Neutral to Ground Filter
Jumper
Indoor Installations
Removal is accomplished by pulling the green jumper from the connector on
the ISM . Once removed, the jumper should be placed in the clear vinyl pocket
containing the unit test data for future use if desired (Figure 10) .
Connector on ISM
TM
Neutral to Ground Jumper
Removed from ISM
TM
Current Technology
®
recommends feeding all PX3 models with a disconnect,
circuit breaker, molded case switch or fused disconnect .
If a breaker or molded case switch is used for connecting the phase
conductors, Current Technology
®
recommends using circuit breakers
in the range of 60 to 100 amps.
W A R N I N G ! Prior to proceeding, ensure the SPD unit does not
have voltage applied to its input terminals.
PX3 models equipped with a filter system (“-F” suffix), and have a neutral
connection, come with a green jumper wire that loops out of the 3-pin
connector on the ISM and connects a filter neutral to ground . In certain
medical applications, or circuits which employ GFCI protection, this Neutral to
Ground filter connection should be removed .
Figure 10
NEMA 1 enclosures are suitable for indoor use only .