Culligan Hi-Flo

®

 3 Softener Engineer’s Specification

Page 4

¨

 

(Meter Initiated alternating system ONLY)

One remote mounted mechanical turbine-type meter will be provided.

The meter provided shall be 2.0 inches, compatible with the specified piping. It will be designed to allow ease of
removal of the turbine for inspection without modification of the piping system. The meter will be electrically
connected to the cycle timer.

The meter provided shall be functional within the flow range of 3 to 130 gpm and will be provided with a
threaded tee meter fitting.

4.5

EXCHANGE RESIN
The ion exchange resin shall be virgin high capacity “standard mesh” of sulfonated polystyrene type stable over
the entire pH range with good resistance to bead fracture from attrition or osmotic shock. Each cubic foot of
resin will be capable of removing 30,000 grains of hardness as calcium carbonate when regenerated with 15
lbs. of salt. The resin shall be solid, of the proper particle size of 20-50 mesh, U.S. standard screen and will
contain no agglomerates, shells, plates or other shapes that might interfere with the normal function of the water
softener. The resin shall be manufactured to comply with the food additive regulation 21 CFR 173.25 as set
forth by the USFDA.

The system shall include _____ cubic feet of exchange resin per vessel and a total of _____ cubic feet of resin
for the system.

4.6

BRINE SYSTEM
Provide a complete brine system consisting of a plastic tank, salt platform, brine well, an automatic brine valve
and all necessary fittings for operation with the water softening system. The system shall consist of a combined
brine measuring and salt storage tank with salt platform. The tank will be sized ____ inches x _____ inches; the
system will include a total of _____ brine tank(s).

The brine tank will be equipped with a float operated non-corrosive field serviceable brine float valve for
automatic control of brine withdrawal and fresh water refill.

The brine valve will automatically open to admit brine to the resin tank during eduction and close automatically
providing positive shut-off to prevent air from entering the system. The brine valve will also regulate the flow of
soft water into the brine tank during refill. The brine valve works with the timed fill feature of the main operating
valve controls to admit the correct volume of fresh water to the brine tank in accordance with the salt dosage
setting on the controls. The brine valve will include a float operated safety shut-off valve as a back up to the
timed refill from the main operating valve control to prevent brine tank overflow.

4.7

ACCESSORIES

(All Optional selections)

4.7.1

¨

 

Water test kits for hardness tests will be supplied.

4.7.2

¨

 Pressure Gauges for hard water inlet and soft water outlet.

4.7.3

¨

 Sampling Cocks for hard water inlet.

4.7.4

¨

 Vacuum Breaker for protecting Fiberglass tanks from vacuum.

5.0

INSTRUCTIONS

_____ complete sets of installation, operating and maintenance manuals shall be provided.

6.0

FIELD SERVICE

The services of a factory authorized service representative can be made available to supervise, inspect and
provide operator training as required for initial start-up and system operation. Contact your local Culligan dealer
for service rates and scheduling.

7.0

WARRANTY

A single written warranty must be provided from the manufacturer of the water softener system covering
workmanship and materials.

Rev. 11/00

Summary of Contents for Automatic Water Softeners

Page 1: ...ine A single turn of dial sets correct amount dosage and capacity Dubl Safe Brine System Positive overfill protection Automatic refill control is backed up by shutoff float valve to minimize chance of...

Page 2: ...nts For dishwashing cleaning material savings scale reduction Car washes Quality results detergent and water heating savings scale reduction Light industry For process and make up water boiler and coo...

Page 3: ...tanks and one brine tank system Commercial Systems 2000 Culligan 1 800 CULLIGAN www culligan com Printed in USA 4 00 DCO 992587 SL 0074 Moore Part No 46944 Single Exchange Capacity1 Service Flow Rates...

Page 4: ......

Page 5: ......

Page 6: ...Series Hi Flo 3 automatic water softener will be to remove mineral hardness from a known water supply to a level not to exceed ________ mg l as determined by an accepted ASTM or EDTA test method when...

Page 7: ...em shall be of the single point diffuser type to dispense water laterally to avoid channeling within the resin bed 4 2 2 The lower distribution system shall be of the single point distributor type con...

Page 8: ...ted Parallel Twin Unit Each unit shall include a volumetric meter mechanically coupled to the timer control Upon exhaustion of either tank its control shall activate a motor drive that will immediatel...

Page 9: ...of a combined brine measuring and salt storage tank with salt platform The tank will be sized ____ inches x _____ inches the system will include a total of _____ brine tank s The brine tank will be eq...

Reviews: