Installation Instructions

Note:

When grounding equipment, ensure that 
you use a good earth ground. Otherwise, 
operational errors may occur.

1. Ensure power is disconnected from the 

I/STAT-LCD and from all devices that will 
be connected to the I/STAT-LCD.

Warning:

Failure to disconnect power from all 

interconnected equipment when per-
forming electrical installation may result 
in electrical shock or burns.

2. Mount the I/STAT-LCD base to a wall-

mounted, standard electrical utility box 
no more than 100 feet (30 m) from the 
controller.

3. Connect a 22-AWG (0.324 mm

2

), 

shielded, twisted-pair cable (Belden 9184) 
from the controller’s I/STAT port to ter-
minal block TB1 on the I/STAT-LCD as 
follows:

a. Connect the DATA wire from the con-

The following figure shows the I/STAT-LCD, 
its dimensions, its mounting-hole locations, 
and the electrical connections required to 
connect it to a controller. 

 2.75" 

 (6.98 cm) 

Front

Back

 4.50" 

TB1

1

2

3

DATA

+12 VDC

GROUND

1

2

3

TB1

TBx

I/STAT-LCD

MR, ASC, 7728,

or NetPoint device

2.38"

2.38"

2.38"

(6.03 cm)

(6.03 cm)

(6.03 cm)

(8.38 cm)

(8.38 cm)

(8.38 cm)

3.30"

3.30"

3.30"

0.60" (1.52 cm)

0.60" (1.52 cm)

0.60" (1.52 cm)

0.60" (1.52 cm)

0.60" (1.52 cm)

0.60" (1.52 cm)

(11.43 cm)

(11.43 cm)

(11.43 cm)