Pmax 

260W 

Max. PV module numbers in series                                                     

→ 

36VDC÷30.9 

Vmp 

30.9V 

Imp 

8.42A 

Max. PV module numbers in parallel                                           

→ 

40A÷8.42                                                                                                                   

Total PV module numbers is 1×5=5 

Voc 

37.7V 

Isc 

8.89A 

 

Example for CPS3000EOH24SC

 

After considering Voc of PV module not exceeds 55VDC and Max. Vmp within 30~36VDC, we can 

choose PV module with below specification. 

 

Pmax 

260W 

Max. PV module numbers in series                                                     

→ 

36VDC÷30.9 

Vmp 

30.9V 

Imp 

8.42A 

Max. PV module numbers in parallel                                           

→ 

50A÷8.42                                                                                                                   

Total PV module numbers is 1×6=6 

Voc 

37.7V 

Isc 

8.89A 

 

 

CAUTION! 

Ensure that Open Circuit Voltage (Voc) of PV modules not exceeds 40V for 

CPS1200EOH12SC and 55V for CPS2200/3000EOH24SC, or else the inverter may be damaged. 

If PV voltage or current is out of normal range, the unit will stop solar charging and send a warning 

code. 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for CPS1200EOH12SC

Page 1: ...Solar Hybrid Inverter CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC User s Manual ...

Page 2: ...our Equipment 6 2 4 Hardware Installation Guide 6 3 DEFINITIONS FOR ILLUMINATED LCD INDICATORS 9 4 OPERATION CONFIGURATION 10 Power On Off 10 View LCD Information 10 Audible Alarm On Off 11 PV Utility Priority 11 Charger Control 11 Input Voltage Range Selector 11 5 TROUBLESHOOTING 12 6 TECHNICAL SPECIFICATIONS 14 APPENDIX PV MODULE SELECTION 15 ...

Page 3: ...vent accumulation and concentration of hydrogen gas at the top of the compartment CAUTION A battery can present a risk of electrical shock and high short circuit current When working on batteries remove watches rings or other metal objects Use tools with insulated handles CAUTION Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected CAUTION To avo...

Page 4: ...e solar energy from panels into usable AC and store excess power in batteries as backup power during blackout and emergencies The Solar Hybrid Inverter comes with a small and compact design which helps to simplify the installation process With Green thinking in mind CyberPower is always in the lead in providing the most pioneering energy saving solution CPS1200EOH12SC CPS2200EOH24SC User Manual CP...

Page 5: ...5 CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC Application Diagram ...

Page 6: ...stem performance keep the load below 80 of the unit s rated capacity 2 4 Hardware Installation Guide Step 1 Connect the Battery For optimal battery life and reasonable recharging time make sure the batteries capacity no less than 100Ah Use batteries with same brand type and capacity Connect DC input cables of this product to external batteries Red cable to the battery s Positive polarity Black cab...

Page 7: ...to switch off the power from PV for the need of maintenance and service please install a circuit breaker between the product and PV module CAUTION To reduce risk of injury use appropriate cables for PV connection The wiring can only be performed by trained personnel Refer to below table for recommended cable size Model PV Charging Current Wire Gauge CPS1200EOH12SC 40A 12AWG CPS2200EOH24SC 40A 12AW...

Page 8: ...capacity is achieved To recharge the battery and maintain optimal battery charge simply leave the unit plugged into a wall outlet at all times The battery can be charged whether the unit is turned on or off DO NOT connect Neutral of the Power Distribution Box to a the OUTPUT Neutral of this product or b the INPUT Neutral of connected equipment Otherwise reversed polarity will damage the product an...

Page 9: ...displays normal line mode and battery backup mode 3 LINE MODE The unit is supplying utility power to connected equipment 4 BATTERY MODE The unit is operating from its external batteries 5 MUTE This icon appears whenever the unit is in silent mode The buzzer does not beep during silent mode until the battery reaches low capacity 6 OVERLOAD This icon appears and an alarm sounds to indicate the outle...

Page 10: ...r source Solar first default solar energy will provide power to load as first priority Utility first utility will provide power to load as first priority Standby Charging Mode When the power button is not pressed Mode 1 When Utility exist LCD only displays icon The unit bypasses utility power to output and charge the battery Mode 2 When PV exist LCD only displays icon Solar power charges the batte...

Page 11: ...voltage is 13 7V for CPS1200EOH12SC and 27 4V for CPS2200EOH24SC CPS3000EOH24SC Customized for poor battery condition The charging voltage is 13 3V for CPS1200EOH12SC and 26 6V for CPS2200EOH24SC CPS3000EOH24SC If the battery is aging lower the charging voltage to enhance the charging capability Input Voltage Range Selector Input voltage range is defined in specification section Output voltage is ...

Page 12: ...rvicing of the DC fuse should only be performed by trained personnel For more information on DC fuse replacement contact CyberPower Systems Batteries are discharged Recharge the unit for at least 8 hours The product may require service Contact CyberPower Systems There is no LCD display The product is not turned on Press the power button Batteries are discharged Recharge the unit for at least 8 hou...

Page 13: ...y 1 2 second A05 PV Voltage High Beep every second A06 Battery Low Beep every 2 seconds A07 PV Current High Beep every second E50 Output Voltage High Constant tone E51 Output Short Constant tone E52 Overload Fault Constant tone E53 Fan Fail Constant tone E54 Over Charge Constant tone ...

Page 14: ...l Block Transfer Time 8ms Typical Narrow Mode Battery Battery Voltage 12V 24V 24V Charging Current 20A 10A 20A PV Input Solar Charger Maximum Input Power Watt 500W 1000W 1300W Nominal PV Input Voltage 12Vdc 24Vdc 24Vdc Optimal Operating Voltage Range 15 18VDC 30 36VDC 30 36VDC Maximum PV Input Voltage 40V 55V 55V Charging Current 40A 40A 50A Environmental Operating Temperature C 0 C to 40 C Operat...

Page 15: ... requirements a Total Voc Inverter s max PV input voltage b Vmp falls within Inverter s optimal operating voltage range If one PV module cannot meet this requirement connect multiple PV modules in series to increase the total voltage Example for CPS1200EOH12SC After considering Voc of PV module not exceeds 40VDC and Max Vmp within 15 18VDC we can choose PV module with below specification Pmax 85W ...

Page 16: ... can choose PV module with below specification Pmax 260W Max PV module numbers in series 1 36VDC 30 9 Vmp 30 9V Imp 8 42A Max PV module numbers in parallel 6 50A 8 42 Total PV module numbers is 1 6 6 Voc 37 7V Isc 8 89A CAUTION Ensure that Open Circuit Voltage Voc of PV modules not exceeds 40V for CPS1200EOH12SC and 55V for CPS2200 3000EOH24SC or else the inverter may be damaged If PV voltage or c...