INSTALLATION
The product is designed for tower installation and rack installation for 2-post rack and 4-post
rack. Read and follow the procedures thoroughly before and during your installation of the
product. The installation videos are available on our website, visit www.cyberpower.com or scan
the QR code below for detailed information.
Preparation
CAUTION!
It is strongly recommended to have an additional person assist this installation
process if the product is heavy.
CAUTION!
It is strongly recommended that the 2 post rack be bolted to the floor prior to the
installation of the product.
1. Remove all equipment connected to the product.
2. Make sure the product is disconnected from AC power source.
3. Remove internal batteries to reduce weight of the unit before the installation.
Refer to BATTERY REPLACEMENT section for instructions.
Reminder: If you would like to have the UPS installed at the same time, turn off the UPS first and
repeat above steps to your UPS.
Rack Installation for 2-post Rack
1. Attach the brackets with provided M5 flat head screws.
2. Affix the product to the rack with suitable M5/M6 screws and cage nuts.
(M5 pan head screws are provided with the product in the mechanical accessory box.)
Rack Installation for 4-post Rack
1. Use the provided M5 flat head screws to attach the brackets and provided M5 pan head
screws for hanging brackets.
2. Screw the hanging rails to the rack with provided M5 pan head screws and plastic washers.
3. Lift the product upon the hanging rails and slide the unit into the rack. Affix the product to
the rack with provided M5 pan head screws. If handles are needed, affix them to the brackets
with M4 flat head screws.