1. NA-9161 Specification 

1-2. Technical Specification   

1-1. General Specification   

FieldBus Input/Output System 

 

CANopen Network Adapter 

 PROFIBUS  Network Adapter 

 Digital Input / Output 

 Analog  Input / Output 

 Special Module 

Quick Guide  

NA-9161 

FnIO S-series 

* Specifications and designs could be changed without advance Notice 

Class 2, adjacent to voltage rating (30Vmax.) 

Cautions for your Safety 

Do not assemble the products and wire with power applied to the system. Else it may cause an electric arc, which can result into unexpected 
and potentially dangerous action by field devices. Arching is explosion risk in hazardous locations. Be sure that the area is non-hazardous or 
remove system power appropriately before assembling or wiring the modules. 

Do not touch any terminal blocks or IO modules when system is running. Else it may cause the unit to an electric shock or malfunction. 

Keep away from the strange metallic materials not related to the unit and wiring works should be controlled by the electric expert engineer. 
Else it may cause the unit to a fire, electric shock or malfunction. 

If you don’t follow the directions, it could cause a personal injury, damage to the equipment or explosion 

If you disobey the instructions, there may be possibility of personal injury, damage to equipment or  
explosion. Please follow below Instructions. 

   Check the rated voltage and terminal array before wiring. Avoid the circumstances over 55

 of temperature. Avoid placing it directly in the  

      sunlight.  

   Avoid the place under circumstances over 85% of humidity.  

   Do not place Modules near by the inflammable material. Else it may cause a fire. 

   Do not permit any vibration approaching it directly.  

   Go through module specification carefully, ensure inputs, output connections are made with the specifications. Use standard cables for wiring.  

   Use Product under pollution degree 2 environment. 

Before using the unit                                                                        

*We appreciate you for purchasing CREVIS Products. To use the units more effectively, please read this quick guide and refer to 
the respective user manual for further details. 

Warning

Caution! 

* Power Isolators must be used according to the usage of 5VDC/24VDC/48VDC or AC Voltage modules 

ITEM 

SPECIFICATION 

ITEM 

SPECIFICATION 

Surrounding Air 

Temp./  

Ambient Temp. 

-20

~55

 / -40

~85

 

Network Type 

CANopen 

Relative  

Humidity 

5% ~ 90% without condensation 

Cable 

 CANopen Special Cable 

Durable-vib. 

/impact 

IEC68-2-6(2G) / 10G 

Cable Length 

25 m  ~  5km, Depending on Baudrate  

EMC/ESD 

EN50082 / EN50081 

Comm. Sp 

10 Kbps ~ 1Mbps 

Mount Position 

On the left of FnIO-S series 

Station Type 

CANopen Slave 

Atmosphere 

Not so dusty without corrosive gas 

Max. Station No. 

Max. 32 Module 

Field Supp.Volt. 

Class 2, 24VDC 

24VDC (11VDC ~ 28.8VDC)

‏ 

Number of PDOs 

available  

8 Transmit PDOs / 8 Receive PDOs 

Field Supp. Cur. 

Max. 10A 

Number of SDOs 

available 

1 Standard SDOs 

FnBus Sup. Cur 

Max. 1.5A@5Vdc 

Peripheral signal 

Input 64 bytes / Output 64 bytes 

Baud rate Setting 

Support Auto-baudrate 

Station Type 

CANopen Slave 

Size 

45mm 

×

 99mm 

×

 70mm 

Node address Set. 

Rotary S/W  #1, #2 (x10, x1) 

Weight 

155g 

Power Dissipation 

100mA 

Certification 

FCC / UL / cUL / CE / RoHS(EU,China) 

Summary of Contents for FnIO S Series NA-9161

Page 1: ...s 99 Node Max Class2 24VDC 24VDC 11VDC 28 8VDC Peripheral signal Input 64 bytes Output 64 bytes 10A Number of PDOs available 8 Transmit PDOs 8 Receive PDOs FnBus 1 5A 5Vdc Number of SDOs available 1 S...

Page 2: ...2 1 Wiring of communication System power line for CanOpen 2 3 3 1 Din Rail 3 2 Din Rail Din rail Din Rail...

Page 3: ...data Passed the expansion module configuration Green FnBus Connection Run Exchanging IO Expansion Slot is connected and run exchanging I O data Red FnBus connection fault during exchanging IO One or...

Page 4: ...eptance S W 0 1 5 2 I O Process Image Map 5 1 Rotary switch 5 3 Bus Cable and Termination Resistors Bus length m Bus cable Termination resistance Baud rate Kbit s Length related Resistance m m Cross s...

Page 5: ...e Avoid placing it directly in the sunlight Avoid the place under circumstances over 85 of humidity Do not place Modules near by the inflammable material Else it may cause a fire Do not permit any vib...

Page 6: ...3 1 How to mount on Din Rail 3 2 How to dismount from Din Rail Pull down the locking mechanism by using screw driver as the following pictures Press down the module lightly on the Din Rail until it c...

Page 7: ...ansion module configuration Green FnBus Connection Run Exchanging IO Expansion Slot is connected and run exchanging I O data Red FnBus connection fault during exchanging IO One or more IO module occur...

Page 8: ...10KB Auto baud rate 2 Baud rate Setting The select S W can be set in the range from 0 to 8 The Acceptance S W can be set in the range from 0 to 1 5 2 I O Process Image Map 5 1 Rotary switch 5 3 Bus Ca...

Reviews: