4 OPERATION & CONFIGURATION 

 
Power On/Off 

Power On

 

Press the 

POWER

 button to turn on the unit. 

Power Off

 

Press the 

POWER

 button again to turn off the unit. 

 

Function Setup

 

Press the 

SETUP

 button for 4 seconds 

to access the setup mode’s 7 functions: 

Audible Alarm, Auto 

Restart Voltage, Low Battery Shutdown Voltage, LCD Auto Sleep, Cycling Display, Back to Default, 

and Return to Status Display

. Short press the 

SELECT

 button to view the functions. When a function is 

selected, short press the 

SETUP

 button to access the function

’s options. Short press 

SELECT

 button 

to view the options. When the desired option is selected, short press 

SETUP

 button to confirm the 

setting. The unit will leave Setup Mode if there is no operation in 60 seconds. 

 

Audible Alarm

 

Press 

SELECT

 button for 2 seconds to enable the audible alarm (beeps once) or disable (beeps twice) 

the audible alarm. The MUTE icon will appear on the LCD display when the audible alarm is disabled. 

 

Function Setup Guide 

 

Function 

Options 

Default 

Description 

Page 1 - Audible Alarm 

 

 

 

 

 

On 

 

Off 

 

ESC 

On 

If Off is selected, the unit will 

mute alarms and the Mute 

icon will appear on the LCD 

display. 

Page 2 

– Auto Restart Voltage 

 

 

 

 

 

 

 

 

 

CPS1000/1200E

ILCD: 

Any/10.5/11.0/ 

/11.5/12.0/12.5/

13.0/FUL 

 

CPS2200EILCD: 

Any/21.0/22.0 

/23.0/24.0/25.0 

/26.0/FUL 

Any 

When the utility power 

comes back and starts to 

charge the battery, the 

Power Inverter will auto 

restart at the setting battery 

voltage. 

 

 

Summary of Contents for CPS1000EILCD

Page 1: ...Power Inverter CPS1000EILCD CPS1200EILCD CPS2200EILCD User s Manual ...

Page 2: ...2 ...

Page 3: ...ower Requirements of Your Equipment 7 2 4 Hardware Installation Guide 7 3 DEFINITIONS FOR ILLUMINATED LCD INDICATORS 9 4 OPERATION CONFIGURATION 11 Power On Off 11 Function Setup 11 Audible Alarm 11 Function Setup Guide 11 Charger Control 13 Input Voltage Range Selector 13 5 TROUBLESHOOTING 14 6 TECHNICAL SPECIFICATIONS 16 ...

Page 4: ...vent accumulation and concentration of hydrogen gas at the top of the compartment CAUTION A battery can present a risk of electrical shock and high short circuit current When working on batteries remove watches rings or other metal objects Use tools with insulated handles CAUTION Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected CAUTION To avo...

Page 5: ... home office users the always on power supply with the exceptional power performance Featuring the high efficiency conversion design the Power Inverter supplies long lasting and reliable power to various appliances and provide longer backup for equipment These units can be installed in either a horizontal or wall mounted placement to make the most of your space Power Inverter Input Power Cord User...

Page 6: ...6 CPS1000EILCD CPS1200EILCD CPS2200EILCD Application Diagram ...

Page 7: ...m performance keep the load below 80 of the unit s rated capacity 2 4 Hardware Installation Guide Step 1 Connect the Battery For optimal battery life and reasonable recharging time make sure the batteries capacity no less than 100Ah Use batteries with same brand type and capacity Connect DC input cables of this product to external batteries Red cable to the battery s Positive polarity Black cable ...

Page 8: ...s achieved To recharge the battery and maintain optimal battery charge simply leave the unit plugged into a wall outlet at all times The battery can be charged whether the unit is turned on or off DO NOT connect Neutral of the Power Distribution Box to a the OUTPUT Neutral of this product or b the INPUT Neutral of connected equipment Otherwise reversed polarity will damage the product and connecte...

Page 9: ...mation Icon Description Normal Mode Power On The Power Inverter is turned on Standby Mode Power Off The Power Inverter is off while the LCD display remains on Utility Power Utility power source supplies AC power Load Capacity The approximate load capacity of the unit s outlet in 25 increments Battery Capacity The approximate battery capacity and charging status in 25 increments Fault This icon app...

Page 10: ...pes of modes regarding to the operation of the Power Inverter The corresbonding LCD displays are as shown below LCD Display Operation Mode Standby Mode In Standby Mode the Power Inverter is off and the Utility power bypasses to output and in the meantime charges the battery The LCD is on to show battery status Line Mode The Power Inverter is turned on and AC input power is normal It supplies power...

Page 11: ...is selected short press SETUP button to confirm the setting The unit will leave Setup Mode if there is no operation in 60 seconds Audible Alarm Press SELECT button for 2 seconds to enable the audible alarm beeps once or disable beeps twice the audible alarm The MUTE icon will appear on the LCD display when the audible alarm is disabled Function Setup Guide Function Options Default Description Page...

Page 12: ... Page 4 LCD Auto Sleep Off 0 5 1 2 Min ESC 1 Min If Auto Sleep is selected the LCD display will shut off after 0 5 1 2 minutes if no activity Page 5 Cycling Display Off 0 5 1 Min ESC 0 5 Min If the buttons are not touched in 0 5 1 minute the LCD will start cycling the Inverter information Page 6 Back to Default ESC Yes ESC Select Yes to restore the factory default settings Page 7 Return to Status ...

Page 13: ...Voltage Range Selector Input voltage range is defined in specification section Output voltage is the same as input voltage in AC mode Narrow 190 260Vac For connected equipment that are sensitive to the fluctuation of voltage range narrow the input voltage range and the output voltage will follow Wide 100 280Vac For connected equipment that are less sensitive to the fluctuation of voltage range set...

Page 14: ...rvicing of the DC fuse should only be performed by trained personnel For more information on DC fuse replacement contact CyberPower Systems Batteries are discharged Recharge the unit for at least 8 hours The product may require service Contact CyberPower Systems There is no LCD display The product is not turned on Press the power button Batteries are discharged Recharge the unit for at least 8 hou...

Page 15: ...e Alarm A64 Overload Rapid beeping every 1 2 second E07 Output Voltage High Constant tone E09 Output Short Constant tone E14 Overload Fault Constant tone E18 Fan Fail Constant tone E13 Over Charge Constant tone E25 Output Unbalance Constant tone ...

Page 16: ...ac Output Frequency 50 60Hz Outlet Type 1 UN 1 UN 1 UN Transfer Time 8ms Typical Narrow Mode Battery Battery Voltage 12V 24V 24V Charging Current 20A 20A 15A Environmental Operating Temperature C 0 C to 40 C Operating Relative Humidity 0 to 90 non condensing Physical Dimensions WxHxD mm 250 x 90 x 265 250 x 90 x 265 250 x 90 x 265 Weight kg 2 05 2 2 2 2 For more information visit www cyberpower co...

Page 17: ......

Reviews: