Pub 49004
Effective 9/00
Page 4
Fig. 5 Terminal Board
APPLY ONLY 24VDC TO CONTROL TERMINAL
BOARD UNLESS SPECIFIED OTHERWISE IN THIS
MANUAL. ALL CONTROL WIRING IS 22 - 12 AWG.
FAILURE TO FOLLOW THIS CAUTION COULD RE-
SULT IN SEVERE DAMAGE TO THE CONTROLLER.
Power Wiring
Control Wiring Inputs
The controller on the IT Soft Starter has the inputs shown
in Table 4 on Page 5 of this leaflet.
Fig. 4 Elementary Diagram for Soft Starter with
HAND/OFF/AUTO/RESET with PLC Shown
with 120VAC Alarm and Run Indication
261349
CAUTION
APPLIQUER UNE TENSION DE 24V C.C. AUX BORNES
SAUF AVIS CONTRAIRE DANS CE MANUEL. TOUTE
LA FILERIE DE COMMANDE EST DE CALIBRE 22 A
12 AWG. L’INOBSERVATION DE CETTE MESURE
POURRAIT CAUSER DES DOMMAGES IMPORTANTS
AU CONTROLEUR.
ATTENTION
THERE CAN BE LINE VOLTAGE POTENTIAL AT THE
MOTOR LOAD TERMINALS EVEN WITH THE START-
ER IN THE OFF STATE. THIS IS DUE TO THE POSSI-
BLE LEAKAGE ACROSS SCRS. ALWAYS DISCON-
NECT INPUT POWER BEFORE SERVICING STARTER
MOTOR.
CAUTION
IL PEUT EXISTER UNE TENSION DE LIGNE AUX
BORNES DU COTE CHARGE DU MOTEUR BIEN QUE
LE MOTEUR SOIT ARRETE. CELAS’EXPLIQUE DU
FAIT DE FUITES POSSIBLES A TRAVERS LES RE-
DRESSEURS AU SILICIUM. TOUJOURS DEBRANCH-
ER L’ALIMENTATION AVANT D’EFFECTUER DES
TRAVAUX SUR LE DEMARREUR.