The Vecto III records both voltages and currents of a single 3-phase feeder with IEC
61000-4-30 Class A performance.
•
Voltage inputs:
•
Class A performance over all of the input range inclusive of 63.5 V (if L-N
measurements are done in a 110 V line-line VT circuit)
•
6 terminals are used for 4 voltage input channels with maximum input
ratings of 600 V.
o
The first 4 terminals connect 3 different phase voltages such as in a
3-phase system.
o
Input channel 1-3 is referenced to a neutral (4
th
terminal)
connection. This 4
th
terminal acts as a reference channel and can be
any phase voltage if a 3-phase line-line voltage circuit is measured.
o
If it is a 3-phase line-neutral voltage circuit, then the 4
th
terminal
will be connected to the neutral voltage.
o
The 5
th
and 6
th
terminal is the 4
th
channel and a fully differential (2
terminal) input channel.
•
Current inputs:
•
4 X 1/5 A CT inputs
•
4 X 1 V
rms
differential voltage transducer inputs with a 5 V power supply
(to be used to power Rogowski coils).
•
Digitisation of input signals
•
500 kHz sampling of primary input signals.
•
50 kHz is digitally retained and subjected to the IEC 61000-4-30 Class A
signal processing requirements.
•
Power supply
•
PoE and/or a 90-300 V AC/DC power factor corrected power supply.
•
1/2 hour power failure ride-through via an internal LiFePO
4
battery.
•
Data storage
Summary of Contents for Vecto III
Page 63: ...Vecto III User Manual 63 Figure 33 CT circuit connection layout...
Page 70: ...Vecto III User Manual 70 Appendices 1 Vecto III dimensions...
Page 71: ...Vecto III User Manual 71 2 Vecto III wiring diagram...
Page 72: ...Vecto III User Manual 72 3 Vecto III Top View...
Page 74: ...Vecto III User Manual 74 2964 2197 2569 3541...
Page 76: ...Vecto III User Manual 76 2964 2197 2569 3541 1084...
Page 78: ...Vecto III User Manual 78 2934 1084 3539 2431 2951 2487 2964 2535 2486 2571 2488 2344 2346 2600...