Crouse-Hinds MTL F300 Instruction Manual Download Page 11

7

INM F300 rev 6

DRAFT - 09 July 2019

DRAFT - 09 July 2019

ATEX SAFETY INSTRUCTIONS

The following information is in accordance with the Essential Health and Safety 
Requirements (Annex II) of the EU Directive 2014/34/EU [the ATEX Directive - safety of 
apparatus] and is provided for those locations where the ATEX Directive is applicable.

8 .1  General

a)  This equipment must only be installed, operated and maintained by competent 

personnel. Such personnel shall have undergone training, which included instruction 
on the various types of protection and installation practices, the relevant rules 
and regulations, and on the general principles of area classification. Appropriate 
refresher training shall be given on a regular basis. [See clause 4.2 of EN 60079-17].

b)  This equipment has been designed to provide protection against all the relevant 

additional hazards referred to in Annex II of the directive, such as those in clause 1.2.7.

c)  This equipment has been designed to meet the requirements of EN 60079-15.

8 .2  Installation

a)  The installation must comply with the appropriate European, national and local 

regulations, which may include reference to the code of practice EN 60079-14. In 
addition, particular industries or end users may have specific requirements relating 
to the safety of their installations and these requirements should also be met. For 
the majority of installations the Directive 1999/92/EC [the ATEX Directive - safety of 
installations] is also applicable.

b)  This apparatus may be installed in a safe area and also in a Zone 2 location 

providing that the relevant installation conditions are met. When mounted in a 
Zone 2 location the apparatus must be provided with an enclosure, which offers an 
additional degree of protection appropriate to the area classification.

c)  Unless already protected by design, this equipment must be protected by a 

suitable enclosure against:
i)  mechanical and thermal stresses in excess of those noted in the certification 

    documentation and the product specification  

ii) aggressive substances, excessive dust, moisture and other contaminants.

Read also the Special Conditions for Safe Use (below) for any additional or more 
specific information.

Special Conditions of Safe Use for Zone 2 applications

Ex nA IIC T4 Gc and Ex nA [ic] IIC T4 Gc

1.  The apparatus is to be  installed  in an enclosure which maintains a minimum  

ingress protection rating of IP54 and meets the enclosure requirements of EN 
60079-0, EN 60079-11 and EN 60079-15.

2.  Provisions shall be made externally to the apparatus  to prevent the rated input 

being exceeded by transient disturbances of more than 140% of the rated voltage.  

See footnote.

FISCO Ex ic IIC T4 Gc

1.  The apparatus is to be  installed  in an enclosure which maintains a minimum  

ingress protection rating of IP54 and meets the enclosure requirements of 

 

EN 60079-0 and EN 60079-11.

Note: All MTL fieldbus power supplies are designed to protect the fieldbus trunk from transient 
disturbances on the DC power feed and will meet the requirements of maintaining transient 
disturbances below 140% of the rated voltage.

Summary of Contents for MTL F300

Page 1: ...F300 megablock range MTL fieldbus device couplers July 2019 INM F300 rev 6 Instruction manual MTL fieldbus networks DRAFT 09 July 2019...

Page 2: ...19 Declaration of Conformity A printed version of the Declaration of Conformity has been provided separately within the original shipment of goods However you can find a copy of the latest version at...

Page 3: ...5 ELECTRICAL CONNECTIONS 3 5 1 DC Power Requirements 4 5 2 Terminator 4 5 3 Trunk connections 4 5 4 Spur port connections 5 5 5 Cable screen connections 5 5 6 Surge protection 5 6 TESTING 6 6 1 Power...

Page 4: ...ontents of this manual and the product datasheet Ensure installation and operating personnel have received adequate training for this task Ensure that any operating instructions are fully understood b...

Page 5: ...n also be fitted to any of the Megablock fieldbus terminals to provide protection against induced surges and transients that can potentially destroy or degrade certain components inside the F300 Megab...

Page 6: ...ing bars for F312 pack of 10 The standard connector for the Megablock is a pluggable screw terminal elevator type Pluggable spring clamp connectors rely on constant spring pressure to maintain contact...

Page 7: ...r the ledge of the DIN rail Push the Megablock against the edge of the rail then rotate the Megablock until it sits flat onto the DIN rail then release the pressure to allow the clips on the other sid...

Page 8: ...minator so that the T F97 molded logo is facing inwards towards the body of the Megablock otherwise difficulty will be experienced in accessing the spring clamp buttons to remove it For screw terminal...

Page 9: ...onnector provides and cable screen S connections See section 5 5 for information on cable screen grounding Cable screen connections The S screen terminals for the trunk and the spurs are interconnecte...

Page 10: ...e FS32 and tighten its securing screws 7 Repeat 5 and 6 for all the other FS32 modules A separate grounding bar F300 BAR is used for the trunk connector which must be similarly connected to ground see...

Page 11: ...is also applicable b This apparatus may be installed in a safe area and also in a Zone 2 location providing that the relevant installation conditions are met When mounted in a Zone 2 location the app...

Page 12: ...epair This product cannot be repaired by the user and must be replaced with an equivalent certified product NOTE All MTL fieldbus power supplies are designed to protect the fieldbus trunk from transie...

Page 13: ...t used if the F3xx contains an internal Terminator T part number suffix FM CONTROL DRAWING FOR F3XX MEGABLOCK SERIES FIELDBUS CONNECTION BLOCKS CID2 Zone 2 INSTALLATIONS Doc No 502 484 Rev C 0 Sheet 1...

Page 14: ...nator Installation DIN Rail Mounting F3xx Megablocks are designed to be mounted on 35 mm DIN rail using the clip mechanism on the back of each unit Mounting can be vertical or horizontal Use of DIN ra...

Page 15: ...o the apparatus to prevent the rated input being exceeded by transient disturbances of more than 140 of the rated voltage See footnote FISCO Ex ic IIC T4 Gc 1 The apparatus is to be installed in an en...

Page 16: ...vided by Power Source or Power Supply Sheet 1 of 4 If the Fieldbus Power Supply is protected by a type of protection listed in IEC 60079 0 it may be installed in the Hazardous Area Megablock Part Numb...

Page 17: ...EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT except gray spurs Gas Groups IIC IIB IIA C o 80nF 80nF 80nF L o 0 15mH 0 26mH 0 26mH CONTROL DRAWING...

Page 18: ...ved by Cyrus Kelly Date 10 FEB 2017 Doc No 502 485 Rev E 0 Device Inductance 0 10 H Device Capacitance 0 5nF FISCO ic FNICO Installation Requirements Sheet 3 of 4 Installation to comply with IEC 60079...

Page 19: ...ide in the two channels on each side of the F3xx until they latch in place at the bottom of the case The channels are sized differently so the Partition cannot be installed backwards If needed the F97...

Page 20: ...u Street Off Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91 0 44 24501463 E mail mtlindiasales eaton com ITALY MTL Italia srl Via San Bovio 3 20090 Se...

Reviews: