SPRINGBACK CHARTS
Chart A – RIGID Conduit/Schedule 40 Pipe
Conduit
Size
Deduct
Length
————————— Springback —————————
15
˚
30
˚
45
˚
60
˚
90
˚
1/2"
7
1
⁄
2
"
18
34
49
65
95
3/4"
9
1
⁄
4
"
17
33
48
62
92
1"
11"
18
33
50
65
95
1
1
⁄
4
"
13
5
⁄
8
"
15
30
45
63
93
1
1
⁄
2
"
15
3
⁄
8
"
20
36
51
65
95
2"
16
7
⁄
8
"
18
33
49
66
94
Chart B – EMT Conduit
Conduit
Size
Deduct
Length
————————— Springback —————————
15
˚
30
˚
45
˚
60
˚
90
˚
1/2"
7
1
⁄
2
"
19
34
49
65
96
3/4"
9
1
⁄
4
"
19
34
50
65
97
1"
11"
19
34
50
65
97
1
1
⁄
4
"
13
5
⁄
8
"
19
33
50
65
95
1
1
⁄
2
"
14
7
⁄
8
"
17
32
49
63
93
2"
16
1
⁄
8
"
17
33
48
64
95
Chart C – IMC Conduit
Conduit
Size
Deduct
Length
————————— Springback —————————
15
˚
30
˚
45
˚
60
˚
90
˚
1/2"
7
1
⁄
2
"
22
38
54
69
100
3/4"
9
20
36
48
66
98
1"
11"
20
35
52
67
99
1
1
⁄
4
"
13
5
⁄
8
"
18
33
49
65
95
1
1
⁄
2
"
14
7
⁄
8
"
20
35
51
66
98
2"
16
1
⁄
4
"
19
35
51
66
97
NOTE: Springback figures are approximate.
Minimum Stub Length = Deduct Length plus 2"
Chart C1 – PVC Coated Rigid Conduit
Conduit
Size
Deduct
Length
————————— Springback —————————
15
˚
30
˚
45
˚
60
˚
90
˚
1/2"
7
1
⁄
2
"
16
31
47
62
93
3/4"
9
15
31
46
62
93
1"
11"
16
32
47
63
94
1
1
⁄
4
"
13
5
⁄
8
"
15
30
46
61
92
1
1
⁄
2
"
14
7
⁄
8
"
18
33
49
64
95
2"
16
1
⁄
8
"
19
34
50
65
96