AND STORAGE
ROUTINE MAINTENANCE
1.
Use dry soft clothes to clean the panel and plastic parts. Do not use any detergent that contains
alcoholic ingredient.
2.
Unplug the INVERTER from power inlet if the INVERTER will not operate for long period of time.
STORAGE
1.
First turn off your INVERTER and disconnect its power cord from the wall outlet. Disconnect all
cables connected the INVERTER to avoid battery drain.
2.
The INVERTER should be stored in a cool dry location.
3.
Make sure the battery is fully charged before the INVERTER is stored.
4.
For extended storage in moderate climates, the battery should be charged for 12 hours every 3
months by plugging the power cord into the wall receptacle and turning on the main switch. Repeat
it every 2 months in high temperature locations.
DEFINITIONS FOR INDICATORS
Condition
Fault
Battery Mode
AC Mode
Alarm
Normal Mode
(Battery is fully charged)
Off
Off
On
Off
Normal Mode
(Battery is charging)
Off
Off
Normally On but blink
every 5 seconds
Off
Battery Mode
(above low battery voltage)
Off
On
Off
Off
Battery Mode
(under low battery voltage)
Off
On
Off
Beeps every 2
seconds
Off charge mode
(Auto bypass)
Off
Off
Normally Off but blink
every 5 seconds
Off
Fault
On
Off
Off
Beeps
continuously
Overload
Beeps every
0.5 seconds
Off
Off
Beeps every 0.5
seconds
TROUBLE SHOOTING
Problem
Possible Causes
Remedy
No LED display
1. Battery Weak
1. Re-charge battery
2. Battery defective
2. Battery replacement.
3. Power switch is not
pressed
3. Press and hold power
switch.
Mains normal but not works in
AC mode
1. AC Input missing
1. Check AC input
connection.
2. Input protector is effective
2. Reset the input protector.
Alarm buzzer beeps
continuously
Overload
Verify that the load matches
the capability specified in
the specs.
Backup time is shortened
Overload
Remove some non-critical
load.
Battery voltage is too low.
Charge battery for 8 hours
or more.
If any abnormal situations occur that are not listed above, please contact service personnel.
TECHNICAL SPECIFICATIONS
Model
CPS1000EI
CPS2000EI
Capacity (VA)
1000VA
2000VA
Capacity (Watts)
600W
1200W
Input
Input Voltage Range
Wide mode: 100VAC-280VAC
Narrow mode: 190VAC-260VAC
Frequency Range
50/60Hz
Output
On Battery Output
Voltage
Simulated Sine Wave at /-10%
On Battery Output
Frequency
50/60Hz
Overload Protection
On Utility: Circuit Breaker, On Battery: Internal Current Limiting
Physical
Total # of INVERTER
Receptacles
(1) Shuko
Maximum Dimensions
265mm(L)*250cm(W)*90cm(H)
Weight
1.9 kg / 4.2 Lbs
2.0 kg / 4.4 Lbs
Battery
Lead Acid Battery
12VDC
24VDC
Charging Voltage
13.7VDC
27.4VDC
Charging Current
10A
Warning Diagnostics
Indicators
AC Mode, Battery mode, Fault
Audible Alarms
Low Battery, Overload, Fault
Environmental
Operating Temperature
+32
°
F to 104
°
F ( 0
°
C to 40
°
C )
Operating Relative
Humidity
0 to 90% NON-CONDENSING
Management
Auto-Charger
Yes
Auto-Restart
Yes
Visit
www.cpsww.com
for more product information and the nearest CyberPower local contact for your
region.