A
List of Terminals
EDGE Main Controller
Terminal name
Description
Alarm - COM
Alarm relay input, the COM (Common) is the voltage source needed to switch
Alarm - NO (Normally
Opened)
Alarm relay output, When a relay contact is normally open (NO), there is an opened con-
tact when the relay is not energized
Alarm - NC (Normally
Closed)
Alarm relay output, When a relay contact is Normally Closed (NC), there is a closed con-
tact when the relay is not energized
Functional earth
Functional Ground Terminal Primarily used for functional earth terminals which are gen-
erally associated with test and measurement circuits. These terminals are not for safety
earthing purposes but provide an earth reference point
Automation - 24V
Communication bus 1 - power supply 24VDC
Automation - A
Communication bus 1 - Signal A of RS485 communication
Automation - B
Communication bus 1 - Signal B of RS485 communication
Automation - GND
Communication bus 1 - power supply return
Safety - 24V
Communication bus 2 - power supply 24VDC
Safety - A
Communication bus 2 - Signal A of RS485 communication
Safety - B
Communication bus 2 - Signal B of RS485 communication
Safety - GND
Communication bus 2 - power supply return
3-Slot and 6-Slot Expansion Box
Terminal name
Description
IN (x)
Analog inputs can set in 0-5V mode, in dry contact mode, in 4-20mA mode, in tempera-
ture mode. Inputs are used for sensors : temperature probes, humidity probes, static
pressure probes, water meters, dry contacts.
GND(x) close to IN(x)
Analog inputs returns. Inputs are used for sensors : temperature probes, humidity
probes, static pressure probes, water meters, dry contacts.
24V+
24VDC Supply Outputs are used to supply sensors, maximum current per output : 50mA
GND close to 24V+
Returns of 24VDC supply outputs used to supply sensors
RELAY(x) – COM
Relay inputs, the COM (Common) is the voltage source needed to switch.
RELAY (x) – NO
Relay outputs, when a relay contact is normally open (NO), there is an open contact
when the relay is not energized.
RELAY(x) – NC
Relay output, when a relay contact is Normally Closed (NC), there is a closed contact
when the relay is not energized.
AUTOMATION - 24V
Communication bus 1 - power supply 24VDC
AUTOMATION - A
Communication bus 1 - Signal A of RS485 communication
AUTOMATION - B
Communication bus 1 - Signal B of RS485 communication
891–00516
EDGE Wiring Diagram
73
Summary of Contents for EDGE 074-11793
Page 4: ...NOTES 4 891 00516 EDGE Wiring Diagram...
Page 16: ...Chapter 1 Introduction 16 891 00516 EDGE Wiring Diagram...
Page 22: ...NOTES 22 891 00516 EDGE Wiring Diagram...
Page 25: ...NOTES 891 00516 EDGE Wiring Diagram 25...
Page 37: ...NOTES 891 00516 EDGE Wiring Diagram 37...
Page 45: ...Chapter 2 Wiring Diagrams Figure 2 25 Inlet Wiring 891 00516 EDGE Wiring Diagram 45...
Page 46: ...Chapter 2 Wiring Diagrams Figure 2 26 Inlet Failsafe Wiring 46 891 00516 EDGE Wiring Diagram...
Page 72: ...NOTES 72 891 00516 EDGE Wiring Diagram...
Page 76: ...NOTES 76 891 00516 EDGE Wiring Diagram...
Page 79: ...C Extending a cable Best practice using a junction box 891 00516 EDGE Wiring Diagram 79...
Page 80: ...Appendix C Extending a cable Using of heat shrink tubing 80 891 00516 EDGE Wiring Diagram...