22
Main menu
Submenu
Description
OverTemp Restart
YES
(default)
Enable auto restart when temperature occurs.
NO
Disable auto restart when temperature occurs.
Buzzer ON/OFF
ON
(default)
Alarm on.
OFF
Alarm off.
Battery Type
Lead_Acid
Lead_Acid.
Custom
Lead_Acid
Self-defined Lead_Acid.
Max charge Curr
xxxA
(default 40A)
If battery type is selected as lead acid battery,
this program can be set up. Setting range is
from 10A to 130A.
Bulk charge Volt
xx.xV
(default 56.4V)
If battery type is selected as “self-defined
Lead_Acid”, this program can be set up. Setting
range is from 50.0V to 57.4V.
Float charge Volt
xx.xV
(default 54V)
If battery type is selected as “self-defined
Lead_Acid”, this program can be set up. Setting
range is from 50~56V.
Battery Low Volt
xx.xV
(default 46.4V)
Setting voltage point back to battery mode
when selecting
“
BAT first” or “PV first”. Setting
range is from 44.4~51.4V.
System Time
xxxx/xx/xx
xx:xx:xx
Setup the system time
COM Addr
xxx
Setup communication address