**ONBOARD STAGES** ((1)Target = 73.0°)
(2)# (3)SENSORS (4)MODE (5)ON (6)OFF (7)TIMER
1
-------1 Feed 76 74 None
2
Light Ramp
3
-----321 Cstir 76 74 Min 2
4
-------1 Cneg 76 74 Min 1
5
------2- CNeg 77 75 None
6
-----3-- CNeg 78 76 None
7
------2- CNeg 79 77 None
8
-------1 CNeg 80 78 None
NOTE: Highlight and press ENTER to
bring up details on each stage.
7.8
Onboard ON/OFF Stages
Onboard On/Off Stages are the 8
stages included on the EV1200
controller.
NOTE: The stage
settings for Onboard Stages 1 thru
8 will be the same also for the
Expansion Stages 1 thru 8.
For
expansion stages, refer to
Section 6.9
NOTE: When programming stages
you are allowed to edit the settings
from the main screen. You are also
allowed to go into each stage and see
a detailed screen. To do this, have a
stage number highlighted and then
press enter.
(1)Target
– Displays the current set
Target Temperature.
(2) Stage # -
Stage Numbers.
(3) Sensors –
The sensors which may be used to control the ON or OFF point of a stage. Sensors 1 thru 8
may be selected or unselected for each stage. The specific stage will operate from the selected
sensor/sensors. Active sensors will be indicated by a number starting with #1 from right to left.
Inactive sensors will be indicated by a - or hyphen. When "outside-" is displayed, outside sensor is
active. To use sensors 1,2 and 3, "-----321" should be displayed.
(4) Mode –
This mode column will indicate how the stage is Programmed to operate.
(OFF) Disables stage from operating during automatic operation.
(Heat) Heat Mode: This method of heating only operates when the curtains are in the closed
position and the operating sensor is below the on temperature.
(CSTIR) Cool Stir Mode: This mode setting allows the cool stage to run whether the main curtain
is open or closed.
(CNEG) Cool Negative: Method of ventilation where air is drawn out of the building by fans,
creating a negative static pressure which draws air into the house from all openings at a
even pace. Will not operate in Tunnel or Nat.
(CNEGT) Cool Negative Tunnel: A combination of the Cool Negative and the Cool Tunnel
Modes.
(CTUN) Cool Tunnel: Only operate during Tunnel operation with one exception being set as a
minimum ventilation timer which will allow the stage to operate on a timer only, in
minimum or power ventilation.
(LIGHT) The LIGHT Mode: See Section 7.12.
(FEED) The FEED mode: See Section 7.11.
(CEVAP) Cool Evaporative mode See Section 7.10.6
(CHEAT) Cooler Heat mode: Heat stage for the Cooler.
(CCOOL) Cooler Cool mode: Cool stage for the Cooler.
(5&6) ON/OFF –
The ON column will indicate the current setting for the onpoint temperature of the stage.
Set this to the temperature you would like for the stage to come on at. The OFF column will
indicate the current setting for the offpoint temperature of the stage. Set this to the temperature you
would like for the stage to turn off at.
(7) TIMER –
None, Min1, Min2, Var, Cool, OPT1-OPT8: This Timer column will indicate what type of
timer you want the stage to operate from. If the stage doesn't need a timer then you must have this
setting to none.