PWM-C Transducers Installation Sheet

TCON172 06/97

 

P.O. Box 59469, Dallas, TX 75229
Phone: (972) 323-1111     FAX: (972) 242-0026

 

 

 1997 by Control Systems International. 

Control Systems

International

®

 

Specifications

 

Dimensions ................................................... 3.25" W 

 

×

 

 4.0" L

................................................................... (8.25 

 

×

 

 10.2 cm)

Snap-track dimensions.................................. 3.5" W 

 

×

 

 4.0 " L

..................................................................... (8.9 

 

×

 

 10.2 cm)

Input pulse duration ................................... 0.1–25.6 seconds

or ................................................................ 0.1–5.2 seconds

Input pulse resolution ..................................................... 0.4%

Resolution counts .......................................................... 0–255

Input interface

................... Dry contact, triac or open collector transistor

Input excitation voltage............................................+15 VDC

........................................................ (continuous or pulsed)

Output current range:

PWM-C1............................................................... 4–20 mA
PWM-C2............................................................... 0–20 mA

Output excitation voltage........................................13.5 VDC

..................................... (675 

 

 

 maximum loop resistance)

Linearity .............................................................. 1% full scale

Operating temperature.......................... 32–132

 

°

 

 F (0–50

 

°

 

 C)

Relative humidity..........................10–90% (noncondensing)

Supply voltage .......................................24–35 VDC @ 75 mA

or .....................................18–28 VAC @ 150 mA, 50/60 Hz

Engineering Coefficients (input range 0.1–5.2 seconds):

M (slope)................................................................. 0.19608
B (intercept)...........................................................-1.96078

Engineering coefficients (input range 0.1–25.6 seconds):

M (slope)................................................................. 0.03922
B (intercept)...........................................................-0.39216

 

Note:

 

These M and B coefficients apply to 0–100% input source 
range.

 

Figure 1.

PWM-C Series Wiring Diagram

Remove both R27 and

Input

Power

Clock

3.5" Width

4.0" Length

J2

5

Sec

Sec

25

R27

D5

Red LED Indicates Detection
Of Pulse Input

Green Flashing LED indicates
Power and Clock Rate

5 Sec/25 Sec

Pulse Width

Selection

Remove R27 for MR
or I/SITE triac input.

– Common (Ground)

+ Current Output to

+24 V

– GND

24V Supply

Polarity

Indication

Applies if DC

Supply Is Used

Common (Ground)

Connection When
Triac or Transistor

Output Is Used

Pulse Width

Modulated

Output Using

Normally-Open

Relay Contact

or

Open Collector

Transistor

or Triac

CONTROL UNIT

Device Under Control

D5 for UC triac input.

1

V

2

G

3

I

4

O

5

G

0.47 µf

Install 0.47 µf capacitor
across terminals 2 and 3
if used with MR-VAV-AX.

1

V

2

G

3

I

4

O

5

G