background image

Ground Fault Trip Unit pick-up setting through one
phase of the circuit breaker as shown in Figure 5-1.
This should cause the breaker to trip and the ground
fault alarm light should light in less than 1 second. Reset
the breaker. Repeat the test on the other two phases.

If the system is a 4-wire system with a neutral current
sensor, apply the same current as described above
through one phase of the breaker returning through the
neutral sensor as shown in Figure 5-2. The breaker
should not trip and the ground fault alarm light should
not light.  Repeat the test on the other two phases.

If the system is a 3-wire system with no neutral current
sensor, apply the same current as described above
through any two phases of the breaker with the connec-
tions exactly as shown in Figure 5-3.  The breaker
should not trip and the ground fault alarm light should
not light. Repeat the test using the other two combina-
tions of breaker phases.

FIELD TESTING SHOULD BE USED FOR FUNCTION-
AL TESTING AND NOT FIELD CALIBRATION OF
THE DIGITRIP OPTIM 550 GROUND FAULT TRIP
UNIT.

ANY TEMPORARY CONNECTION MADE FOR THE
PURPOSE OF CONDUCTING TESTS SHOULD BE
RESTORED TO PROPER OPERATING CONDITIONS
BEFORE RETURNING THE BREAKER TO SERVICE.

The results of the test are to be recorded on the test
form provided with the equipment.

6.0 RATING PLUG

The rating plug, as illustrated in Figure 3-5, is used to
establish the continuous ampere rating of the related cir-
cuit breaker.

The Long Delay protection function of the trip unit is set
at the rating plug value (I

n

). The Short Delay and

Instantaneous protection functions are set as a multiple
of I

n

. The Ground Fault protection function is indepen-

dent of I

n

.

Different rating plugs are available to match the desired
current rating and type of circuit breaker into which the
trip unit is to be installed (Table 3.1).

I.L. 29C508B

Page 7

Effective 9/00

!

CAUTION

Figure 5-1  Connections for Ground Fault Trip Test

Source

Low 
Voltage
Source

L        C         R

N

Load

Current Limiting
Resistor
(if required)

Source

Low 
Voltage
Source

L       C          R

N

Load

Current Limiting
Resistor
(if required)

Figure 5-2  Connections for Ground Fault No-Trip Test,
with a Four-Wire System

Summary of Contents for Digitrip OPTIM 550

Page 1: ...TY PROCEDURES CUTLER HAMMER IS NOT LIABLE FOR THE MISAP PLICATION OR MISINSTALLATION OF ITS PROD UCTS The user is cautioned to observe all recommendations warnings and cautions relating to the safety...

Page 2: ...DC applications a thermal magnetic trip unit should be used The Digitrip OPTIM 550 Trip Unit for the L Frame is available in 3 different types and four different maximum ampere ratings Table 1 1 Groun...

Page 3: ...ring channels Ground fault trip units are supplied from the factory with a wire harness with pigtail lead connections for a neutral current sensor white and gray wires A neutral current sensor is prov...

Page 4: ...etaining slots of the trip unit I L 29C508B Page 4 Effective 9 00 Figure 3 3 Neutral Current Sensor Placement 1 50 Table 3 1 Digitrip L Frame OPTIM Rating Plugs Max Amps In Catalog Number of trip unit...

Page 5: ...ed to avoid exceeding a safe terminal temperature operating range Consult Cutler Hammer for recommendations 4 1 GENERAL The Digitrip OPTIM 550 Trip Unit provides a tripping sig nal to the flux transfe...

Page 6: ...RFORMANCE TESTING FOR GROUND FAULT TRIP UNITS 5 2 1 CODE REQUIREMENTS The National Electrical Code under Article 230 95 C requires that any ground fault protection system be per formance tested when f...

Page 7: ...TING AND NOT FIELD CALIBRATION OF THE DIGITRIP OPTIM 550 GROUND FAULT TRIP UNIT ANY TEMPORARY CONNECTION MADE FOR THE PURPOSE OF CONDUCTING TESTS SHOULD BE RESTORED TO PROPER OPERATING CONDITIONS BEFO...

Page 8: ...es which mount on the trip unit are available for use The number of the instruction leaflet covering the installation of each accessory is shown Alarm Signal Lockout ASL Switch I L 29C183 Auxiliary Sw...

Page 9: ...round Fault Test Record should be Retained by Those in Charge of the Building s Electrical Installation in order to be Available to the Authority having Jurisdiction Test Date Circuit Breaker Number R...

Page 10: ...I L 29C508B Page 10 Effective 9 00...

Page 11: ...I L 29C508B Page 11 Effective 9 00...

Page 12: ...Cutler Hammer Pittsburgh Pennsylvania U S A Effective 9 00 ISI Style 6603C85H03 Printed in U S A Page 12 I L 29C508B...

Reviews: