Tab). Enter a new descriptive name in the “Enter Symbol Comment” dialog box and
click
OK
.
Detail View of a Analog Scaler (S-3) in SIMPL Windows’ Programming Manager
Detail View of a Analog Initialize Symbol (S-4) in SIMPL Windows’ Programming Manager
Detail View of a Analog Equate Symbol (S-5) in SIMPL Windows’ Programming Manager
The example SIMPL program is provided with a sixth logic symbol, Analog
Initialize. The purpose of this symbol is to initialize the value so that devices
receiving the analog signal do not exhibit drastic voltage swings upon start up or
reset. Implement this symbol only if the jumper is set to 50%. Also, replace the
input, “jumper-button”, with a logic constant, “1”.
10
•
CNX Analog Output Expansion Card: CNXAO-8
Operations Guide - DOC. 8142