![CSW RTP Series Product Instructions Download Page 2](http://html1.mh-extra.com/html/csw/rtp-series/rtp-series_product-instructions_2693049002.webp)
Page 2 of 3
RTP SERIES
Condensate Removal Pumps
ELECTRICAL CONNECTIONS
AVERTISSEMENT
ADVERTENCIA
ATTENTION
PRECAUCIÓN
1. Shut off electrical power at fuse box before making any connections. All wiring must comply with local codes.
2. Line voltage: Connect power cord to line voltage specified on motor and nameplate. Power cord must be connected to a constant
source of power (not a fan or other device that runs intermittently). If power cord does not have a plug, wiring is as follows: green
(or green/yellow)—ground. Black (or brown)—line. White (or blue)—neutral.
3. Safety switch: The safety overflow switch should be connected to a class II low voltage circuit. To control a thermostatic circuit the
COM and NC connections from the safety switch are to be wired in series with the low voltage thermostat circuit to shut down the
heating/AC circuit. The COM and NO switch contacts may be used to actuate a low voltage alarm circuit (connected in series) if the
heating/cooling system cannot be disrupted. The safety switch comes from the factory with leads connected to the COM and NO
switch terminals. Typical hook-up of “NC” circuits would be (Figures 2 & 3).
4. If fused plug is used on 230 V units, a 1.0 amp fuse is recommended (not included in the package).
PIPING
1. Run flexible tubing or pipe from evaporator drain into one of the three pump inlets. Be sure inlet piping is sloped downward to
allow gravity flow (Figure 4). Extend the inlet piping into the tank from 1 to 3 inches to ensure that it will not interfere with proper
float operation. Be sure that the inlet piping is cut at an angle where it enters the tank.
2. The outlet piping should be flexible tubing secured with a hose Clamp (not provided) or pipe (3/8 inch ID. maximum to prevent
excessive flow back to unit). From condensate unit, extend discharge piping straight up as high as necessary. Do not extend this
line above the head/GPH of the particular model being installed. From this high point, slope discharge line down slightly to a point
above drain area; then turn down and extend to a point below or approximately level with the bottom of the condensate unit. This
will give a siphoning effect which will improve efficiency of the condensate unit and will, in most cases eliminate the need for a
check valve (Figure 5). If it is not possible to slope discharge line down, make an inverted “U” trap directly above the pump at the
highest point.
SERVICE INSTRUCTIONS
AVERTISSEMENT
ADVERTENCIA
ATTENTION
PRECAUCIÓN
1. Make certain that the unit is disconnected from the power source before
attempting to service or remove any component!
2. Be sure the floats move freely. Clean as necessary (Figure 6).
3. Clean the tank with warm water and mild soap.
4. Check the inlet and outlet piping. Clean as necessary. Be sure there are no
kinks in the line that would inhibit flow.
TESTING
1. Turn on power.
2. Remove motor/tank cover assembly and hold level.
3. Test motor switch by raising motor switch float with finger (Figure 6).
Motor should turn on just before float contacts cover.
4. Test safety switch by raising safety switch float with finger. Safety switch
should activate before float contacts cover.
5. Replace motor/tank cover assembly on tank.
This pump is suitable for gas furnace condensate applications. Caution
must be taken to ensure acidity of condensate does not increase below the
average pH of 3.4 (to prevent localized pocket of acid that acts like a battery
causing pitting) by routinely cleaning or flushing tank with fresh water.
Motor switch float
Safe-T-Switch float
Figure 6
Figure 7