background image

 

INSTALLATION INSTRUCTIONS  

S W A N   1 0 0 0    

 PASSIVE INFRARED & MICROWAVE DETECTOR With PET IMMUNITY  

 

 

PRODUCT FEATURES

PRODUCT FEATURES

PRODUCT FEATURES

PRODUCT FEATURES 

A new generation of professional movement 
spread spectrum analyzing PIR & MW 
detectors with PET immune function. 

The Swan 1000 is a combination of PIR & MW 
detectors, providing protection from intruders by PYRO 
sensor element and MW (based on Doppler concept).  
Using micro controller for PIR & MW signal analyzing, 
with special ASIC technology for PIR pulse processing, 
assures “false alarm free” operation. 

 

Quad (Four element) PYRO sensor and hard 
lens for outstanding detection performance and 
elimination of false alarms. 

 

Microwave detection based on Doppler concept. 

 

Unique Microwave Motion Sensor Module with 
microstrip patch antenna. 

 

VLSI based electronics with movement speed 
spectrum analysis. 

 

Height installation calibrations free. 

 

User-friendly installation with or w/o swivel 
bracket. 

 

2-way Microwave sensitivity adjustment. 

 

2-way PIR sensitivity adjustment. 

 

Bi directional temperature compensation. 

 

Environmental immunity. 

 

The Swan 1000 provides 

pet immunity

 up to 

25Kg. Pet active bellow 1m. 

SELECT MOUNTING LOCATION 

Choose a location most likely to intercept an intruder. 
(Our recommendation is a corner installation). See 
detection pattern – fig.4. The quad-element high 
quality sensor detects motion crossing the beam; it is 
slightly less sensitive detecting motion toward the 
detector. 
Recommended mounting height – 1.8m-2.4m. 

 

AVOID THE FOLLOWING LOCATIONS 

  Facing direct sunlight. 

  Facing areas that may change temperature 

rapidly. 

  Areas where there are air ducts or substantial 

airflows. 

The Swan 1000 performs better when provided with a 
constant and stable environment.  

 

 

 

DETECTOR INSTALLATIO

DETECTOR INSTALLATIO

DETECTOR INSTALLATIO

DETECTOR INSTALLATION

N

N

N

 

The detector can either be wall or corner mounted.   
If ceiling or special wall mounting is required, use the 
optional bracket base. Refer to bracket description.   
(See fig. 7). 

1. To remove the front cover, unscrew the holding screw 

and gently raise the front cover. 

 
 

Fig.1 

2.  To remove the PC board, carefully unscrew the 

holding screw located on the PC board. 

3.  Break out the desired holes for proper installation.  

 

Fig. 2

 

4. The circular and rectangular indentations at the 

bottom base are the knockout holes for wire entry. 
You may also use mounting holes that are not in use 
for running the wiring into the detector.(For option 
with bracket - lead wire through the bracket – fig.7) 

5. Mount the detector base to the wall, corner or ceiling. 

(For option with bracket  see fig.7). 

6. Reinstall the PC board by fully tightening the holding 

screw. Connect wire to terminal block. 

7. Replace the cover by inserting it back in the 

appropriate closing pins and screw in the holding 
screw. 

 

 

DETECTOR CONNECTION

DETECTOR CONNECTION

DETECTOR CONNECTION

DETECTOR CONNECTION 

 

Terminal 1 - Marked “ - ” (GND) 

Connect to the negative Voltage or ground of the 
control panel. 

Terminal 2 - Marked “ + ” (+12V) 

Connect to a positive Voltage  of 8.2 -16Vdc source 
(usually from the alarm control unit) 

Terminals 3 & 4 - Marked “ TAMP ”  

If a Tamper function is required connect these 
terminals to a 24-hour normally closed protective zone 
in the control unit. If the front cover of the detector is 
opened, an immediate alarm signal will be sent to the 
control unit. 

Terminals 5 & 8 - Marked “ EOL ” – 

End of line option. 

Terminals 6 & 7 - Marked 

 RELAY 

 

These are the output relay contacts of the detector. 
Connect to a normally closed zone in the control panel. 

TESTING THE DETECTOR 

Wait for one minute warm up

 

time after applying  

12 Vdc power. Conduct testing with the protected area 
cleared of all people. 

 Walk test

 

1.  Remove front cover.                                              

      Set LED to ON position. 

2.  Reassemble the front cover. 
3.  Start walking slowly across the detection zone. 
4.  Observe that the red LED lights whenever motion is 

detected. 

5.  Allow 5 sec. between each test for the detector to 

stabilize. 

6.  After the walk test is completed, you can set the LED 

to OFF position. 

NOTE:

  

Walk tests should be conducted, at least once a year, 
to confirm proper operation and coverage of the 
detector. 

Fig.3

 

 

 

 

 
 

 

 

 

Fig.4 

 

 

 

 

 

 

 

 

Table 1: 

##

0

1

2

3

4

5

6

7

8

9

10

a

180°

130°

100°

84°

75°

70°

60°

52°

40°

30°

20°

X

0

3

6

9

12

15

18

21

24

27

28,5

Y

10,5

6,09

7,15

6,98

8,01

10,5

10,39 10,24

8,73

7,23

5,03

 

X,Y are corresponds (m) of pattern points when H=30m 

 

Fig.5 

      7101572_D 

 

  

 

 

                          - 1 - 

 

 

 

 

 

    

Holding screw 

 

A.  Wire access holes 
B.  Use for flat wall 

mounting 

C.  Corner mounting - 

use all 4 holes. 
Sharp left or right 
angle mounting - 
use 2 holes (top 
and bottom) 

D.  For bracket 

mounting 

 

 

H

0

2

1

3

4

5

6

7

8

9

10

 

Reviews: