10

 

 

2. Remove the o-ring from OUT1 and OUT2 port and 

insert appropriate orifice. After inserting orifice, replace 

the o-ring. Make sure there are not any substances 
entering into the port. (Figure 21) 

 

3. If hunting persists after inserting the orifice, please 

contact CVS Controls Ltd. or its appropriate agent. 

 

 

TROUBLESHOOTING 

 

Positioner does not respond to the input 

signal. 

 
1. Check supply pressure level. The lever must be at 

least 1.4 kgf/cm

2. 

For spring return type actuator, the 

supply pressure level has to be larger than the spring’s 

specification. 

2. Check if the input signal is properly supplied to the 
positioner. The signal should be 4~20mA DC. 

3. Check if zero pint or span point is properly set. 

4. Check if the positioners nozzle has been blocked. 

Also, check if the pressure is supplied to  

the positioner and the pressure is being exhausted 
through the nozzle. If the nozzle has been blocked by 

any substances, please send the product for repair. 

5. Check if the feedback lever has been installed  

properly. 

 

The

 

pressure of OUT1 reaches exhausting 

pressure level and does not decrease. 

 

1. Check A/M Switch. If the switch has been damaged, 

replace the switch or pilot relay valve. 

2. Check for a gap or damages between the nozzle 

and the flapper. If damaged, pleae contact 

CVS Controls Ltd. 

 

The pressure is exhausted only by the A/M 

switch. 

 

1. Check if the positioners nozzle has been 

blocked. Also, check if the pressure is supplied 

to the positioner and the pressure is being           
exhausted through the nozzle. If the nozzle has been 

blocked by any substances, please contact            

CVS Controls Ltd. 

 

Linearity is too low 

 

1. Check if the positioner is properly positioned. 

Especially if the feedback lever is parallel to the 

ground at 50% point. 

2. Check if zero and span point have been properly 

adjusted. If either one of the values is being adjusted, 
another one must be adjusted as well. 

3. Check if the supply air pressure level is stable from 

the regulator. If the level is unstable, the regulator 

must be replaced. 

 

Hysteresis is too low 

 

1. In case of a double acting actuator, check if seat 

adjustment has been properly performed. Please 

contact CVS for any further inquiries regarding the 
seat adjustment. 

2. Backlash can ccur when the feedback lever and 

lever spring loosen. To avoid backlashing, please 

adjust the lever spring. 

3. Check if the connection bar to the feedback lever is 
tightly fastened. 

 
 
 

 

CVS Controls Ltd. 
Product Manual: CVS Rack & Pinion Actuator 

CVS Controls Ltd. 
Process Management 
And Instrumentation 

Orifice Diameter 

Orifice 

O - Ring (P5) 

OUT2 

OUT1 

Actuator Size  Orifice Size  Suffix Symbol 

90 cm

less 

O 1 

90 - 180 cm

3

 

O 2 

180 cm

more 

none 

Summary of Contents for CVS1000L

Page 1: ...he product or parts If alterations or modifications are required please contact CVS Controls Ltd The manufacturer warrants the product from the orig inal date of purchase for one 1 year except as othe...

Page 2: ...ischarge through port OUT1 to the actuator 10 As the actuators inner pressure increases the actuator stem 12 will move pushing on the feedback lever 13 This movement is transferred to the cam 14 and p...

Page 3: ...y 1 2 NPT Explosion Proof CSA Class 1 Zone 1 Group IIB T5 Protection IP66 40 60 C Linearity 1 0 F S Hysteresis 1 0 F S Sensitivity 0 2 F S 0 5 F S Repeatability 0 5 F S Air Consumption 3LPM Sup 1 4kgf...

Page 4: ...nd Instrumentation ZERO UNIT TORQUE MOTOR BASE BODY JUNCTION BOX COVER PILOT VALVE FEEDBACK SHAFT SPAN UNIT VENT UNIT FEEDBACK LEVER 224 3 132 3 6 Conduit Entry PT NPT 1 2 PF G 1 2 Out 2 NONE 45 122 1...

Page 5: ...se consider the following when making a bracket i Feedback level should be leveled at 50 of the valve stroke Refer to step 7 ii Feedback lever connection bar of actuator clamp should be installed at t...

Page 6: ...troke To adjust move the bracket or connection bar Figure 7 Stroke 70mm NOTE After installing the YT 1000L operate the valve from 0 to 100 stroke by using the air filter regulator on the actuator Both...

Page 7: ...hat has more than a 6mm inner diameter 4 Do not use an extremely long pipeline system It may affect flow rate due to the friction inside the pipeline Piping Connection with Actuator YT 1000 series sin...

Page 8: ...or 20mA and rotate adjuster clockwise or counter clockwise to adjust the actuator s initial point When setting the initial point the specification of valve and system must be taken into account Please...

Page 9: ...tting change 4 If OUT2 in single acting actuator or double acting actuator is used the A M switch will not operate Adjustment Seat Adjuster 1 Seat adjustment is set according to the customers request...

Page 10: ...nozzle and the flapper If damaged pleae contact CVS Controls Ltd The pressure is exhausted only by the A M switch 1 Check if the positioners nozzle has been blocked Also check if the pressure is supp...

Page 11: ...11 Ordering Information CVS Controls Ltd Product Manual CVS Rack Pinion Actuator CVS Controls Ltd Process Management And Instrumentation...

Page 12: ...eet Edmonton Alberta Canada T6E 0A5 Office 780 437 3055 Fax 780 436 5461 Calgary Sales Office 3516 114 Avenue SE Calgary Alberta Canada T2Z 3V6 Office 403 250 1416 Fax 403 291 9487 Website www cvs con...

Reviews: