DIN Rail Control Processor
Crestron
DIN-AP2
Connectors, Controls & Indicators (Continued)
# CONNECTORS
1
,
CONTROLS &
INDICATORS
DESCRIPTION
9
COM1 & COM 2
(2) 5-pin 3.5 mm detachable
terminal blocks, bidirectional
comprising (2) RS-232 ports
Max Wire Size: 1.5 mm
2
(16 AWG)
Up to 115.2k baud
Hardware and software
handshaking support
GND
: Ground
TX
: Transmit data
RX
: Receive data
RTS
: Request to send
CTS
: Clear to send
10
RELAYS
(1) 8-pin 3.5 mm detachable
terminal block comprising (4)
normally open, isolated relays
Max Wire Size: 1.5 mm
2
(16 AWG)
Rated 1 Amp, 30 Volts AC/DC
MOV arc suppression across
contacts
(Continued on following page)
10
•
DIN Rail Control Processor: DIN-AP2
Operations & Installation Guide – DOC. 6662A