1.  To assure proper installation, measure the voltage on 

each phase and ensure the correct device is installed. 

2.  Turn off power to the circuit where surge protector is to 

be installed.

3.  Mount device to keep conductor length as short as 

possible. Cut wires to length and connect to circuit per 

wiring diagram below avoiding sharp bends or looping.

4.  Splice the included Rectorseal RSH60-VMD 24V 

thermostat control wires into the Y1 terminal 

thermostat wire. 

5.  Reinstall covers, restore power and confirm diagnostic 

LED is illuminated.

ALTERNATIVE WIRING METHOD:

This SPD can be also be installed by splicing into the wires of the 

WIP, within the disconnect box or by using a double lug adapter.

Device Ratings

Normal Voltage

Per Leg

Max. Operating Voltage 

(MCOV) Per Leg

Max. Discharge 

Current (IMAX)

120 VAC

150 VAC

60kA

240 VAC DIAGRAM 

Split-Phase System: 1 Ph, 2W + G

240 VAC 2-Pole

Disconnect Diagram

Para instrucciones en español visite 

www.rectorseal.com 

Technical Support Call 1-800-648-6802

 

All surge protection devices require a good ground connection for effective operation

Black

Black

Green

Ground

120 VAC DIAGRAM 

Single-Phase System: 1 Ph, 2W + G 

BL

ACK

GREEN

BL

ACK

120 VAC

RSH-60 VMD

24 VAC

Y1

Y1

BL

ACK

GREEN

BL

ACK

RSH-60 VMD

24 VAC

Y1

Y1

240 VAC

120 VAC

120 VAC

LINE 2

LINE 1

LED VERDE

CONDICIÓN

LED ROJO

ALARMA AUDIBLE

Protección contra

sobretensiones
Sin protección contra

sobretensiones

Bajo Voltaje

Protección de ciclo corto

ENCENDIDO

APAGADO

––

DESTELLO

APAGADO

ENCENDIDO

––

––

––

––

ENCENDIDO

––

Diagnostic Operations

GREEN LED

CONDITION

RED LED

AUDIBLE ALARM

Surge Protection

No Surge Protection

Under Voltage

Short Cycle Protection

ON

OFF

––

OFF

ON

––

––

––

––

ON

LED VERT

ÉTAT

LED ROUGE

ALARME AUDITIVE

Protection Contre

Les Surtensions
Non Protection Contre

Les Surtensions
Sous Tension

Protection Du

Cycle Court

ALLUMÉ

ÉTEINDRE

––

FLASH

ÉTEINDRE

ALLUMÉ

––

––

––

––

ALLUMÉ

––

Opérations de diagnostic

Operaciones de diagnóstico