2500C-2572-B Quick Start Guide (62-466-010

Page 5

 

F

LASHING 

G

REEN

 if no duplicate has been detected. While in the state, you can access the module web server pages 

only.  

 

Once the PLC successfully initiates the Start Network Services command, the module will begin using the IP 

parameters specified in the command and will enable all module network services. The MSD should display the IP 

address and subnet mask (in CIDR format) specified by the PLC logic. The NS LED should be S

TEADY 

R

ED

 if a duplicate IP 

address is detected; otherwise, the NS LED should be S

TEADY 

G

REEN

.  If the module is not in this state, see the 

CTI 2572-

B Installation and Operation Guide

 for troubleshooting instructions.  

Entering the Module into the PLC I/O Configuration 

If you want to use PLC logic to monitor and/or control the module operation, you must enter the 2572-B into the PLC 

I/O configuration using your PLC programming application. The 2572-B is configured as a Special Function module with 

2 WX and 6 WY words.  In the following example, the 2572-B module is installed into slot 1 on I/O base 0 (local base) 

and will be logged in starting at address 1.     

 

 

 

After you read the I/O base, if the number of WX and WY words are the same as those shown in the example above 

and Special function = YES, then the PLC can recognize the module.  Change the address as required by your 

application and save the result.  If the line is blank or erroneous, re-check the module to ensure that it is firmly seated 

in the I/O base slot.  Generate the PLC I/O configuration chart again by reading the I/O base.  If the problem persists, 

contact your distributor or CTI customer support.  

 

NOTE: 

The module must be configured in the I/O table before you can use PLC logic to start the module, monitor 

the module status, or control the module operation. 

 

Storing Network Parameters in Flash 

If you have selected the AutoStart option (SW4), you will need to manually set the IP parameters to correspond to 

your networking requirements.  

 

The 2572-B IP Parameters can be set using the embedded web server. Point your browser to the main Product 

Information page by entering the IP address of the 2572-B module in the browser URL field. From the list of pages on 

the left hand side of the page, select the M

ODULE 

C

ONFIGURATION

 page. When the configuration page is displayed, enter 

the new IP address information in the appropriate fields and press the Update Module button.  

 