![CTI 2550-A Installation And Operation Manual Download Page 35](http://html1.mh-extra.com/html/cti/2550-a/2550-a_installation-and-operation-manual_2693834035.webp)
C T I 2550-A Installation and O peration G uide
23
SPECIFICATIONS
Input Channels:
8 isolated input channels
Signal Range:
Unipolar: 0 to 5VDC, 0 to 10VDC, or 0 to 20mA
Bipolar: -5 to +5VDC, -10 to +10VDC, or -20 to +20mA
Update Time:
8WX mode: 4 mSec all channels
Digital Filtering Time Constant:
0.3 Sec
DC Input Resistance:
Voltage Mode: 680k
W
Current Mode: 250
W
DC Accuracy:
Voltage Mode: 0.1% of full scale from 0
/
to 60
/
C
Current Mode: 0.2% of full scale from 0
/
to 60
/
C
Resolution (8WX Mode):
Unipolar: 12 bit plus sign 0-5VDC range=1.25mV/step
0-10VDC range=2.5mV/step
0-20mA range=10
:
A/step
Bipolar: 11 bit plus sign +5 to -5VDC=2.5 mV/step
+10 to -10VDC range=5mV/step
-20 to +20mA range=10
:
A/step
Common Mode Range:
±
150 VDC, 130 VAC 50/60Hz
Common Mode Rejection:
>140db @ 60Hz (digital filtering disabled)
Normal Mode Rejection:
>40db @ 500 Hz
Connector:
Removable, standard Siemens® front face
connector #2587705-8006
Wire Gauge:
14-22 AWG
Input Protection:
Input ESD Protection: 20,000V
Overrange Protection: 100V
Isolation:
1500VDC channel-to-channel
1500VDC channel-to-PLC
Summary of Contents for 2550-A
Page 2: ...ii CTI 2550 A Installation and Operation Guide ...
Page 4: ...iv CTI 2550 A Installation and Operation Guide ...
Page 6: ...vi CTI 2550 A Installation and Operation Guide ...
Page 8: ...viii CTI 2550 A Installation and Operation Guide ...
Page 12: ...xii CTI 2550 A Installation and Operation Guide ...
Page 22: ...10 CTI 2550 A Installation and Operation Guide ...
Page 34: ...22 CTI 2550 A Installation and Operation Guide ...
Page 38: ...26 CTI 2550 A Installation and Operation Guide ...
Page 39: ...CTI 2550 A Installation and Operation Guide 27 USER NOTES ...
Page 40: ...28 CTI 2550 A Installation and Operation Guide ...
Page 42: ...30 CTI 2550 A Installation and Operation Guide ...