I/DISC Reader
Installation Guide
24
CSI Readers
4.
Connect the white (DATA 1) wire from the PIN pad to terminal 3 on the breakout
box or DPU.
5.
Connect the green (DATA 2) wire from the PIN pad to terminal 5 on the breakout
box or DPU.
6.
Connect the brown (LED GREEN) wire from the PIN pad to terminal 7 on the
breakout box or DPU.
7.
Connect the tan (CHASSIS GROUND) wire from the PIN pad to a good earth
ground.
8.
From a host workstation, configure I/NET to use the ESSEX PIN pad. Common
settings are:
✧
Reader Type:
–
I/DISC w/PIN
(I/NET version 4.x and I/NET 2000 version 1.x)
–
I/DISC
(I/NET 2000 version 2.x and later)
✧
PIN Pad
(I/NET 2000 version 2.x and later only):
Activated
✧
LED Polarity: Anode
✧
Door Mode Schedule:
–
“PIN Enable” to require both an I/DISC read and PIN entry
–
“Secure” to require an I/DISC read only
✧
Key/Card Translation: Perform these translations as necessary using the I/NET
Key/Card Translations editor.
Refer to the I/NET 2000 System Operator Guide or Technical Reference Guide for more
information concerning I/NET 2000.