CTI Janus Programmable Automation Controller IOG
Cable Distance
Cable distance depends upon the baud rate being used. See the following table.
Baud Rate
Segment Distance
Total Distance (All Segments)
9.6
–
93.75 Kb
1,200 m (3,930 ft)
12,000 m (39,300 ft)
187.5 Kb
1,000 m (3, 280 ft)
10,000 m (32,800 ft)
500 Kb
400 m (1,310 ft)
4,000 m (13,100 ft)
1.5 Mb
200 m (660 ft)
2,000 m (6,600 ft)
3 to 12 Mb *
100 m (330 ft)
1,000 m (3,300 ft)
*
Baud rates greater than 1.5 Mb require special connectors and repeaters.
7.2.2
Configuring a Profibus DP Network
The Profibus DP network is configured using
Janus Workbench
. See the
Janus Workbench
help for a complete
description of the configuration and operation of the Profibus network.