Sensors are not reading the correct temperature
•
Go to the chiller status screen and scroll down to “Loop Water Out” to see the temperature of the supply
sensor and compare it to the actual temperature of the outlet pipe
•
First thing to check is to tighten all of the connections on the terminal strip on the circuit board
•
Unplug sensor out of the wire harness and ohm it out
per chart
•
If sensor is bad, borrow the common loop supply
sensor to replace it till you get a new one.
•
Sensor is a negative temperature coefficient thermistor
•
Resistance decreases with temperature increase