9. Start-Up
Figure 9A
7. Disconnect the manometer and replace the 1/8" plug.
8. Open the door to the burner side of the heater. Remove the 1/8" plug from the manifold side of the
valve. Connect manometer as in
step 2, then repeat step 3 and 4 when the solenoid engages to
ignite the gas valve the reading on the gauge should read
a maximum of 11" W.C. for LPG, and
3.5" W.C. for NG. This reading is the manifold pressure for the unit and is the most important
reading for actual heater output.
To adjust manifold pressure, remove the gas valve cover and
slotted brass screw that covers the regulator.
Turn the nylon regulator screw
clockwise to increase pressure and counterclockwise to decrease pressure. When pressure is set,
replace all covers and repeat steps 6 and 7.
9. Turn the supply gas ON.
NOTE:
Each gas valve is set at the factory for NG or LPG use. To convert a unit already in field service
to a different gas, the proper conversion kit must be purchased. The manifold pressure is set
at the factory on an individual heater basis. This setting must be checked after
field installation.
Summary of Contents for C225
Page 21: ...PNEG 308 Purafire 21 6 Wiring Diagrams 120V Models Figure 6A...
Page 22: ...22 PNEG 308 Purafire 6 Wiring Diagrams 220V Models Figure 6B...
Page 23: ...PNEG 308 Purafire 23 7 Wiring Harness Wiring Harness Assembly Figure 7A...
Page 32: ...32 PNEG 308 Purafire 11 Parts List C225 NG LP Galv Purafire 120V 60 Hz...
Page 34: ...34 PNEG 308 Purafire 11 Parts List C225 X1 NG LP Galv Purafire 220V 50 60 Hz...
Page 36: ...36 PNEG 308 Purafire 11 Parts List C80M NG LP Galv Purafire 120V 60 Hz...
Page 38: ...38 PNEG 308 Purafire 11 Parts List C80M X1 NG LP Galv Purafire 220V 50 60 Hz...
Page 56: ...56 PNEG 308 Purafire NOTES...