HV Breakout Module – Mounting and installation
Installation Manual
14
Version 01.20 // 2021
HV BM 3.1: Connecting the HV power cable to the module
As for the HV BM 3.1, the HV power cables are connected to the module by using Phoenix
terminals. The cable cross-section may not exceed 6 mm² each. The stripping length is
12 mm. The wires can be fitted with wire end sleeves, but it is not absolutely necessary.
4.3.2 Preparing the PG gland
"
Loosen the four pressure screws using an
adequate wrench and remove them from
the threads.
Some PG cable glands are equipped with a two-
component silicone sealing insert (blue) and a
removable inlet.
The sealing insert has a specific sealing area (cable
diameter) with and without inlet. This is marked
accordingly (in Fig. 4-5: 25-20 mm and 20-15 mm).
"
Remove the sealing insert and cut out the
inlet if required.
The following PG gland types are available:
CSM type
9/14
11/20
15/25
CSM article number
ART1520202
ART1520201
ART1520200
Pflitsch designation
bg 220ms tri /sc
bg 225ms tri /sc
bg 232ms tri /sc
Sealing range without
inlet
9 – 14 mm
16 – 20 mm
20 – 25 mm
Sealing range with inlet
—
11 – 16 mm
15 – 20 mm
Connecting thread
M20
M25
M32
Wrench width
SW24
SW30
SW36
Tightening torque
6
max. 10 Nm
max. 15 Nm
max. 15 Nm
Tab. 4-1: Technical data of the PG glands used
6 For tightening torques and further manufacturer information, see
https://www.pflitsch.de/fileadmin/user_upload/Downloads/
Kataloge/Blueglobe_Katalog_2014_web.pdf
, p. 74.
Fig. 4-5: PG glands opened